2009-01-29 17:51:43 | SUBMITTAL FOR GENERATOR AND ATS DEVICES. | | REDLINED THE *EMERGENCY DISCONNECT* IN SUBMITTED. THE | | GLASS TYPE SHUNT TRIP IS NOT A RATED DISCONNECT. THE | | DISCONNECTTING MEANS RATED FOR THE LOAD SERVED IS | | LOCATED ON RISER. SHOWN ON EMDP,EDPLS AND EACH BREAKER | | ON THE GENERATOR. THIS GLASS BREAK TYPE OF BUTTON IS IN | | ADDITION TO THE RATED DISCONNECTS AS SHOWN. | | 230.76,230.79,225.39 ETC |
|