Date |
Text |
2008-05-07 16:11:08 | REVIEW #: 2ND |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| ONE SET OF PLANS HAS BEEN MARKED-UP DURING REVIEW TO |
| ASSIST WITH CLARITY OF COMMENTS. |
| |
| 1 THROUGH 3: OK |
| |
| 4 THROUGH 9: THESE COMMENT RESPONSES ARE NOT ABLE TO BE |
| REVIEWED AT THIS TIME. THEY ALL INVOLVE CORRECTIONS TO |
| THE ENERGY CALCULATIONS, WHICH WERE NOT INCLUDED WITH |
| THIS RESUBMITTAL. PLEASE PROVIDE CORRECTED ENERGY |
| CALCULATIONS FOR REVIEW PRIOR TO PERMIT ISSUANCE IN |
| ACCORDANCE WITH FBCB 13-103.3. |
| |
| 10. OK |
| |
| 11. PG M-101A: |
| A) FIRE-RESISTANCE RATED WALLS HAVE BEEN ADDED TO |
| CORRIDOR AND LOBBY AREA AS SHOWN ON PG A-101A, A-401 |
| AND A-402. BASED ON THESE LOCATIONS, THERE ARE AT LEAST |
| FOUR DUCT PENETRATIONS OF RATED WALLS AT OFFICE 124 AND |
| OFFICE 126 WHICH ARE NOT PROTECTED. SHOW HOW THESE |
| PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH |
| FBCM 607.5. COORDINATE ANY AND ALL CHANGES IN WALL |
| TYPES BETWEEN ARCHITECTURAL, LIFE SAFETY AND MECHANICAL |
| PLANS. |
| NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA |
| WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE |
| DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE |
| DESIGN INTENT. |
| B) THE 18X20 GREASE EXHAUST DUCT FROM KITCHEN 115 IS |
| NOW SHOWN PENETRATING TWO RATED WALL ASSEMBLIES. A |
| GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A |
| FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE |
| ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET |
| TERMINAL IN ACCORDANCE WITH FBCM 506.3.10. SHOW HOW |
| THIS DUCT IS TO BE ENCLOSED IN ACCORDANCE WITH THIS |
| SECTION OR EXCEPTION #1. |
| C) DISHWASHER EXHAUST DUCT IS SHOWN PENETRATING |
| CORRIDOR WALL WITH FIRE/SMOKE DAMPER AT WALL |
| PENETRATION. THIS DUCT WILL BE CONVEYING HOT, |
| MOISTURE-LADEN AIR TO THE OUTDOORS. IS THE FIRE/SMOKE |
| DAMPER AND DUCT USED AT THIS LOCATION DESIGNED FOR |
| THESE CONDITIONS? DUCTS CONVEYING MOISTURE-LADEN OR |
| WASTE-HEAT-LADEN AIR SHALL BE CONSTRUCTED, JOINED AND |
| SEALED IN AN APPROVED MANNER IN ACCORDANCE WITH FBCM |
| 506.4.2. PLEASE PROVIDE ADDITIONAL DETAILS FOR THIS |
| APPLICATION. |
| |
| 12 THROUGH 19: OK |
| |
| 20. PG M-102A: NOTES HAVE BEEN CORRECTED AND MADE |
| LEGIBLE. HOWEVER, TWO OF THE CO SENSORS IN THIS AREA |
| ARE BEING DESIGNATED BY MECHANICAL NOTE #2 RATHER THAN |
| NOTE #7. PLEASE CORRECT FBCM 404, FBCB 106.1.1. |
| |
| 21 THROUGH 23: OK |
| |
| 24.M-102A: OK EXCEPT: STAIR PRESSURIZATION TEST WILL |
| BE REQUIRED FOR BOTH PRESSURIZED STAIRS TO VERIFY |
| COMPLIANCE WITH MAXIMUM DOOR OPENING FORCES ALLOWED PER |
| FBCB 11-4.13.11. THIS WILL BE A PROVISO ON IN EFFECT |
| UNTIL FINAL MECHANICAL INSPECTION HAS PASSED. ALSO, PG |
| M-404 STILL SHOWS STAIR PRESSURIZATION FANS CONNECTED |
| TO A BUILDING SMOKE CONTROL SYSTEM WHICH DOES NOT |
| EXIST. PLEASE CORRECT. IN ADDITION, BOTH SF-2 AND SF-3 |
| WILL REQUIRE DUCT SMOKE DETECTORS FOR FAN SHUT-DOWN IN |
| ACCORDANCE WITH FBCM 606.2. |
| |
| 25 THROUGH 28: OK |
| |
| 29. PG M-103A: THE DESIGN INTENT IN THIS AREA REMAINS |
| UNCLEAR. WHILE ARCHITECTURAL PLANS NOW SHOW THESE DUCTS |
| IN A RATED ENCLOSURE, THIS PAGE ALSO SHOWS TWO |
| FIRE/SMOKE DAMPERS AT THE FLOOR PENETRATION WHILE PG |
| M-102A SHOWS TWO FIRE DAMPERS AT THE FLOOR PENETRATION. |
| |
| NOTE: WHILE THE DESIGN IS PERMITTED TO EXCEED MINIMUM |
| CODE REQUIREMENTS, A SHAFT ENCLOSURE IS NOT REQUIRED AT |
| THIS LOCATION IN ACCORDANCE WITH FBCM 607.6.1. |
| PROVIDING THE TWO FIRE DAMPERS SHOWN ON M-102A AND TWO |
| FIRE DAMPERS AT THE WALL PENETRATIONS BETWEEN ROOMS 231 |
| AND 235 WOULD ELIMINATE THE NEED FOR A SHAFT ENCLOSURE |
| AND THE 6 COMBINATION FIRE/SMOKE DAMPERS SHOWN ON |
| M-103A. THIS, OF COURSE, DEPENDS ON THE DESIGN INTENT. |
| |
| 30. PG M-103A: IN EXITWAY 230, PROVIDE A |
| THROUGH-PENETRATION FIRESTOP SYSTEM DETAIL FOR THE 6 |
| INCH ROUND EXHAUST DUCT PENETRATING THE RATED WALL INTO |
| EXITWAY 230 WITH NO FIRE DAMPER IN ACCORDANCE WITH FBCM |
| 607.1.1. |
| NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA |
| WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE |
| DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE |
| DESIGN INTENT. |
| |
| 31 THROUGH 38: OK |
| |
| 39. M-105A AND M-105B: PLEASE SEE COMMENT #24 ABOVE. |
| ALSO, WIND RESISTANCE CRITERIA FOR OUTDOOR APPLIANCES |
| WILL BE COVERED BY PROVISO ONCE ALL OTHER OUTSTANDING |
| COMMENTS ARE ADDRESSED AND PRIOR TO PERMIT ISSUANCE. |
| |
| 40. OK |
| |
| 41. PG M-404: PLEASE SHOW HEIGHT OF EXHAUST DISCHARGE |
| ABOVE ROOF TO BE MINIMUM 40 INCHES IN ACCORDANCE WITH |
| FBCM 506.3.12.1. ALSO, PLEASE SEE PG M-105A REGARDING |
| THE LOCATION OF KEF-1. EXHAUST OUTLETS SHALL BE LOCATED |
| NOT LESS THAN 10 FEET HORIZONTALLY FROM PARTS OF THE |
| SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY LINES |
| AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE |
| WITH FBCM 506.3.12.3. THE MINIMUM HORIZONTAL DISTANCE |
| BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE |
| BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH |
| STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN |
| DISCHARGE OPENING IN ACCORDANCE WITH FBCM 506.5.5. |
| |
| 42. OK |
| |
| IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |