2008-04-16 16:50:31PROJECT: 1910 PALM BEACH LAKES BLVD. / LAQUINTA HOTEL
  
 PROJECT DETAIL: SUBMITTAL FOR 6TH FLOOR ARCH WINDOW
 FRAMING MITIGATION
  
 CODE REVIEW:
  
 CODE REVIEW:
 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS
 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS
 CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION
  
 STATUS: FAILED
  
 COMMENTS:
  
 1) PLEASE SUBMIT WIND LOAD DESIGN CALCULATIONS AS PER
 THE FOLLOWING:
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2. WIND IMPORTANCE FACTOR, IW, AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M2) TO BE USED FOR THE SELECTION OF
 EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 2) PLEASE INDICATE THE EXISTING CONCRETE DESIGN
 STRENGTH FOR THE USE OF THE POWDER ACTUATED FASTENERS
 IF PAF'S ARE TO BE USED.
  
 3) PLEASE NOTE ON DRAWING: " 6TH FLOOR WINDOW
 ELEVATION" AND ADDRESS OF PROJECT WITHIN THE TITLE
 BLOCK.
  
  