2008-04-16 16:50:31 | PROJECT: 1910 PALM BEACH LAKES BLVD. / LAQUINTA HOTEL |
| |
| PROJECT DETAIL: SUBMITTAL FOR 6TH FLOOR ARCH WINDOW |
| FRAMING MITIGATION |
| |
| CODE REVIEW: |
| |
| CODE REVIEW: |
| 2004 FLORIDA EXISTING BUILDING CODE W/2006 REVISIONS |
| 2004 FLORIDA BUILDING CODE W/ 2006 REVISIONS |
| CITY OF WEST PALM BEACH AMENDMENTS 2004 EDITION |
| |
| STATUS: FAILED |
| |
| COMMENTS: |
| |
| 1) PLEASE SUBMIT WIND LOAD DESIGN CALCULATIONS AS PER |
| THE FOLLOWING: |
| |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| 2. WIND IMPORTANCE FACTOR, IW, AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M2) TO BE USED FOR THE SELECTION OF |
| EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 2) PLEASE INDICATE THE EXISTING CONCRETE DESIGN |
| STRENGTH FOR THE USE OF THE POWDER ACTUATED FASTENERS |
| IF PAF'S ARE TO BE USED. |
| |
| 3) PLEASE NOTE ON DRAWING: " 6TH FLOOR WINDOW |
| ELEVATION" AND ADDRESS OF PROJECT WITHIN THE TITLE |
| BLOCK. |
| |
| |
| PLAN REVIEW: KEN CONRAD |
| PHONE: 561.805.6666 |
| E-MAIL: KCONRAD @WPB.ORG |
| |