Date |
Text |
2008-11-07 10:12:41 | ** DENIED REVISIONS ** |
| |
| ** A CALLED WAS PLACED TO ENGINEER ON 11/6/08 IN THE |
| AFTERNOON HOWEVER HE WAS OUT OF THE OFFICE. SOME OF |
| THESE ITEMS WILL NEED TO BE GONE OVER. |
| |
| ** THANK YOU FOR NARRATIVE ON REVISIONS. IT IS MOST |
| HELPFUL. |
| |
| 1) NOTE: NOTED FOR INFORMATION. AS THERE ARE SEVERAL |
| LIGHTING FIXTURES ADDED AND INCLUDING REVISIONS OF THE |
| TYPES OF LIGHTING FIXTURES, PER FBC 13-415.2, |
| 13-415.2.ABC.1.1,.1.2, .1.3 AND 13-400.3A COMPLETED |
| REVISED ENERGY CALCULATIONS WILL BE REQUIRED. THIS |
| SHOULD BE SUBMITTED ONCE ALL KNOWN COMPONENTS TO |
| BUILDING ARE COMPLETED. |
| |
| 2) NOTE: PLEASE KNOW FOR ITEMS SUCH AS CAMERAS AND |
| OTHER LOW VOLTAGE WHICH WAS NOT PART OF ORIGINAL PLANS |
| NEED TO BE PERMITTED. THE VALUE FOR THESE ITEMS IN THE |
| SCOPE OF WORK NEEDS TO BE APPLIED TO LOW VOLTAGE |
| PERMITS REQUIRED. |
| 105.1, 108.3. |
| NEC 800 |
| |
| ** AS OF THIS REVIEW ONLY THE LOW VOLTAGE FOR DATA AND |
| CATV HAS BEEN APPLIED FOR AND PERMITTED. |
| |
| 3) NOTE: PLEASE SUBMIT COMPLETED LIGHTING CONTROL PANEL |
| SCHEDULES. FOR EXAMPLE: POOL AREA LIGHTING IS ONE AREA |
| NOTED WHICH MENTIONS TO WIRE THROUGH LIGHTING CONTROL |
| PANEL HOWEVER THE PANELS SUBMITTED DO NOT INDICATE |
| THIS. THIS IS ONE EXAMPLE ONLY.. |
| 13-415.1.ABC.1.1, .1.2, .1.3. |
| |
| 4) NOTE: INFORMATION IS NEEDED FOR NEW WAP ( WIRELESS |
| ACCESS POINTS) ADDED TO PLANS. THE PLANS SPECIFICALLY |
| CALL OUT FOR *RECEPTACLES*. THIS LENDS TO THESE BEING |
| INSTALLED IN THE HALLWAYS WITH EQUIPMENT WHICH WILL BE |
| PLUGGED IN. THESE WOULD BE REQUIRED TO BE INSTALLED |
| BELOW THE CEILING HANGING IN THE HALLWAY. |
| PLEASE SEE 400.8. THE FOLLOWING HAS BEEN EXTRACTED FROM |
| THE CODE FOR REVIEW. |
| **400.8 |
| USES NOT PERMITTED |
| UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS |
| AND CABLES SHALL NOT BE USED FOR THE FOLLOWING: |
| (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE |
| (2) WHERE RUN THROUGH HOLES IN WALLS, STRUCTURAL |
| CEILINGS, SUSPENDED CEILINGS, DROPPED CEILINGS, OR |
| FLOORS |
| (3) WHERE RUN THROUGH DOORWAYS, WINDOWS, OR SIMILAR |
| OPENINGS |
| (4) WHERE ATTACHED TO BUILDING SURFACES |
| EXCEPTION TO (4): FLEXIBLE CORD AND CABLE SHALL BE |
| PERMITTED TO BE ATTACHED TO BUILDING SURFACES IN |
| ACCORDANCE WITH THE PROVISIONS OF 368.56(B) |
| SECTION 368.56(B) PROVIDES THE REQUIREMENTS FOR THE |
| INSTALLATION OF FLEXIBLE CORDS INSTALLED AS BRANCHES |
| FROM BUSWAYS. |
| (5) WHERE CONCEALED BY WALLS, FLOORS, OR CEILINGS OR |
| LOCATED ABOVE SUSPENDED OR DROPPED CEILINGS |
| (6) WHERE INSTALLED IN RACEWAYS, EXCEPT AS OTHERWISE |
| PERMITTED IN THIS CODE |
| THE FLEXIBLE CORDS AND CABLES REFERRED TO IN ARTICLE |
| 400 ARE NOT LIMITED TO USE WITH PORTABLE EQUIPMENT. |
| THEY MAY NOT BE USED, HOWEVER, AS A SUBSTITUTE FOR THE |
| FIXED WIRING OF A STRUCTURE OR WHERE CONCEALED BEHIND |
| BUILDING WALLS, FLOORS, OR CEILINGS (INCLUDING |
| STRUCTURAL, SUSPENDED, OR DROPPED-TYPE CEILINGS). SEE |
| 240.5, 590.4(B), AND 590.4(C) FOR THE USES OF |
| MULTICONDUCTOR FLEXIBLE CORDS FOR FEEDER AND |
| BRANCH-CIRCUIT INSTALLATIONS AND FOR OVERCURRENT |
| PROTECTION REQUIREMENTS FOR FLEXIBLE CORD. SEE 410.30 |
| FOR CORD-CONNECTED LUMINAIRES. |
| (7) WHERE SUBJECT TO PHYSICAL DAMAGE |
| ** |
| PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT INFORMATION. |
| |
| 5) NOTE: PLEASE SEE THE LIGHTING ON PLANS AS NOTED ON * |
| PROVISO * ISSUED WHEN PERMIT WAS ISSUED HAS NOT BEEN |
| ADDRESSED. PLEASE SEE E201 AS SOME OF THE LIGHTING |
| STILL NOT COORDINATE WITH THE LIGHTING ON THE ROOM |
| LAYOUT PLANS FOR LIGHTING CONTROLS ON E 203,204 ETC. |
| EXAMPLES ON THREE PREVIOUS REVIEWS WERE GIVEN AND THEY |
| WILL BE GIVEN AGAIN. SEE KING ACCESSIBLE, AND DOUBLE |
| QUEEN ACCESSIBLE ETC. |
| 13-415.1.ABC.1.1, .1.2, .1.3 |
| FBC 106.1.1 FOR CLARITY, COORDINATION OF PLANS. |
| *** CALL TO GO OVER THESE AS THEY CAN BE POINTED OUT. |
| |
| 6) NOTE: THE FOLLOWING SHEETS SIGNED, DATED AND SEALED |
| OCT 9TH APPEAR TO BE OK AT THIS TIME HOWEVER BASED ON |
| THE COMMENTS ABOVE THE OTHER SHEETS IN SETS MAY ALL |
| NEED REVISIONS. THE FOLLOWING SHEETS IF NO CHANGES ARE |
| MADE WILL BE STAMPED ONCE RESUBMITTED AND NO |
| CORRECTIONS ARE NEEDED. |
| PLEASE CALL TO GO OVER IF NEEDED. NO REVISION FEE WILL |
| BE CHARGED FOR THESE SHEETS WHEN BRINGING BACK |
| CORRECTED PLANS AS LONG AS NO CHANGES ARE MADE. |
| 107A, 107B, 205,301,302, AND 403. THESE SHEETS DO NOT |
| APPEAR TO NEED REVISIONS AT THIS TIME ALTHOUGH THAT MAY |
| CHANGE. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |