Date |
Text |
2008-05-20 11:41:35 | 1. PLEASE EXPLAIN CARD READERS ON STAIR # 1 DOORS. THE |
| USE OF EXIT DOORS SHALL NOT REQUIRE THE USE OF A CARD |
| SO THAT THEY CAN BE UTILIZED. CARD READERS ALSO NOTED |
| ON EXITWAY DOOR AND OTHER LOCATIONS PER THE DOOR |
| SCHEDULE DISPLAYED ON PAGE A-611. PLEASE EXPLAIN |
| RATIONALE. ALL RATED FIRE DOORS AND APPURTENANT |
| EQUIPMENT SHALL COMPLY WITH NFPA 80, THE STANDARD FOR |
| FIRE DOORS AND WINDOWS AND BE EQUIPPED WITH |
| SELF-CLOSING DEVICES TO CAUSE THE DOORS TO POSITIVELY |
| LATCH WHEN CLOSED. |
| |
| 2. PLEASE PROVIDE FLAMESPREAD DATE FOR CANOPY SHOWN ON |
| PAGE A-202. |
| |
| 3. THE FIRE DEPARTMENT CONNECTION SHALL BE EQUIPPED |
| WITH LOCKING KNOX-BOX CAPS. |
| |
| 4. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF |
| THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| |
| 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| NOTE # 11 ON ARCHITECTURAL SHEETS REGARDING TACTILE |
| SIGNAGE MAY BE CONFUSING TO SOME. |
| |
| 6. KEY NOTES # 2 "KEY CARD ACCESS ON ARCHITECTURAL |
| SHEETS NEEDS TO BE FURTHER EXPLAINED. EXIT ACCESS AND |
| EXIT DOORS SHALL NOT REQUIRE THE USE OF AKY, TOOL, |
| SPECIAL KNOWLDEGE TO EXIT. |
| |
| 7. THE GREASE DUCT ILLUSTRATED ON PAGE A-100D SHALL |
| MEET ALL OF THE REQUIREMENTS OF NFPA 96. |
| |
| 8. EMERGENCY INSTRUCTIONS FOR RESIDENTS AND GUESTS ARE |
| REQUIRED ON EVERY HOTEL ROOM DOOR. FIRE SAFETY |
| INFORMATION SHALL BE PROVIDED TO GUESTS. |
| |
| 9. LISTED QUICK RESPONSE OR LISTED RESIDENTIAL |
| SPRINKLERS SHALL BE PROVIDED FOR THE FIRE SPRINKLER |
| SYSTEM. |
| |
| 10. HEARING IMPAIRED ROOMS SHALL BE EQUIPPED WITH |
| VISIBLE NOTIFICATION APPLIANCES. |
| |
| 11. MECHANICAL DRAWINGS DISPLAY SEVERAL DEFICIENCIES |
| THAT HAVE BEEN HIGHLIGHTED IN RED BY THE MECHANICAL |
| PLAN REVIEWER. SEVERAL ARE RELATED TO FIRE AND LIFE |
| SAFETY. |
| |
| 12. THE NO EXIT SIGNS SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 7 OF THE LIFE SAFETY CODE. |
| |
| 13. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE |
| CORRECTED. |
| |
| |
| MIKE CARSILLO, BATTALION CHIEF |
| BUREAU OF FIRE PREVENTION |
| 804-4724 PHONE |
| 804-4774 FAX |