2008-04-22 11:06:01 | *****DENIED***** | | | | THE COMMENTS (NOT MARKED OK) FROM THE PREVIOUS FIRE | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | 1.STRUCTURAL CALCULATION COVER SHEET AND MEZZANINE | | SHEET 1 STILL SHOW 100 AS THE SUITE NUMBER.SHOULD BE | | SUITE 1000 | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD | | AS A GENERAL NOTE | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD | | AS A GENERAL NOTE | | | | 4.OK | | | | 5.OK | | | | 6.OK | | | | 7.HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE | | SPRINKLER AND FIRE ALARM DEVICES.SPRINKLERS ARE | | SHOWN, HOWEVER SPRINKLER PROTECTION NEEDED ABOVE AND | | BELOW THE MEZZANINE.PROVIDE A LAYOUT OF THE FIRE | | ALARM DEVICES IN THE SPACE INCLUDING THE PROPOSED | | MEZZANINE. | | | | 8.OK | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|