2009-02-16 10:47:30 | ** DENIED REVIEW ** |
| |
| ** REVISIONS |
| |
| |
| 1) NOTE: ALL SUBMITTED REPORTS FOR COORDINATION STUDY |
| AND SHORT CIRCUIT CALCULATIONS NEED TO BE SIGNED, DATED |
| AND SEALED BY THE ENGINEER OF RECORD. |
| FAC 61G15-23.002 |
| FS 471.023 |
| |
| 2) NOTE: THE COORDINATION STUDY NEEDS TO INCLUDE ALL |
| EQUIPMENT/PANELS/MAIN BREAKERS AND CONDUCTORS FOR LIFE |
| SAFETY (700 SYSTEMS) AND LEGALLY REQUIRED (701) |
| SYSTEMS. 700.27,701.18 AND 240.12. THIS IS IMPERATIVE |
| FOR THESE SYSTEMS TO COORDINATE. AT ANY GIVEN POINT THE |
| LACK OF COORDINATION COULD RESULT IN A LOSS OF AN |
| ENTIRE PANEL, MULTIPLE PANELS OR AN ENTIRE EMERGENCY OR |
| LEGALLY REQUIRED SYSTEM. |
| PLEASE SEE THE FOLLOWING ITEMS WHICH COULD NOT BE FOUND |
| IN THE COORDINATION STUDY. THERE WILL BE COMMENTS BELOW |
| ALSO WITH RESPECT TO THE SHORT CIRCUIT CALCULATIONS AND |
| ANALYSIS. |
| |
| A) PLEASE SEE PANEL ELSW2 IS NOT LOCATED IN THE |
| COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION |
| ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION. |
| |
| B) PLEASE SEE PANEL EMLW2 IS NOT LOCATED IN THE |
| COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION |
| ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION. |
| |
| C) PLEASE BE SURE TO INCLUDE THE LARGEST CIRCUIT |
| CONTRIBUTION IS INCLUDED ON BOTH OF THESE PANELS. |
| |
| D) MSB IS NOTED AS MDP. (SAME HOWEVER ONLY MISPRINTED |
| FOR IDENTIFICATION). |
| |
| E) PLEASE INCLUDE CONDUCTOR CONTRIBUTION FOR ALL |
| EQUIPMENT. THE CONDUCTORS ARE NOTED FOR EDPLS, TLSE2 |
| FEEDER, CONDUCTORS FOR ELSE2 AND FIRE PUMP. HOWEVER |
| WHERE ARE THE OTHERS? |
| |
| F) PLEASE ALSO SEE MISSING TLSW-2. |
| |
| 3) NOTE: PLEASE BE SURE THE SHORT CIRCUIT CALCULATIONS |
| SCHEDULE ALSO COORDINATES WITH THE IDENTIFICATION OF |
| ALL EQUIPMENT ON THE STUDY AND THE PLANS. THE SHORT |
| CIRCUIT CALCULATIONS WILL BE NOTED AS SCC FOR THE |
| REMAINDER OF THESE COMMENTS. SAME CODE SECTIONS AS |
| NOTED ABOVE. |
| |
| FOR EXAMPLE: THE LIST OF PANELS AND EQUIPMENT ON THE |
| THIRD PAGE OF THE SCC IN INDICATES AN ELSE3, YET THERE |
| IS NO SUCH EQUIPMENT NOTED ON PLANS OR COORDINATION |
| STUDY. |
| THE RISER AT THE BACK OF THE SCC ALSO DOES NOT INCLUDE |
| THIS ELSE3 PANEL. IF THIS IS REALLY THE ELSW2 PANEL, |
| PLEASE ADJUST BOTH THE SCC AND THE SCC RISER. |
| |
| FOR EXAMPLE: THE LIST ON THIS SAME PAGE THREE OF THE |
| SCC DOES NOT LIST EMLW2. THE RISER ON THE BACK OF THE |
| SCC DOES INCLUDE THIS EMLW2 PANEL. |
| |
| |
| **THE COMMENTS ABOVE IN NOTE #2 ALREADY GIVE THE NOTE |
| WITH RESPECT TO THE COORDINATION STUDY MISSING THE |
| ELSW2 AND EMLW2. |
| |
| 4) NOTE: PLEASE IDENTIFY RECEPTACLES NOTED ON PANEL |
| SCHEDULE EMLW2 FOR CIRCUITS 15, 17 /19. THE SCHEDULE |
| INDICATES REC HOWEVER THE INFORMATION ON THE RISER |
| ACTUALLY SHOWS THESE AS CIRCUITS TO THE GENERATOR. THE |
| OCP FOR CIRCUIT 17/19 SEEMS TO BE A LARGER BREAKER OR |
| CIRCUIT WHICH WILL BE A REVISED PORTION OF THE STUDY. |
| THIS NEEDS TO BE VERIFIED BEFORE REVISED THE |
| COORDINATION STUDY. |
| 408.4 |
| FBC 106.1.1, 106.5 FOR CLARITY, COORDINATION OF RECORD |
| PLANS. |
| |
| 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL |
| CHANGES WITH RESPECT TO PLANS FROM AIC RATINGS, |
| CONDUCTORS ETC FROM PREVIOUS PLANS A NEW ELECTRICAL |
| INSPECTION WILL BE REQUIRED BEFORE THE TCO. |
| |
| |
| 6) NOTE: SHEETS E-102A, 102B, 103A ,203 AND 204 ARE OK. |
| THESE SHEETS RETAINED FOR FILE. |
| THE OTHER SHEETS SUCH AS RISER, AND PANEL SCHEDULE |
| SHEETS NEED TO BE BROUGHT BACK IN IF THEY ARE NOT |
| REVISED. |
| |
| *** ALL COMMENTS WERE GONE OVER WITH THE ENGINEER OF |
| RECORD. THE ORIGINAL COMMENTS E-MAILED TO THE ENGINEER |
| HAVE BEEN ADJUSTED FOR THESE POSTED NOTES. ONE COMMENT |
| WAS REMOVED AS THE PRINTED SHEET WAS NOT EASILY |
| READABLE AND ENGINEER CLARIFIED INFORMATION. THE |
| COMMENT #4 ABOVE WAS REVISED ALSO FOR MORE INFORMATION |
| AND COORDINATION NEEDED. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |