2008-11-19 16:21:24REVISION # 5
  
 1. ON PAGE E-101 C EXIT SIGNS STILL APOPEAR TO DIRECT
 PERSONS INTO GARAGE AREA WHICH IS CONSIDERED MORE
 HAZARDOUS THAN THE AREA THEY ARE EXISTING FROM. PLEASE
 REMOVE THESE EXIT SIGNS SO PERSONS DO NOT EXIT INTO A
 MORE HAZARDOUS AREA.
  
 2. THE CARBON MONOXIDE DETECTORS (CO) SHALL BE PROPERLY
 TESTED WITH CALIBRATION GAS AT THE ESTABLISHED SET
 POINTS OF THE MANUFACTURER.
  
 3. THE KNOX BOX SHOULD BE INSTALLED NEAR THE MAIN
 INGRESS/EGRESS DOOR FOR THE HOTEL.
  
 4. CARD READERS OR ANY SECURITY DEVICES SHALL NOT
 INTERFERE WITH REQUIRED EXITING FROM THE BUILDING.
  
 5. NATURAL GAS INSTALLATION SHALL COMPLY WITH
 APPROPRIATE NFPA STANDARDS AND RECOGNIZED SAFE
 PRACTICES.
  
  