2008-10-31 15:46:24 | REVISION FAILED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| 1. SHT P-203A INDICATES 3 GAS DRYERS, BUT ONLY 2 GAS |
| DRYERS ARE SHOWN. NO CHANGE IN DRYER AMOUNTS SHOWN ON |
| FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 402.1. |
| |
| 2. SHT P-500 THE FLOOR DRAINS (3) ADDED NEAR THE BASE |
| OF STACK SAN-13 AND BY THE TOILET ROOMS FOR THE SPA'S |
| ARE NOT VENTED. SECTIONS 901.2.1 & 908.3. |
| |
| 3. SHT P-501 THE SANITARY RISER DIAGRAM DOES NOT |
| REFLECT THE FLOOR PLAN AT THE WASH MACHINES FOR THE |
| GUEST LAUNDRY ROOM. THE TRAP & LAUNDRY BOX ARE SHOWN ON |
| EACH SIDE OF THE STACK ON THE FLOOR PLAN, BUT ARE SHOWN |
| ON ONE SIDE OF THE STACK ON THE RISER DIAGRAM. ALSO THE |
| SECOND TRAP IS NOT SHOWN CONNECTING TO THE STACK. |
| SECTIONS 106.1.1 & 706.3. |
| |
| 4. SHT P-503 REVISION #4 HAS BEEN DELETED FROM THE |
| REVISION INDEX. PLEASE KEEP ALL PREVIOUS REVISION |
| NUMBERS IN INDEX THROUGH OUT THE PERMIT CYCLE. NO NEW |
| CHANGES INDICATED ON THE SHEET AS REVISION #5. IF NO |
| CHANGES/REVISIONS NOT REQUIRED FOR PUBLIC RECORD. |
| SECTION 106.1.3. |
| |
| 5. SHT P-602 NATURAL GAS SIZING TABLE. NOT ALL CHANGES |
| HAVE BEEN INDICATED WITH A CLOUD OR REVISION NUMBER. |
| SEE SECTION LOAC (CFH) FOR A, J, K & L AS WELL AS APPL |
| LOAD (CFH) FOR J. PIPE SECTION N SECTION LOAD TO BE 700 |
| AND THE LONGEST RUN TO BE SECTION P, NOT O. PLEASE |
| CORRELATE ALL CHANGES TO NATURAL GAS SIZING TABLE AND |
| CLOUD ALL REVISIONS AND INDICATE WITH A REVISION |
| NUMBER. SECTION 106.1.3. |
| |
| 6. SHT P-602 GAS RISER DIAGRAM INDICATES SECTION P TO |
| BE 1/2", BUT IT ALSO SHOWS 3/4" GAS VALVE AND CAP. |
| PLEASE CLARIFY. SECTIONS 106.1.1 AND 402.1. |
| |
| 7. SHT P-602 GAS RISER DIAGRAM DOES NOT SHOW SECTION O. |
| PLEASE CORRELATE WITH GAS SIZING TABLE. SECTIONS |
| 106.1.1 & 402.1. |
| |
| 8. SHT P-602 GAS RISER DIAGRAM. UNIONS ARE REQUIRED |
| DOWNSTREAM OF THE SHUT OFF VALVES FOR EACH REGULATOR AT |
| THE WATER HEATERS AND THE POOL HEATER. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |