2008-06-12 15:09:231. THE PREVIOUS PLAN REVIEW COMMENTS APPEAR TO HAVE
 BEEN PROPERLY ADDRESSED WITH THE REVISED PLANS AND
 COMMENT LETTER.
  
 2. THERE STILL APPEARS TO BE CONFUSION RELATED TO THE
 FIRE PROTECTION DRAWINGS. THE FIRE PROTECTION KEYED
 NOTES INDICATES THAT A CLASS III MANUAL WET STANDPIPE
 SYSTEM WITH 2 1/2 TO 1 1/2 REDUCERS WITH CAPS ATTACHED
 TO A CHAIN ARE GOING TO BE PROVIDED. PER NFPA 14, THE
 STANDARD FOR STANDPIPE SYSTEMS A MANUAL WET STANDPIPE
 SYSTEM IS DEFINED AS A WET STANDPIPE SYSTEM CONNECTED
 TO A SMALL WATER SUPPLY FOR THE PURPOSE OF MAINTAINING
 WATER WITHIN THE SYSTEM OR SHARING A WATER SUPPLY WITH
 AN AUTOMATIC SPRINKLER SYSTEM BUT NOT HAVING A WATER
 SUPPLY ATTACHED TO IT. THIS PROPSOSED SYSTEM IS A
 SYSTEM THAT RELIES ON THE FIRE DEPARTMENT TO CONNECT TO
 THE FIRE DEPARTMENT CONNECTION TO SUPPLY SYSTEM DEMAND.
 FURTHER A CLASS III STANDPIPE SYSTEM PROVIDES HOSE
 STATIONS FOR USE BY BUILDING OCCUPANTS. BUILDING
 OCCUPANTS AND STAFF CANNOT BE SUFFICIENTLY TRAINED TO
 USE CLASS III STANDPIPES.
  
 3. NO PRIOR APPROVAL FOR THE MANUAL WET STANDPIPE
 SYSTEM ARRANGEMENT HAS OCCURRED WITH THIS OFFICE. SOME
 TIME AGO THIS INFORMATION WAS DISCUSSED AS THE PREVIOUS
 PLANS DID NOT SEEM TO COORDINATE WITH OTHER DRAWINGS.
 NO APPROVAL FOR A MANUAL WET STANDPIPE SYSTEM WILL BE
 ALLOWED FOR THIS NEW HOTEL.
  
 4. ON PAGE FP-205A A COMBINATION CLASS II STANDPIPE
 SYSTEM HAS BEEN CALLED OUT FOR THE ROOF MANIFOLD.
  
 5. ON PAGE FP-201A A SIX INCH FIRE LINE IS DESCRIBED. A
 100 PSI ELECTRIC PUMP IS ALSO NOTED ALTHOUGH THE EXACT
 GPM FOR THE PUMP COULD NOT BE LOCATED.
  
 6. NO FIRE PUMP DETAILS OR SPECIFIC DRAWINGS COULD BE
 LOCATED.
  
 7. THE FIRE LINE APPEARS TO LEAVE THE EXISTING TWELVE
 INCH FIRE MAIN AND ENTERS PRIVATE PROPERTY AND IS
 REDUCED TO SIX INCHES AND ENTERS THE SPRINKLER BFP
 ROOM. WHERE IS THE POINT OF SERVICE BEING CONSIDERED
 AND WHERE IS THE FIRE SPRINKLER RISER LOCATED.
  
 8. TWELVE FIFTY IS REFERENCED ON THE FIRE PROTECTION
 PLANS HOWEVER ONLY THREE TEST HEADERS ARE AVAILABLE
 WHICH EQUATES TO ONE THOUSAND GPM'S.
  
 9. A CAREFUL REVIEW OF THE CIVIL AND FIRE PROTECTION
 DRAWINGS NEEDS TO OCCUR SO THE DESIGN INTENT IS
 APPARANT. A MANAUL WET STANDPIPE SYSTEM IS NOT APPROVED
 AND SHALL BE REMOVED FROM THE DRAWINGS.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX