Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop B
Sequence Number 2
Notes
Date Text
2008-05-24 12:16:32BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004 AS AMENDED/REVISED
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE BUILDING PLAN REVIEW OF 2/25/08:
  
 3B)FBC 715.3SHEET A-611,FIRE-RATED DOORS ON THE
 EXIT ACCESS CORRIDOR SERVING THE CONFERENCE ROOM(S).
 DOORS 127 AND 153 ARE NOT SHOWN AS FIRE-RATED ON DOOR
 SCHEDULE SHEET A-611.REVISE THE DOOR SCHEDULE.
  
 3C)FBC 715.3SHEET A-101A AND SHEET A-611,
 FIRE-RATED DOORS REQUIRED IN OCCUPANCY SEPARATION WALL
 BETWEEN PARKING GARAGE AND LOBBY.DOOR 131 IS NOT
 SHOWN AS FIRE-RATED ON DOOR SCHEDULE SHEET A-611.
 REVISE THE DOOR SCHEDULE.
  
 3E)FBC 302.3.2SHEET A-102B (AND CORRESPONDING LIFE
 SAFETY SHEET G-007) AND SHEET A-103B.ON SHEET A-102B
 (AND CORRESPONDING LIFE SAFETY SHEET G-007), THE
 MEZZANINE LEVEL WALL ON GRID 2 BETWEEN GRIDS A AND B.4
 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR FIRE-RATED
 OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE PARKING
 GARAGE AND EMERGENCY ELECTRICAL ROOM.AMEND SHEET
 A-102B.ALSO, ON SHEET A-103B, THE SECOND FLOOR LEVEL
 WALL BETWEEN THE PARKING GARAGE AND THE GUEST LAUNDRY
 NEAR GRID B/1.2 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR
 FIRE-RATED OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE
 PARKING GARAGE AND THE VESTIBULE AND ELECTRICAL ROOM.
 AMEND SHEET A-103B.
  
 3M) FBC 1012.1SHEET A-702, STAIR #2 - ROOF LEVEL
 PLAN.STAIR ACCESS TO THE ROOF HAS BEEN PROVIDED BUT
 THE GUARDRAIL DOES NOT CONTINUE TO THE SOUTH WALL.THE
 LANDING SHALL HAVE GUARDING AGAINST FALLING.AMEND
 SHEET A-702.
  
 4I) FBC* 106.1.2SHEET AC-102.COMPACTOR SCISSOR
 LIFT.SUBMIT SHOP DRAWINGS AND MANUFACTURER'S
 SPECIFICATION WITHIN 90 DAYS OF PERMIT ISSUANCE.
  
 5B) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN
 PARKING GARAGE OCCUPANCY SEPARATION WALL.DOORS M004,
 M005A, M013 ARE SHOWN AS 45 MINUTE OR 20 MINUTE
 FIRE-RATED ON DOOR SCHEDULE SHEET A-611.THESE DOORS
 SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.REVISE THE
 DOOR SCHEDULE.ALSO, DOOR M005B IS SHOWN AS NON-RATED.
 IT IS AN ELEVATOR LOBBY DOOR AND SHALL BE A MINIMUM OF
 20 MINUTE FIRE-RATED.REVISE THE DOOR SCHEDULE.
  
 6B) FBC 707.2SHEET A-102B.CHASES AND PARTITION
 WALLS ABOVE ROOMS 104-108.CONTRARY TO THE COMMENT
 RESPONSE LETTER, WALL TYPE TAGS HAVE NOT BEEN ADDED TO
 THE CHASES CALLING THEM OUT AS 2 HOUR FIRE-RATED
 CHASES.ALSO, THE WALL TYPE TAGS ON THE PARTITIONS
 SEPARATING THE ROOMS ON SHEET A-102B WOULD CLARIFY THE
 INTENTION AT THIS LEVEL.
  
 8D) FBC 707.4SHEET A-103A, DOOR 245 TO THE LINEN
 SHAFT TERMINATION ROOM IS SHOWN ON DOOR SCHEDULE SHEET
 A611 AS 45 MINUTE FIRE-RATED.THE DOOR SHALL BE A
 MINIMUM OF 90 MINUTE FIRE-RATED.ALSO, THE WALL
 BETWEEN THE TERMINATION ROOM AND THE VENDING/ICE ROOM
 DOES NOT HAVE A WALL TYPE TAG TO SHOW THE REQUIRED
 FIRE-RATING.AMEND SHEET A-103A.
  
 9A) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN
 PARKING GARAGE OCCUPANCY SEPARATION WALL.DOOR 237 IS
 20 MINUTE FIRE-RATED ON DOOR SCHEDULE SHEET A-611.
 THIS DOOR SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.
 REVISE THE DOOR SCHEDULE.
  
 11C) FBC 707.2SHEET A-104B.CHASES IN THE ELECTRICAL
 ROOM 302/402/502 AND IN THE PARTITIONS BETWEEN HOTEL
 ROOMS.CONTRARY TO THE COMMENT RESPONSE LETTER, WALL
 TYPE TAGS HAVE NOT BEEN ADDED TO THE CHASE IN THE
 ELECTRICAL ROOM.ALSO, THERE ARE NO WALL TYPE TAGS ON
 THE CHASES IN THE PARTITION WALLS SEPARATING HOTEL
 ROOMS.
  
 20) PROVISO:EXTERIOR LIGHT GAUGE METAL FRAMING TO BE
 SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED AND STAMPED.
  
 21) PROVISO:FIN WALL SHOWN ON SHEET A-511, DETAIL 9.
 THE STEEL FRAME AND "CURTAIN WALL" FOR THIS DECORATIVE
 ELEMENT OF THE BUILDING SHALL BE SUBMITTED AS SHOP
 DRAWINGS AFTER BEING REVIEWED BY THE DESIGNER OF
 RECORD, APPROVED AND STAMPED.
  
 22D) MULLION PRODUCT APPROVAL.IT IS NOTED THAT THE
 MULLION LENGTHS HAVE BEEN IDENTIFIED BY HIGHLIGHTER PEN
 ON THE PRODUCT APPROVAL.PLEASE NOTE THAT WE REQUIRE
 THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, ETC. IN
 INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP WHEN THE
 DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF THE
 PROJECT UNDER THE MANDATORY RECORD RETENTION PROGRAM.
 THIS APPLIES TO ALL IDENTIFICATION MARKING ON ALL
 PRODUCT APPROVALS AND OTHER DOCUMENTS.
  
 22I)PRE-ENGINEERED A/C EQUIPMENT STANDS.NO PRODUCT
 APPROVAL OR COMMENT RESPONSE WAS SUBMITTED TO ADDRESS
 THE COMMENT REQUIRING SUBMITTAL OF PRODUCT APPROVAL
 DOCUMENTATION FOR PRE-ENGINEERED A/C EQUIPMENT STANDS.
  
 22J) CARLISLE ROOFING PRODUCT APPROVAL.IT IS NOTED
 THAT THE ROOFING PRODUCT APPROVAL DOCUMENTS HAVE BEEN
 MARKED UP WITH HIGHLIGHTER PEN.PLEASE NOTE THAT WE
 REQUIRE THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS,
 ETC. IN INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP
 WHEN THE DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF
 THE PROJECT UNDER THE MANDATORY RECORD RETENTION
 PROGRAM.THIS APPLIES TO ALL IDENTIFICATION MARKINGS
 ON ALL PRODUCT APPROVALS AND OTHER DOCUMENTS.
  
 30A)FBC 903.2.7FIRE SPRINKLERS.CONTRARY TO THE
 COMMENT RESPONSE LETTER, THE REVISED FIRE PROTECTION
 PLANS DO NOT SHOW FIRE SPRINKLER COVERAGE IN THE
 ELEVATOR SHAFT ABOVE THE SECOND FLOOR LEVEL.SEE
 FP-204A AND FP-205A (BOTH REVISION B, SIGNED AND SEALED
 ON 4/15/08).
  
 30B)THERE IS STILL NO SHEET FP-205B.IF THIS IS
 INTENTIONAL, IT WOULD BE MORE CLEAR IF SHEET FP-205A
 HAD A NOTE TO THAT EFFECT RATHER THAN A "MATCHLINE".
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS