Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 9
Notes
Date Text
2009-01-29 17:51:43SUBMITTAL FOR GENERATOR AND ATS DEVICES.
 REDLINED THE *EMERGENCY DISCONNECT* IN SUBMITTED. THE
 GLASS TYPE SHUNT TRIP IS NOT A RATED DISCONNECT. THE
 DISCONNECTTING MEANS RATED FOR THE LOAD SERVED IS
 LOCATED ON RISER. SHOWN ON EMDP,EDPLS AND EACH BREAKER
 ON THE GENERATOR. THIS GLASS BREAK TYPE OF BUTTON IS IN
 ADDITION TO THE RATED DISCONNECTS AS SHOWN.
 230.76,230.79,225.39 ETC