2008-09-23 16:45:31 | BUILDING PLAN REVIEW |
| PERMIT: 08010249 |
| ADD: 295 LAKEVIEW AVE. |
| CONT: KAST CONSTRUCTION |
| TEL: (561)718-6141 |
| E-MAIL: [email protected] |
| |
| ARCH: PFVS/ GREGORY R PORTMAN |
| TEL: (404)503- 5000 |
| |
| STRUC: OMNJ/ THOMAS M BOG ACKI |
| TEL: (561)835-9994 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| WINDOW SHOP DRAWING REVIEW: |
| ACTION: DENIED |
| |
| 1) SHEET 9 OF 12 |
| A) W2- NOTE DETAIL4/10 INDICATES NO ANCHORS REQUIREDAT |
| CONTINIOUS JAMB WHERE AS DETAIL INDICATES ANCHOR |
| SPACING ON SIDE JAMBS. DISCREPANCY 106.1.2 ADDITIONAL |
| INFORMATION 1609..6 |
| |
| B) W-2 ALSO INDICATS THAT THE JAMBS & MULLION ARE NOT |
| REINFORCED, THE TRIBUTARY AREA FOR THE HORIZONTAL |
| MULLION IS ROUGHLY 46.5"X72" SHEET 3 OF 7 MULLIONS W/O |
| REINFORCEMENT INDICATE A -80.0 WHERE AS |
| THE WINDOW INDICATES A NEGATIVE 89. |
| |
| C) W-2A IS THE SAME SIZE WINDOW WITH THE SAME SITUATION |
| AS THE W-2 WINDOW. |
| |
| D) W-3A NO DESIGNATION AS TO MUTTINS. |
| |
| E) W-3A THE JAMB AND MULLION DETAIL INDICATES |
| NON-REINFORCED WITH LOW PRESSURES FROM NOA SHEET 3 OF |
| 7.UN-REINFORCED JAMBS AND MULLIONS ARE GOOD TO 80 PSF |
| THIS WINDOW IS INDICATED AS A -89.LOW PRESSURE |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |