2009-02-12 18:03:44 | ** DENIED REVIEW ** |
| |
| REVISION #9 |
| |
| 1) NOTE: PLANS SUBMITTED WERE FOR REVISION #9 WHICH WAS |
| FOR NEW SUPPLY FAN AND EXHAUST FANS ADDED. IN THE |
| REVIEW OF PAGE E-502 A REVISION #8 WAS LOCATED ON PANEL |
| SCHEDULE ELSW2 FOR CO CONTROL PANEL. HOWEVER A REVISION |
| #8 WAS NEVER SUBMITTED AND THE REVISED PLANS SHOWING |
| REVISIONS UP THROUGH REVISION #9 DOES NOT SHOW OR |
| INDICATE THIS NEW CO PANEL. |
| AS PLANS FOR ALL REVISED PANELS SHOWING ALL REVISED |
| LOADS WERE NOT SUBMITTED THESE OTHER ITEMS COULD NOT BE |
| REVIEWED. |
| SPOKE TO KAST CONSTRUCTION REPRESENTATIVE ON THE PHONE |
| AND REVISED ELECTRICAL SHEETS FOR FANS WILL NOT BE |
| NEEDED AT THIS TIME. FIELD INSPECTION WAS DONE AND FANS |
| ARE ALREADY TESTED BY INSPECTORS. THIS IS ALSO TO BE |
| VERIFIED WITH THE ELECTRICAL INSPECTOR. |
| THESE WILL BE PART OF REVISIONS TO BE SUBMITTED ON |
| 2/13/09. |
| |
| ** A CALLED BY PLACED TO TLC ENGINEERS @ 5:55PM TO GO |
| OVER COMMENTS. A MESSAGE WAS LEFT ON VOICE MAIL BRIEFLY |
| EXPLAINING THESE ITEMS AND TO RETURN PHONE CALL TO THIS |
| OFFICE. |
| |
| 2) NOTE: PLEASE BE SURE TO COORDINATE ALL REVISED |
| SHEETS TO DATE WHEN SUBMITTING REVISED PLANS AND |
| COORDINATION STUDY FOR REVIEW. |
| |
| |
| ** IMPORTANT ** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPARTMENT |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |