2008-06-12 15:09:23 | 1. THE PREVIOUS PLAN REVIEW COMMENTS APPEAR TO HAVE |
| BEEN PROPERLY ADDRESSED WITH THE REVISED PLANS AND |
| COMMENT LETTER. |
| |
| 2. THERE STILL APPEARS TO BE CONFUSION RELATED TO THE |
| FIRE PROTECTION DRAWINGS. THE FIRE PROTECTION KEYED |
| NOTES INDICATES THAT A CLASS III MANUAL WET STANDPIPE |
| SYSTEM WITH 2 1/2 TO 1 1/2 REDUCERS WITH CAPS ATTACHED |
| TO A CHAIN ARE GOING TO BE PROVIDED. PER NFPA 14, THE |
| STANDARD FOR STANDPIPE SYSTEMS A MANUAL WET STANDPIPE |
| SYSTEM IS DEFINED AS A WET STANDPIPE SYSTEM CONNECTED |
| TO A SMALL WATER SUPPLY FOR THE PURPOSE OF MAINTAINING |
| WATER WITHIN THE SYSTEM OR SHARING A WATER SUPPLY WITH |
| AN AUTOMATIC SPRINKLER SYSTEM BUT NOT HAVING A WATER |
| SUPPLY ATTACHED TO IT. THIS PROPSOSED SYSTEM IS A |
| SYSTEM THAT RELIES ON THE FIRE DEPARTMENT TO CONNECT TO |
| THE FIRE DEPARTMENT CONNECTION TO SUPPLY SYSTEM DEMAND. |
| FURTHER A CLASS III STANDPIPE SYSTEM PROVIDES HOSE |
| STATIONS FOR USE BY BUILDING OCCUPANTS. BUILDING |
| OCCUPANTS AND STAFF CANNOT BE SUFFICIENTLY TRAINED TO |
| USE CLASS III STANDPIPES. |
| |
| 3. NO PRIOR APPROVAL FOR THE MANUAL WET STANDPIPE |
| SYSTEM ARRANGEMENT HAS OCCURRED WITH THIS OFFICE. SOME |
| TIME AGO THIS INFORMATION WAS DISCUSSED AS THE PREVIOUS |
| PLANS DID NOT SEEM TO COORDINATE WITH OTHER DRAWINGS. |
| NO APPROVAL FOR A MANUAL WET STANDPIPE SYSTEM WILL BE |
| ALLOWED FOR THIS NEW HOTEL. |
| |
| 4. ON PAGE FP-205A A COMBINATION CLASS II STANDPIPE |
| SYSTEM HAS BEEN CALLED OUT FOR THE ROOF MANIFOLD. |
| |
| 5. ON PAGE FP-201A A SIX INCH FIRE LINE IS DESCRIBED. A |
| 100 PSI ELECTRIC PUMP IS ALSO NOTED ALTHOUGH THE EXACT |
| GPM FOR THE PUMP COULD NOT BE LOCATED. |
| |
| 6. NO FIRE PUMP DETAILS OR SPECIFIC DRAWINGS COULD BE |
| LOCATED. |
| |
| 7. THE FIRE LINE APPEARS TO LEAVE THE EXISTING TWELVE |
| INCH FIRE MAIN AND ENTERS PRIVATE PROPERTY AND IS |
| REDUCED TO SIX INCHES AND ENTERS THE SPRINKLER BFP |
| ROOM. WHERE IS THE POINT OF SERVICE BEING CONSIDERED |
| AND WHERE IS THE FIRE SPRINKLER RISER LOCATED. |
| |
| 8. TWELVE FIFTY IS REFERENCED ON THE FIRE PROTECTION |
| PLANS HOWEVER ONLY THREE TEST HEADERS ARE AVAILABLE |
| WHICH EQUATES TO ONE THOUSAND GPM'S. |
| |
| 9. A CAREFUL REVIEW OF THE CIVIL AND FIRE PROTECTION |
| DRAWINGS NEEDS TO OCCUR SO THE DESIGN INTENT IS |
| APPARANT. A MANAUL WET STANDPIPE SYSTEM IS NOT APPROVED |
| AND SHALL BE REMOVED FROM THE DRAWINGS. |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| 804-4709 PHONE |
| 804-4774 FAX |