2008-05-07 16:11:08REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
 ONE SET OF PLANS HAS BEEN MARKED-UP DURING REVIEW TO
 ASSIST WITH CLARITY OF COMMENTS.
  
 1 THROUGH 3: OK
  
 4 THROUGH 9: THESE COMMENT RESPONSES ARE NOT ABLE TO BE
 REVIEWED AT THIS TIME. THEY ALL INVOLVE CORRECTIONS TO
 THE ENERGY CALCULATIONS, WHICH WERE NOT INCLUDED WITH
 THIS RESUBMITTAL. PLEASE PROVIDE CORRECTED ENERGY
 CALCULATIONS FOR REVIEW PRIOR TO PERMIT ISSUANCE IN
 ACCORDANCE WITH FBCB 13-103.3.
  
 10. OK
  
 11. PG M-101A:
 A) FIRE-RESISTANCE RATED WALLS HAVE BEEN ADDED TO
 CORRIDOR AND LOBBY AREA AS SHOWN ON PG A-101A, A-401
 AND A-402. BASED ON THESE LOCATIONS, THERE ARE AT LEAST
 FOUR DUCT PENETRATIONS OF RATED WALLS AT OFFICE 124 AND
 OFFICE 126 WHICH ARE NOT PROTECTED. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5. COORDINATE ANY AND ALL CHANGES IN WALL
 TYPES BETWEEN ARCHITECTURAL, LIFE SAFETY AND MECHANICAL
 PLANS.
 NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA
 WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE
 DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE
 DESIGN INTENT.
 B) THE 18X20 GREASE EXHAUST DUCT FROM KITCHEN 115 IS
 NOW SHOWN PENETRATING TWO RATED WALL ASSEMBLIES. A
 GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A
 FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE
 ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET
 TERMINAL IN ACCORDANCE WITH FBCM 506.3.10. SHOW HOW
 THIS DUCT IS TO BE ENCLOSED IN ACCORDANCE WITH THIS
 SECTION OR EXCEPTION #1.
 C) DISHWASHER EXHAUST DUCT IS SHOWN PENETRATING
 CORRIDOR WALL WITH FIRE/SMOKE DAMPER AT WALL
 PENETRATION. THIS DUCT WILL BE CONVEYING HOT,
 MOISTURE-LADEN AIR TO THE OUTDOORS. IS THE FIRE/SMOKE
 DAMPER AND DUCT USED AT THIS LOCATION DESIGNED FOR
 THESE CONDITIONS? DUCTS CONVEYING MOISTURE-LADEN OR
 WASTE-HEAT-LADEN AIR SHALL BE CONSTRUCTED, JOINED AND
 SEALED IN AN APPROVED MANNER IN ACCORDANCE WITH FBCM
 506.4.2. PLEASE PROVIDE ADDITIONAL DETAILS FOR THIS
 APPLICATION.
  
 12 THROUGH 19: OK
  
 20. PG M-102A: NOTES HAVE BEEN CORRECTED AND MADE
 LEGIBLE. HOWEVER, TWO OF THE CO SENSORS IN THIS AREA
 ARE BEING DESIGNATED BY MECHANICAL NOTE #2 RATHER THAN
 NOTE #7. PLEASE CORRECT FBCM 404, FBCB 106.1.1.
  
 21 THROUGH 23: OK
  
 24.M-102A: OK EXCEPT: STAIR PRESSURIZATION TEST WILL
 BE REQUIRED FOR BOTH PRESSURIZED STAIRS TO VERIFY
 COMPLIANCE WITH MAXIMUM DOOR OPENING FORCES ALLOWED PER
 FBCB 11-4.13.11. THIS WILL BE A PROVISO ON IN EFFECT
 UNTIL FINAL MECHANICAL INSPECTION HAS PASSED. ALSO, PG
 M-404 STILL SHOWS STAIR PRESSURIZATION FANS CONNECTED
 TO A BUILDING SMOKE CONTROL SYSTEM WHICH DOES NOT
 EXIST. PLEASE CORRECT. IN ADDITION, BOTH SF-2 AND SF-3
 WILL REQUIRE DUCT SMOKE DETECTORS FOR FAN SHUT-DOWN IN
 ACCORDANCE WITH FBCM 606.2.
  
 25 THROUGH 28: OK
  
 29. PG M-103A: THE DESIGN INTENT IN THIS AREA REMAINS
 UNCLEAR. WHILE ARCHITECTURAL PLANS NOW SHOW THESE DUCTS
 IN A RATED ENCLOSURE, THIS PAGE ALSO SHOWS TWO
 FIRE/SMOKE DAMPERS AT THE FLOOR PENETRATION WHILE PG
 M-102A SHOWS TWO FIRE DAMPERS AT THE FLOOR PENETRATION.
  
 NOTE: WHILE THE DESIGN IS PERMITTED TO EXCEED MINIMUM
 CODE REQUIREMENTS, A SHAFT ENCLOSURE IS NOT REQUIRED AT
 THIS LOCATION IN ACCORDANCE WITH FBCM 607.6.1.
 PROVIDING THE TWO FIRE DAMPERS SHOWN ON M-102A AND TWO
 FIRE DAMPERS AT THE WALL PENETRATIONS BETWEEN ROOMS 231
 AND 235 WOULD ELIMINATE THE NEED FOR A SHAFT ENCLOSURE
 AND THE 6 COMBINATION FIRE/SMOKE DAMPERS SHOWN ON
 M-103A. THIS, OF COURSE, DEPENDS ON THE DESIGN INTENT.
  
 30. PG M-103A: IN EXITWAY 230, PROVIDE A
 THROUGH-PENETRATION FIRESTOP SYSTEM DETAIL FOR THE 6
 INCH ROUND EXHAUST DUCT PENETRATING THE RATED WALL INTO
 EXITWAY 230 WITH NO FIRE DAMPER IN ACCORDANCE WITH FBCM
 607.1.1.
 NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA
 WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE
 DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE
 DESIGN INTENT.
  
 31 THROUGH 38: OK
  
 39. M-105A AND M-105B: PLEASE SEE COMMENT #24 ABOVE.
 ALSO, WIND RESISTANCE CRITERIA FOR OUTDOOR APPLIANCES
 WILL BE COVERED BY PROVISO ONCE ALL OTHER OUTSTANDING
 COMMENTS ARE ADDRESSED AND PRIOR TO PERMIT ISSUANCE.
  
 40. OK
  
 41. PG M-404: PLEASE SHOW HEIGHT OF EXHAUST DISCHARGE
 ABOVE ROOF TO BE MINIMUM 40 INCHES IN ACCORDANCE WITH
 FBCM 506.3.12.1. ALSO, PLEASE SEE PG M-105A REGARDING
 THE LOCATION OF KEF-1. EXHAUST OUTLETS SHALL BE LOCATED
 NOT LESS THAN 10 FEET HORIZONTALLY FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY LINES
 AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE
 WITH FBCM 506.3.12.3. THE MINIMUM HORIZONTAL DISTANCE
 BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE
 BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH
 STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN
 DISCHARGE OPENING IN ACCORDANCE WITH FBCM 506.5.5.
  
 42. OK
  