2008-01-28 09:50:50 | ** DENIEDREVIEW ** |
| |
| |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE |
| PLACED ON ELECTRICAL PLANS FOR RELEVANT DESIGN. |
| 2004 FBC W/2007 REVISIONS. |
| 2005 NFPA-70 2003 NFPA-101 |
| |
| 2) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING ANY NEW |
| ELECTRICAL LIGHTING AND WIRING METHODS REQUIRED FOR |
| EGRESS. |
| PLEASE SUBMIT PHOTO-METRICLEVELS FOR NEW EGRESS PATHS |
| AND AREAS. PLEASE SEE NFPA-101 7.8.1.3 AND 7.9.2.2. |
| PLEASE SEE FAC 61G15-33.004 |
| PLEASE SHOW OCCUPANCY OF MEZZ LEVEL AND LIGHTING. |
| |
| 3) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE |
| 13-415.1.ABC.1.1, .1.2 FOR LIGHTING CONTROLS REQUIRED. |
| PLEASE SEE 13-415.2 FOR MAXIMUM LIGHTING PERFORMANCE |
| CALCULATIONS. |
| |
| ** PLEASE KNOW AS THERE WAS NO ELECTRICAL PLANS, NO |
| ELECTRICAL DETAILS ETC SUBMITTED FOR REVIEW THERE MAY |
| VERY WELL BE NEW COMMENTS ON THE NEXT REVIEW. THERE ARE |
| SEVERAL ITEMS WHICH COULD NOT BE REVIEWED AT THIS |
| TIME. |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| CONTACTING THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |