2008-05-24 12:16:32 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6652 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2004 AS AMENDED/REVISED |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS |
| PER THE BUILDING PLAN REVIEW OF 2/25/08: |
| |
| 3B)FBC 715.3SHEET A-611,FIRE-RATED DOORS ON THE |
| EXIT ACCESS CORRIDOR SERVING THE CONFERENCE ROOM(S). |
| DOORS 127 AND 153 ARE NOT SHOWN AS FIRE-RATED ON DOOR |
| SCHEDULE SHEET A-611.REVISE THE DOOR SCHEDULE. |
| |
| 3C)FBC 715.3SHEET A-101A AND SHEET A-611, |
| FIRE-RATED DOORS REQUIRED IN OCCUPANCY SEPARATION WALL |
| BETWEEN PARKING GARAGE AND LOBBY.DOOR 131 IS NOT |
| SHOWN AS FIRE-RATED ON DOOR SCHEDULE SHEET A-611. |
| REVISE THE DOOR SCHEDULE. |
| |
| 3E)FBC 302.3.2SHEET A-102B (AND CORRESPONDING LIFE |
| SAFETY SHEET G-007) AND SHEET A-103B.ON SHEET A-102B |
| (AND CORRESPONDING LIFE SAFETY SHEET G-007), THE |
| MEZZANINE LEVEL WALL ON GRID 2 BETWEEN GRIDS A AND B.4 |
| IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR FIRE-RATED |
| OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE PARKING |
| GARAGE AND EMERGENCY ELECTRICAL ROOM.AMEND SHEET |
| A-102B.ALSO, ON SHEET A-103B, THE SECOND FLOOR LEVEL |
| WALL BETWEEN THE PARKING GARAGE AND THE GUEST LAUNDRY |
| NEAR GRID B/1.2 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR |
| FIRE-RATED OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE |
| PARKING GARAGE AND THE VESTIBULE AND ELECTRICAL ROOM. |
| AMEND SHEET A-103B. |
| |
| 3M) FBC 1012.1SHEET A-702, STAIR #2 - ROOF LEVEL |
| PLAN.STAIR ACCESS TO THE ROOF HAS BEEN PROVIDED BUT |
| THE GUARDRAIL DOES NOT CONTINUE TO THE SOUTH WALL.THE |
| LANDING SHALL HAVE GUARDING AGAINST FALLING.AMEND |
| SHEET A-702. |
| |
| 4I) FBC* 106.1.2SHEET AC-102.COMPACTOR SCISSOR |
| LIFT.SUBMIT SHOP DRAWINGS AND MANUFACTURER'S |
| SPECIFICATION WITHIN 90 DAYS OF PERMIT ISSUANCE. |
| |
| 5B) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN |
| PARKING GARAGE OCCUPANCY SEPARATION WALL.DOORS M004, |
| M005A, M013 ARE SHOWN AS 45 MINUTE OR 20 MINUTE |
| FIRE-RATED ON DOOR SCHEDULE SHEET A-611.THESE DOORS |
| SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.REVISE THE |
| DOOR SCHEDULE.ALSO, DOOR M005B IS SHOWN AS NON-RATED. |
| IT IS AN ELEVATOR LOBBY DOOR AND SHALL BE A MINIMUM OF |
| 20 MINUTE FIRE-RATED.REVISE THE DOOR SCHEDULE. |
| |
| 6B) FBC 707.2SHEET A-102B.CHASES AND PARTITION |
| WALLS ABOVE ROOMS 104-108.CONTRARY TO THE COMMENT |
| RESPONSE LETTER, WALL TYPE TAGS HAVE NOT BEEN ADDED TO |
| THE CHASES CALLING THEM OUT AS 2 HOUR FIRE-RATED |
| CHASES.ALSO, THE WALL TYPE TAGS ON THE PARTITIONS |
| SEPARATING THE ROOMS ON SHEET A-102B WOULD CLARIFY THE |
| INTENTION AT THIS LEVEL. |
| |
| 8D) FBC 707.4SHEET A-103A, DOOR 245 TO THE LINEN |
| SHAFT TERMINATION ROOM IS SHOWN ON DOOR SCHEDULE SHEET |
| A611 AS 45 MINUTE FIRE-RATED.THE DOOR SHALL BE A |
| MINIMUM OF 90 MINUTE FIRE-RATED.ALSO, THE WALL |
| BETWEEN THE TERMINATION ROOM AND THE VENDING/ICE ROOM |
| DOES NOT HAVE A WALL TYPE TAG TO SHOW THE REQUIRED |
| FIRE-RATING.AMEND SHEET A-103A. |
| |
| 9A) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN |
| PARKING GARAGE OCCUPANCY SEPARATION WALL.DOOR 237 IS |
| 20 MINUTE FIRE-RATED ON DOOR SCHEDULE SHEET A-611. |
| THIS DOOR SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED. |
| REVISE THE DOOR SCHEDULE. |
| |
| 11C) FBC 707.2SHEET A-104B.CHASES IN THE ELECTRICAL |
| ROOM 302/402/502 AND IN THE PARTITIONS BETWEEN HOTEL |
| ROOMS.CONTRARY TO THE COMMENT RESPONSE LETTER, WALL |
| TYPE TAGS HAVE NOT BEEN ADDED TO THE CHASE IN THE |
| ELECTRICAL ROOM.ALSO, THERE ARE NO WALL TYPE TAGS ON |
| THE CHASES IN THE PARTITION WALLS SEPARATING HOTEL |
| ROOMS. |
| |
| 20) PROVISO:EXTERIOR LIGHT GAUGE METAL FRAMING TO BE |
| SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE |
| DESIGNER OF RECORD, APPROVED AND STAMPED. |
| |
| 21) PROVISO:FIN WALL SHOWN ON SHEET A-511, DETAIL 9. |
| THE STEEL FRAME AND "CURTAIN WALL" FOR THIS DECORATIVE |
| ELEMENT OF THE BUILDING SHALL BE SUBMITTED AS SHOP |
| DRAWINGS AFTER BEING REVIEWED BY THE DESIGNER OF |
| RECORD, APPROVED AND STAMPED. |
| |
| 22D) MULLION PRODUCT APPROVAL.IT IS NOTED THAT THE |
| MULLION LENGTHS HAVE BEEN IDENTIFIED BY HIGHLIGHTER PEN |
| ON THE PRODUCT APPROVAL.PLEASE NOTE THAT WE REQUIRE |
| THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, ETC. IN |
| INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP WHEN THE |
| DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF THE |
| PROJECT UNDER THE MANDATORY RECORD RETENTION PROGRAM. |
| THIS APPLIES TO ALL IDENTIFICATION MARKING ON ALL |
| PRODUCT APPROVALS AND OTHER DOCUMENTS. |
| |
| 22I)PRE-ENGINEERED A/C EQUIPMENT STANDS.NO PRODUCT |
| APPROVAL OR COMMENT RESPONSE WAS SUBMITTED TO ADDRESS |
| THE COMMENT REQUIRING SUBMITTAL OF PRODUCT APPROVAL |
| DOCUMENTATION FOR PRE-ENGINEERED A/C EQUIPMENT STANDS. |
| |
| 22J) CARLISLE ROOFING PRODUCT APPROVAL.IT IS NOTED |
| THAT THE ROOFING PRODUCT APPROVAL DOCUMENTS HAVE BEEN |
| MARKED UP WITH HIGHLIGHTER PEN.PLEASE NOTE THAT WE |
| REQUIRE THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, |
| ETC. IN INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP |
| WHEN THE DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF |
| THE PROJECT UNDER THE MANDATORY RECORD RETENTION |
| PROGRAM.THIS APPLIES TO ALL IDENTIFICATION MARKINGS |
| ON ALL PRODUCT APPROVALS AND OTHER DOCUMENTS. |
| |
| 30A)FBC 903.2.7FIRE SPRINKLERS.CONTRARY TO THE |
| COMMENT RESPONSE LETTER, THE REVISED FIRE PROTECTION |
| PLANS DO NOT SHOW FIRE SPRINKLER COVERAGE IN THE |
| ELEVATOR SHAFT ABOVE THE SECOND FLOOR LEVEL.SEE |
| FP-204A AND FP-205A (BOTH REVISION B, SIGNED AND SEALED |
| ON 4/15/08). |
| |
| 30B)THERE IS STILL NO SHEET FP-205B.IF THIS IS |
| INTENTIONAL, IT WOULD BE MORE CLEAR IF SHEET FP-205A |
| HAD A NOTE TO THAT EFFECT RATHER THAN A "MATCHLINE". |
| |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |