2008-07-03 11:34:10 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| ****FROM PREVIOUS REVIEW: |
| |
| ******FROM PREVIOUS REVIEWS: |
| |
| 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED: |
| |
| A. OK |
| B. OK |
| C. OK |
| D. OK |
| E. OK |
| F. OK |
| G. OK |
| |
| H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT |
| SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS |
| APPLICATION IS APPLIED FOR). |
| |
| I. N/A |
| J. N/A |
| |
| **********NEW COMMENTS********** |
| |
| 1B. OK |
| 2B. OK |
| 3B. OK |
| |
| ***********NEW COMMENT*********** |
| |
| 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL |
| Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS |
| INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED |
| LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL |
| HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |