Plan Review Notes For Permit 08010249 |
Permit Number |
08010249 |
|
Review Stop |
G |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2009-01-24 23:16:45 | DENIED | | REFERENCE: | | FBC-2004 PLUMBING | | FBC-2004 FUEL GAS | | FBC-2004 BUILDING | | FLORIDA STATUTES | | | | 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE | | INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE | | EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE | | PLUMBING PLAN REVIEW. FS 589. | | | | 2. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM | | 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). -- | | THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE | | THROUGH A WALL ON THE ZERO LOT LINE. | | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | WITH A DESCRIPTION OF THE REVISION MADE, | | IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | ONE SET OF THEM LOOSELY ON TOP OF THE | | COLLATED PLANS TO BE REVIEWED. | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | | | | | |
|