Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 3
Notes
Date Text
2008-06-30 15:23:07** DENIED THIRD REVIEW **
  
 PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS ARE
 IN NEED OF ADDRESSING.
 PLEASE SEE SOME COORDINATION OF OTHER COMMENTS BELOW
 WITH SUPPORTING DOCUMENTS.
  
 1) NOTE: THE PREVIOUS REVIEWS REQUESTED FOR SUBMITTALS
 OF MANUFACTURES SPECS/CUT SHEETS FOR THE ATS,
 GENERATOR, FIRE PUMP AND FIRE PUMP CONTROLLER.
 THE RESPONSE MENTIONS TO SEE SPECS IN THE SUBMITTAL
 BOOKS. PLEASE BE SURE TO COORDINATE SUBMITTALS. FOR
 EXAMPLE:
 PLEASE SEE THERE ARE TWO SUBMITTALS FOR FIRE PUMP: ONE
 SHOWS AURORA, THE OTHER SHOWS MORSE FAIRBANKS. PLEASE
 SEE THERE ARE TWO SUBMITTALS FOR THE FIRE PUMP
 CONTROLLER: ONE SHOWS METRON WHICH DOES NOT INDICATE
 ANY LISTING AND THE OTHER IS A HUBBELL FOR FIRE PUMP
 AND JOCKEY PUMP WHICH DOES SHOW LISTING.
 PLEASE SEE THE ATS SPECS: ONE SHOWS AN ASCO AND THE
 OTHER A CATERPILLAR.
 PLEASE SEE THE GENERATOR SPACES: ONE SHOWS AN ONAN AND
 THE OTHER A CATERPILLAR.
  
 ** PLEASE REMOVE THE DOCUMENTS FORREVIEW AND RECORD
 PLANS. PLEASE BE SURE THE FINAL SPECS DO CONTAIN THE
 LISTING. IF THIS WERE THE ONLY COMMENT A REPRESENTATIVE
 WOULD BE ABLE TO CORRECT IN OFFICE.
 110.3, 90.7, 695 OF NFPA-70, CHAPTER 9 AND 10.
 FBC 106.1.1 FOR CLARITY OF CONSTRUCTION DOCUMENTS.
  
 2) NOTE: PLEASE SEE THE SUBMITTED COORDINATION STUDY
 WHICH WAS PREVIOUSLY REQUESTED. THE INFORMATION ON THE
 STUDY DOES NOT COORDINATE WITH THE SUBMITTED ELECTRICAL
 PLANS. PLEASE SEE SOME EXAMPLES GIVEN.
  
 FOR EXAMPLE:
 PLEASE SEE THE RISER WHICH SHOWS 1-SET OF 3/0 FROM
 GENERATOR TO FIRE PUMP YET THE COORDINATION STUDY SHOWS
 2-SETS OF 4/0.
  
 FOR EXAMPLE:
 PLEASE SEE THE RISER SHOWS 225 FOR ATS-LS, YET THE
 COORDINATION STUDY SHOWS 250AMPS.
  
 FOR EXAMPLE:
 PLEASE SEE THERE IS NO NORMAL FEED TO THE FIRE PUMP.
  
 FOR EXAMPLE:
 PLEASE SEE THE BREAKER OR RISER FOR FIRE PUMP ON THE
 GENERATOR IS SHOWN AS 450AMPS, YET THE COORDINATION
 STUDY SHOWS BREAKER AT 600AMPS.
  
 ** THESE ARE SOME EXAMPLES.
  
 ** PLEASE BE AWARE THAT THESE MUST BE SIGNED, DATED AND
 SEALED BY THE DESIGNER OF RECORD. THESE WERE NOT
 SIGNED, DATED OR SEALED.
 FAC61G15-23.002, 61G15-33.0002, FS 471.025
 NEC 240.12
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 *MINIMUM* LIGHTING REQUIRED FOR LIFE SAFETY. PLEASE SEE
 NFPA-101 7.8.1.3, 7.8, 7.9, 7.9.2
 AS THE MINIMUM LEVELS FOR WALK AREAS (NOT STAIRS) IS
 REQUIRED TO BE 1FT CANDLE UNDER NORMAL AS WELL AS 1FT
 CANDLE UNDER EMERGENCY. THERE ARE SOME EXAMPLES GIVEN
 WHICH THE LIGHTING LEVELS ARE AS LOW HALF THE *MINIMUM*
 REQUIRED BY THE LIFE SAFETY CODE.
  
 FOR EXAMPLE:
 PLEASE SEE E-101C AND E-101D CORRIDOR #149 WHICH SHOWS
 .04 FT CANDLES YET THE MINIMUM NEEDS TO BE A MINIMUM OF
 1FT CANDLE.
  
 FOR EXAMPLE:
 PLEASE SEE 603C, 603DAS THE LIGHTING IN AREAS 237,
 242 AND 230 ARE ALL BELOW THE 1FT CANDLE MINIMUM FOR
 EMERGENCY EGRESS. THESE LEVELS ARE SHOWN AS .5 IN
 CORRIDOR 237, .5 IN CORRIDOR 242 AND .6 INEGRESS PATH
 230.
  
 ** THESE ARE EXAMPLES GIVEN AS A BENEFIT TO DESIGN
 TEAM.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO ALL LIGHTING ON PLANS AND THE NEED FOR
 COORDINATION WITH THE SUBMITTED FLA-COM ENERGY
 CALCULATIONS.
 PLEASE SEE SECTIONS, 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND .1.3.
 THIS IS TO INCLUDE ALL INTERIOR AND EXTERIOR LIGHTING.
 SOME EXAMPLES WILL BE GIVEN BELOW. THESE ARE GIVEN AS A
 BENEFIT ONLY.
  
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTS SUCH AS THE *M* FIXTURES
 SHOWN ON PLANS ON THE SOUTH SIDEWALK YET THESE ARE NOT
 IN ANY EXTERIOR OR INTERIOR LIGHTING IN THE INPUT DATA
 REPORTS.
  
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR ELEVATOR LOBBY MISSING THE SAS
 FIXTURE IN THE IDR. PLEASE ALSO SEE THE SAME ARE FOR
 THE *SP* FIXTURE COUNT.
 ** THIS SAME AREA ON THE METHOD OF CONTROLS INDICATES
 OCCUPANCY SENSORS YET NO OCCUPANCY SENSORS ARE SHOWN ON
 PLANS. THIS APPEARS TO BE AN ERROR IN THE CHOICE OF
 LIGHTING CONTROLS OPTION.
  
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTING IN THE GUEST ROOMS
 NEED TO COORDINATE WITH THE INPUT DATA REPORT. THE
 LIGHTING PLANS ON E-201 AND E-205 ARE NOT THE SAME. IN
 FACT SOME EXAMPLES OF THIS WILL BE GIVEN.
  
 FOR EXAMPLE:
 PLEASE SEE THE KING SUITES.E-201 SHOWS A TOTAL OF 11
 FIXTURES YET THE OTHER LIGHTING PLANS FOR CONTROLS ON
 E-205 SHOW ONLY 8 FIXTURES.
 IN EITHER CASE THE IDR OF THE SUBMITTED ENERGY
 CALCULATIONS ONLY SHOW 7 FIXTURES.
 ** PLEASE LOOK AT LIGHTING PLANS FOR TYPES OF FIXTURES
 AS THERE IS THE DIFFERENCE OF 4 FIXTURES IN EACH OF
 THESE ALONE.
 COORDINATE TYPES OF FIXTURES. (WALL SCONCES ETC)
  
 FOR EXAMPLE:
 PLEASE SEE THE ENLARGED KING ACCESSIBLE UNIT: THIS
 SHOWS DIFFERENT FIXTURES ON E-201 COMPARED TO FIXTURES
 ON E-205. ALL OF THESE UNITS ALSO SHOW A LOWER NUMBER
 OF FIXTURES ON THE IDR. IT IS NOT JUST ONE FIXTURE
 TOTAL, IT IS ONE FIXTURE FOR EACH UNIT.
 ** PLEASE ALSO COORDINATE TYPES OF FIXTURES. (WALL
 SCONCES)
  
 ** THESE WERE S FEW EXAMPLES GIVEN AS A BENEFIT TO
 DESIGN TEAM. THIS IS NOT ALL FIXTURES AS THERE ARE
 OTHERS FOR OTHER UNITS WHICH E201 DOES NOT COORDINATE
 WITH E-205.
  
 5) NOTE: PLEASE BE AWARE OF NEW FLORIDA ADMINISTRATIVE
 CODE RULE 9B-3.0472. THIS REQUIRES ALL BUILDING PERMITS
 ISSUED AFTER JULY 1ST TO CONTAIN CO SENSORS WHEN
 MEETING THE PROVISIONS AND DEFINITIONS AS FOLLOWS.
 PLEASE SEE THIS RULING BECAME IN AFFECT AFTER ADOPTION
 OF FS 553.885.
 ** THIS CAN BE A PROVISO TO ADJUST ALL DEVICES ON PLANS
 HOWEVER PLANS ARE GOING BACK FOR CORRECTIONS AT THIS
 TIME.
  
  
 **********
  
 (1) DEFINITIONS: FORPURPOSES OF THIS RULE, THE
 FOLLOWING DEFINITIONS SHALL APPLY:
 (A) CARBON MONOXIDE ALARM. A DEVICE FOR THEPURPOSE OF
 DETECTING CARBON MONOXIDE, THAT PRODUCES A DISTINCT
 AUDIBLE ALARM,AND IS LISTED OR LABELED WITH THE
 APPROPRIATE STANDARD, EITHER ANSI/UL 2034 -96,
 STANDARD FOR SINGLE AND MULTIPLE STATION CO ALARMS,
 INCORPORATED HEREIN BYREFERENCE, OR UL 2075 - 04, GAS
 AND VAPOR DETECTOR SENSOR, INCORPORATED HEREINBY
 REFERENCE, IN ACCORDANCE WITH ITS APPLICATION. BOTH
 DOCUMENTS MAY BE OBTAINEDBY WRITING TO: CODES AND
 STANDARDS SECTION, DEPARTMENT OF COMMUNITY AFFAIRS,
 2555 SHUMARD OAK BOULEVARD, TALLAHASSEE, FLORIDA
 32399-2100.
  
 (B) FOSSIL FUEL. COAL, KEROSENE,OIL, FUEL GASES, OR
 OTHER PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS
 CARBONMONOXIDE AS A BY-PRODUCT OF COMBUSTION.
  
 (2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNINGHEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE ANOPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FORSLEEPING PURPOSES.
  
 (3) IN NEWCONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRINGWHEN SUCH
 WIRING IS SERVED FROM THE LOCAL POWER UTILITY. SUCH
 ALARMS SHALL HAVEBATTERY BACK UP.
  
 (4)COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY ANATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY,NEW 11-18-07.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]