Plan Review Notes For Permit 08010249 |
Permit Number |
08010249 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2008-06-27 08:36:42 | ************PROVISOS************* | | | | 1. COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS | | SHALL BE DEMONSTRATED PRIOR TO INSTALLATION AND | | INSPECTION OF OUTDOOR APPLIANCES AND EQUIPMENT EXPOSED | | TO WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. ANY | | ALTERNATE MATERIALS AND METHODS PROPOSALS SHALL BE | | SUBMITTED TO THE BUILDING OFFICIAL IN WRITING. | | | | 2. A STAIR PRESSURIZATION TEST SHALL BE PERFORMED PRIOR | | TO FINAL INSPECTION TO VERIFY STAIRWAY DOOR OPENING | | FORCES ARE WITHIN ALLOWED RANGE IN COMPLIANCE WITH FBCB | | 11-4.13.11. | | | | 3. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL | | PROVIDE AN AIR VELOCITY WITHIN THE DUCT SYSTEM OF 1,500 | | TO 2,500 FEET PER MINUTE. KEF-1 ON SCHEDULE (M-002) IS | | TOO SMALL TO PROVIDE REQUIRED EXHAUST VOLUME AND IS | | SMALLER THAN SUPPLY FAN. DEMONSTRATE COMPLIANCE WITH | | FBCM 506.3.4 AND FBCB 13-409.1.ABC.3.6.1. REVISE PLANS | | PRIOR TO ROUGH INSPECTION. | | | | 4. ROOF KEF DETAIL (M-404) SHOWS CLEARANCE UNDER FAN AT | | 14 INCHES. CLEARANCE UNDER FAN TO ROOF SHALL BE IN | | ACCORDANCE WITH FBCB TABLE 1509.7. REVISE PLANS PRIOR | | TO ROUGH INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|