Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 7
Notes
Date Text
2008-11-07 10:12:41** DENIED REVISIONS **
  
 ** A CALLED WAS PLACED TO ENGINEER ON 11/6/08 IN THE
 AFTERNOON HOWEVER HE WAS OUT OF THE OFFICE. SOME OF
 THESE ITEMS WILL NEED TO BE GONE OVER.
  
 ** THANK YOU FOR NARRATIVE ON REVISIONS. IT IS MOST
 HELPFUL.
  
 1) NOTE: NOTED FOR INFORMATION. AS THERE ARE SEVERAL
 LIGHTING FIXTURES ADDED AND INCLUDING REVISIONS OF THE
 TYPES OF LIGHTING FIXTURES, PER FBC 13-415.2,
 13-415.2.ABC.1.1,.1.2, .1.3 AND 13-400.3A COMPLETED
 REVISED ENERGY CALCULATIONS WILL BE REQUIRED. THIS
 SHOULD BE SUBMITTED ONCE ALL KNOWN COMPONENTS TO
 BUILDING ARE COMPLETED.
  
 2) NOTE: PLEASE KNOW FOR ITEMS SUCH AS CAMERAS AND
 OTHER LOW VOLTAGE WHICH WAS NOT PART OF ORIGINAL PLANS
 NEED TO BE PERMITTED. THE VALUE FOR THESE ITEMS IN THE
 SCOPE OF WORK NEEDS TO BE APPLIED TO LOW VOLTAGE
 PERMITS REQUIRED.
 105.1, 108.3.
 NEC 800
  
 ** AS OF THIS REVIEW ONLY THE LOW VOLTAGE FOR DATA AND
 CATV HAS BEEN APPLIED FOR AND PERMITTED.
  
 3) NOTE: PLEASE SUBMIT COMPLETED LIGHTING CONTROL PANEL
 SCHEDULES. FOR EXAMPLE: POOL AREA LIGHTING IS ONE AREA
 NOTED WHICH MENTIONS TO WIRE THROUGH LIGHTING CONTROL
 PANEL HOWEVER THE PANELS SUBMITTED DO NOT INDICATE
 THIS. THIS IS ONE EXAMPLE ONLY..
 13-415.1.ABC.1.1, .1.2, .1.3.
  
 4) NOTE: INFORMATION IS NEEDED FOR NEW WAP ( WIRELESS
 ACCESS POINTS) ADDED TO PLANS. THE PLANS SPECIFICALLY
 CALL OUT FOR *RECEPTACLES*. THIS LENDS TO THESE BEING
 INSTALLED IN THE HALLWAYS WITH EQUIPMENT WHICH WILL BE
 PLUGGED IN. THESE WOULD BE REQUIRED TO BE INSTALLED
 BELOW THE CEILING HANGING IN THE HALLWAY.
 PLEASE SEE 400.8. THE FOLLOWING HAS BEEN EXTRACTED FROM
 THE CODE FOR REVIEW.
 **400.8
 USES NOT PERMITTED
 UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS
 AND CABLES SHALL NOT BE USED FOR THE FOLLOWING:
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE
 (2) WHERE RUN THROUGH HOLES IN WALLS, STRUCTURAL
 CEILINGS, SUSPENDED CEILINGS, DROPPED CEILINGS, OR
 FLOORS
 (3) WHERE RUN THROUGH DOORWAYS, WINDOWS, OR SIMILAR
 OPENINGS
 (4) WHERE ATTACHED TO BUILDING SURFACES
 EXCEPTION TO (4): FLEXIBLE CORD AND CABLE SHALL BE
 PERMITTED TO BE ATTACHED TO BUILDING SURFACES IN
 ACCORDANCE WITH THE PROVISIONS OF 368.56(B)
 SECTION 368.56(B) PROVIDES THE REQUIREMENTS FOR THE
 INSTALLATION OF FLEXIBLE CORDS INSTALLED AS BRANCHES
 FROM BUSWAYS.
 (5) WHERE CONCEALED BY WALLS, FLOORS, OR CEILINGS OR
 LOCATED ABOVE SUSPENDED OR DROPPED CEILINGS
 (6) WHERE INSTALLED IN RACEWAYS, EXCEPT AS OTHERWISE
 PERMITTED IN THIS CODE
 THE FLEXIBLE CORDS AND CABLES REFERRED TO IN ARTICLE
 400 ARE NOT LIMITED TO USE WITH PORTABLE EQUIPMENT.
 THEY MAY NOT BE USED, HOWEVER, AS A SUBSTITUTE FOR THE
 FIXED WIRING OF A STRUCTURE OR WHERE CONCEALED BEHIND
 BUILDING WALLS, FLOORS, OR CEILINGS (INCLUDING
 STRUCTURAL, SUSPENDED, OR DROPPED-TYPE CEILINGS). SEE
 240.5, 590.4(B), AND 590.4(C) FOR THE USES OF
 MULTICONDUCTOR FLEXIBLE CORDS FOR FEEDER AND
 BRANCH-CIRCUIT INSTALLATIONS AND FOR OVERCURRENT
 PROTECTION REQUIREMENTS FOR FLEXIBLE CORD. SEE 410.30
 FOR CORD-CONNECTED LUMINAIRES.
 (7) WHERE SUBJECT TO PHYSICAL DAMAGE
 **
 PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT INFORMATION.
  
 5) NOTE: PLEASE SEE THE LIGHTING ON PLANS AS NOTED ON *
 PROVISO * ISSUED WHEN PERMIT WAS ISSUED HAS NOT BEEN
 ADDRESSED. PLEASE SEE E201 AS SOME OF THE LIGHTING
 STILL NOT COORDINATE WITH THE LIGHTING ON THE ROOM
 LAYOUT PLANS FOR LIGHTING CONTROLS ON E 203,204 ETC.
 EXAMPLES ON THREE PREVIOUS REVIEWS WERE GIVEN AND THEY
 WILL BE GIVEN AGAIN. SEE KING ACCESSIBLE, AND DOUBLE
 QUEEN ACCESSIBLE ETC.
 13-415.1.ABC.1.1, .1.2, .1.3
 FBC 106.1.1 FOR CLARITY, COORDINATION OF PLANS.
 *** CALL TO GO OVER THESE AS THEY CAN BE POINTED OUT.
  
 6) NOTE: THE FOLLOWING SHEETS SIGNED, DATED AND SEALED
 OCT 9TH APPEAR TO BE OK AT THIS TIME HOWEVER BASED ON
 THE COMMENTS ABOVE THE OTHER SHEETS IN SETS MAY ALL
 NEED REVISIONS. THE FOLLOWING SHEETS IF NO CHANGES ARE
 MADE WILL BE STAMPED ONCE RESUBMITTED AND NO
 CORRECTIONS ARE NEEDED.
 PLEASE CALL TO GO OVER IF NEEDED. NO REVISION FEE WILL
 BE CHARGED FOR THESE SHEETS WHEN BRINGING BACK
 CORRECTED PLANS AS LONG AS NO CHANGES ARE MADE.
 107A, 107B, 205,301,302, AND 403. THESE SHEETS DO NOT
 APPEAR TO NEED REVISIONS AT THIS TIME ALTHOUGH THAT MAY
 CHANGE.
  
  
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  