Date Text
2009-01-24 23:16:45DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FLORIDA STATUTES
  
 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE
 INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE
 EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE
 PLUMBING PLAN REVIEW. FS 589.
  
 2. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM
 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). --
 THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE
 THROUGH A WALL ON THE ZERO LOT LINE.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  