Plan Review Notes
Plan Review Notes For Permit 08010311
Permit Number 08010311
Review Stop E
Sequence Number 2
Notes
Date Text
2008-04-03 15:03:00** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE COMMENTS FROM PREVIOUS REVIEW AS
 THE SAME COMMENTS APPLY.
 IF AN OCCUPANT ON THE MEZZANINE LEVEL AND LIGHTS TURN
 OFF, HOW WILL THE OCCUPANT HAVE CONTROLS FOR EGRESS
 LIGHTING FOR MINIMUM LIGHTING LEVELS?
 PLEASE SEE THE NOTES AS PREVIOUSLY MENTIONED STILL
 APPLY. MAY NOT ADD NEW MEZZANINE LEVEL WITHOUT
 ADDRESSING THE MINIMUM FOR LIFE SAFETY CODE ALONG WITH
 OTHER CODES AS NOTED PREVIOUSLY.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  