2008-02-12 16:52:15 | *****DENIED***** |
| |
| |
| 1. THE CORRECT SUITE NUMBER SHALL BE LISTED AS PART OF |
| THE PROJECT SITE ADDRESS. PLEASE SEE THAT SUITE 100 AND |
| SUITE 1000 ARE SHOWN ON THE SUBMITTED PLAN SHEETS AND |
| STRUCTURAL CALCULATIONS DOCUMENTS. PLEASE |
| RECTIFY. |
| |
| 2. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 3. COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| |
| 4. PLEASE INDICATE IF THE BUILDING IS TO BE OCCUPIED |
| DURING THE SCOPE OF WORK. IF SO, MEANS OF EGRESS AND |
| AND REQUIRED FIRE PROTECTION FEATURES ARE TO BE IN |
| PLACE AND CONTINUOUSLY MAINTAINED. |
| |
| 5. PLEASE LIST THE FOLLOWING FOR THE BUILDING: |
| OCCUPANCY TYPE, OCCUPANT LOAD, FIRE ALARM AND/OR FIRE |
| SPRINKLER DEVICES, AND ANY OTHER PERTINENT |
| INFORMATION. |
| |
| 6. PLEASE PROVIDE A CLEAR REPRENSENTATION OF THE |
| MEZZANINE IN RELATION TO THE FLOOR PLAN INCLUDING EXIT |
| LIGHTS/DOORS, EMERGENCY LIGHTS, ETC. |
| |
| 7. HOW WILL THIS MEZZANINE IMPACT THE EXISTING FIRE |
| SPRINKLER AND FIRE ALARM DEVICES. |
| |
| 8. NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| REFERENCED. |
| |
| |
| TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| LETTER, INDICATING WHERE EACH ITEM WAS ADDRESSED |
| |
| |