Date |
Text |
2008-07-18 16:20:59 | * DENIED 4TH REVIEW** |
| |
| |
| |
| 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS> |
| PLEASE SEE COMPLIANCE SUMMARY ON SHEET 2 WHICH APPEARS |
| TO DROP THE 7TH DIGIT FROM THE CRITERIA. CALLED AND |
| SPOKE TO JIM MULLENS FROM TLC AND THEY WILL WORK ON |
| TRYING TO FIX THIS. |
| 13-400.3.A. |
| |
| 2) NOTE: PLEASE SEE ONE SET OF PLANS IS MISSING E201. |
| NEED THREE COMPLETE SETS. |
| FBC 106.1 |
| |
| 3) NOTE: PLEASE SEE THE LIGHTING SHOWN ON E-201 DOES |
| NOT COORDINATE WITH THE LIGHTING WHICH IS NOW SHOWN ON |
| SHEETS E 203,204,ETC. |
| FOR EXAMPLE: |
| PLEASE SEE ENLARGED KING, ACCESSIBLE KING, DOUBLE |
| QUEEN. |
| 13-415.1.ABC.1.1, .1.2 |
| |
| 4) NOTE: PLEASE KNOW THE M FIXTURES ON PHOTO-METRICS |
| ARE STILL SHOWN. THESE CAN BE REDLINED OFF THE PLANS. |
| |
| 5) NOTE: SMOKE/CARBON MONOXIDE DETECTORS WERE NOT |
| REVISED. WILL BE PART OF PROVISO. |
| |
| ** PLACED CALL TO CONTRACTOR REP AND LEFT MESSAGE. |
| |
| ** PLACED CALL TO ENGINEER WHICH IS ON VACATION. |
| ENGINEER OF RECORD WILL CALL BACK TO WORK OUT ITEMS ON |
| PLANS FOR NEW SHEETS. |
| |
| |
| |
| |
| IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |