2009-01-31 10:40:39 | *** DENIED*** | | | | POOL PAK HEATER | | | | 1) NOTE: THE SUBMITTAL FOR THIS ITEM WAS NOT STAMPED OR | | REVIEWED BY THE ELECTRICAL ENGINEERING FIRM/DESIGNER OF | | RECORD. COMMENTS WILL ALSO BE MADE AT THIS HEATING UNIT | | IS NOT INCLUDED WITH THE SUBMITTED ENERGY CALCULATIONS. | | FBC13-412, 13-412.1.ABC.3 EQUIPMENT PERFORMANCE | | STANDARDS. | | THE SPECS SUBMITTED CONTAIN IDENTIFICATION OF MULTIPLE | | VOLTAGES. SOME SHEETS HAVE SOME HAND DRAWN CORRECTIONS | | AND OTHER SHEETS STILL HAVE 460/480V CIRCLED. PLEASE | | COORDINATE THESE ITEMS | | PLEASE SEE 13-412.1.ABC.3. WHERE DO THE SUBMITTED | | DOCUMENTS SHOW ANY INFORMATION OR COMPLIANCE WITH THIS | | TABLE FOR MINIMUM REQUIREMENTS? | | | | FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS. | | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|