Plan Review Notes For Permit 08010249 |
Permit Number |
08010249 |
|
Review Stop |
B |
Sequence Number |
20 |
|
Notes |
Date |
Text |
2008-09-18 13:40:18 | BUILDING PLAN REVIEW | | PERMIT: 08010249 | | ADD: 295 LAKEVIEW AVE. | | CONT: KAST CONSTRUCTION | | TEL: (561)718-6141 | | E-MAIL: [email protected] | | | | ARCH: PFVS/ GREGORY R PORTMAN | | TEL: (404)503- 5000 | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | TEL: (561)835-9994 | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2007 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | SUBMITTAL REVIEW: | | #093000-21 ULTRAFLEX 1 STANDARD POLYMER-ENRICHED TILE | | MORTER | | 00-3000-5 PRECAST 4X4 CONCRETE SHOWER SILL | | ACTION: REVIEWED | | | | BUILDING PROVISO: THIS REVIEW IS FOR THE USE OF | | ULTRAFLEX 1 TO BE USED ON THE INSTALATIOJN OF THE | | PRECAST 4X4 INCH CONCRETE SHOWER SILL ONLY. THE | | CONTRACTOR HAS NOT PROVIDED WHAT TYPE OF MATERIALS WILL | | BE SUBMITTED FOR SOUND DEADENING. THE SUBFLOOR FOR THIS | | PRODUCT IS VERY LIMITED AS TO THE PRODUCT MUST COMPLY | | WITH 1207.3 STRUCTURAL-BORNE SOUND . | | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES | | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A | | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE | | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS | | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE | | WITH ASTM E 492. |
|