Date |
Text |
2008-07-03 11:08:29 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| FHA-98 DESIGN MANUAL |
| CITY WPB MUNICIPAL CODES |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| ******FROM PREVIOUS REVIEWS: |
| |
| 1. OK |
| 2. OK |
| 3. OK |
| 4. OK |
| 5. OK |
| 6. OK |
| 7. OK |
| 8. OK |
| 9. OK |
| 10. OK |
| 11. OK |
| 12. OK |
| 13. OK |
| 14. OK |
| |
| 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 |
| GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING |
| TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. |
| INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW |
| METHOD. SECTIONS 106.1.2 & 608. |
| ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A |
| MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE |
| RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED |
| FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW |
| PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM |
| BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE |
| DRYERS. |
| ******RESPONSE NOTED, BUT THE 950XLU BACKFLOW PREVENTOR |
| IS STILL SHOWN ON SHEETS P203A & P-504. PLEASE SHOW THE |
| N36 VACUUM BREAKER. |
| |
| 16. OK |
| 17. OK |
| 18. OK |
| 19. OK |
| 20. OK |
| 21. OK |
| 22. OK |
| 23. OK |
| 24. OK |
| 25. OK |
| 26. OK |
| 27. OK |
| 28. OK |
| 29. OK |
| 30. OK |
| 31. OK |
| 32. OK |
| 33. OK |
| 34. OK |
| 35. OK |
| 36. OK |
| 37. OK |
| 38. OK |
| 38A. OK |
| 39. OK |
| 40 OK |
| 41. OK |
| 42. OK |
| 43. OK |
| 44. OK |
| 45. OK |
| 46. OK |
| 47. OK |
| 48. OK |
| 49. OK |
| 50. OK |
| 51. OK |
| |
| 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK |
| SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER |
| SECTION 903.4. |
| ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT |
| STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK |
| ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE |
| DRAINAGE STACKS. |
| ******RESPONSE NOTED, BUT RISER "I" DOES NOT SHOW THE |
| BENT FROM THE 2ND FLOOR OR CONNECTION TO THE SANITARY |
| STACK. (SHT 502). |
| |
| 53. OK |
| 54. OK |
| 55. OK |
| 56. OK |
| 57. OK |
| 58. OK |
| 59. OK |
| 60. OK |
| 61. OK |
| 62. OK |
| 63. OK |
| 64. OK |
| 65. OK |
| 66. OK |
| 67. OK |
| 68. OK |
| 69. OK |
| 70. OK |
| 71. OK |
| 72. OK |
| 73. OK |
| 74. OK |
| 75. OK |
| 76. OK |
| 77. OK |
| |
| 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 |
| DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| ******RESPONSE NOTED, BUT COMMENT STILL NOT ADDRESSED. |
| BRANCH LINE SHOWN UPSTREAM OF CONDENSATE CONNECTION AND |
| ST13 ON SHT P-101A. PLEASE CORRELATE. |
| |
| 79. OK |
| 80. OK |
| 81. OK |
| 82. OK |
| 83. OK |
| 84. OK |
| 85. OK |
| 86. OK |
| 87. OK |
| 88. OK |
| 89. OK |
| |
| 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED: |
| |
| A. OK |
| B. OK |
| C. OK |
| D. OK |
| E. OK |
| F. OK |
| G. OK |
| |
| H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT |
| SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS |
| APPLICATION IS APPLIED FOR). |
| |
| I. N/A |
| J. N/A |
| |
| **********NEW COMMENTS********** |
| |
| 1B. OK |
| 2B. OK |
| 3B. OK |
| |
| ***********NEW COMMENT*********** |
| |
| 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL |
| Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS |
| INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED |
| LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL |
| HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |