Plan Review Notes
Plan Review Notes For Permit 08010311
Permit Number 08010311
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2008-04-22 11:06:01*****DENIED*****
  
 THE COMMENTS (NOT MARKED OK) FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 1.STRUCTURAL CALCULATION COVER SHEET AND MEZZANINE
 SHEET 1 STILL SHOW 100 AS THE SUITE NUMBER.SHOULD BE
 SUITE 1000
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.ADD
 AS A GENERAL NOTE
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.ADD
 AS A GENERAL NOTE
  
 4.OK
  
 5.OK
  
 6.OK
  
 7.HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE
 SPRINKLER AND FIRE ALARM DEVICES.SPRINKLERS ARE
 SHOWN, HOWEVER SPRINKLER PROTECTION NEEDED ABOVE AND
 BELOW THE MEZZANINE.PROVIDE A LAYOUT OF THE FIRE
 ALARM DEVICES IN THE SPACE INCLUDING THE PROPOSED
 MEZZANINE.
  
 8.OK
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW