2008-09-09 13:44:12 | BUILDING PLAN REVIEW |
| PERMIT: 08010249 |
| ADD: 295 LAKEVIEW AVE. |
| CONT: KAST CONSTRUCTION |
| TEL: (561)718-6141 |
| E-MAIL: [email protected] |
| |
| ARCH: PFVS/ GREGORY R PORTMAN |
| TEL: (404)503- 5000 |
| |
| STRUC: OMNJ/ THOMAS M BOGACKI |
| TEL: (561)835-9994 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| SUBMITTAL REVIEW |
| ACTION: DENIED |
| |
| SHOP DRAWING: STEEL RACKS @ ROOF |
| |
| 1) PLEASE PROVIDE ADDITIONAL INFORMATION ON WHAT THIS |
| SUBMITTAL IS TO BE USED FOR, IT APPEARS TO BE A |
| SCREENING ENCLOSURE TO HIDE THE RTU ON THE TOP OF THE |
| ROOF. IN DOING SO THIS WILL NEED TO UPDATE |
| SHEETS A-105-A AND A105-B AS TO THIS WOULD BE A |
| REVISION TO BE REVIEWED BY ZONING AND BUILDING. |
| |
| 2) THE SECOND ISSUE IS THIS DETAIL INDICATES CHAIN-LINK |
| BRACKETS BY OTHERS, BUT AGAIN IF FENCING IS TO BE |
| APPLIED AS A SCREENING TYPE MATERIAL, IT WOULD ALSO |
| NEED THE BLINDS INSERTED INTO EACH ROW CREATING A |
| NON-VIEWABLE FENCING THAT WOULD NOT ALLOW WIND TO |
| TRAVEL THROUGH, AND THERE IS NO INDICATION THAT THE |
| ENGINEER OF RECORD THIS REVISION SINCE THE STRUCTURAL |
| PLANS S106-A & S-106B ONLY INDICATE EMBEDS IN THE ROOF |
| SLAB AND THE ACTUAL RTU STANDS WILL BE SUPPLIED LATTER |
| AND REVIEWED AT THAT TIME. |
| |
| 3) THE SHOP DRAWING STAMP IS NOT EVEN ON THIS DOCUMENT |
| BUT A COPY ATTACHED TO ANOTHER PAGE. FL 61G-15-30.006 |
| (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| REVIEW. |
| |
| 4) SINCE THIS IS DOES NOT SHOW UP ON ANY |
| ARCHITECTURALNOR STRUCTURAL SHEETS WHAT ARE THE WIND |
| CRITERIA THIS AREA IS DESIGNED TOO? |
| 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE |
| BUILDING: |
| 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR |
| (KM/HR). |
| |
| 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING |
| CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 |
| AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. |
| |
| 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS |
| UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND |
| DIRECTION SHALL BE INDICATED. |
| |
| 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF |
| DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. |
| 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES |
| IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION |
| OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT |
| SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN |
| PROFESSIONAL. |
| |
| 5) IN REVIEWING THIS DOCUMENT WITH THE MECHANICAL PLAN |
| REVIEWER, IT WOULD APPEAR THIS STRUCTURE WOULD BE MORE |
| THAN A MERE FENCE ENCLOSURE THAT IS TO HIDE THE RTU |
| UNITS, BUT IN ACTUALLITY THIS MAY BE A STRUCTURE TO |
| HOLD THE ACTUAL CLADDING OR PORTIONS OF CLADDING OF THE |
| ROOF TOP UNITS THAT MAY BLOW OF IN A HIGH WIND EVENT. |
| JUNE 27/08 MECHANICAL PROVISO # 1 INDICATED THE NEED TO |
| ILLUSTRATE COMPLIANCE WITH 301.13 FBCM AND ALTERNATE |
| MEANS AND METHODS MAY BE ONE VEHICLE TO BE USED IF |
| ENGINEERING OF THESE UNITS WAS NOT SUBMITTED AND |
| REVIEWED AS CODE COMPLIANT. IN DOING SO ANY DOCUMENTS |
| TO BE SUBMITTED AS ALTERNATE MEANS AND METHODS WILL |
| NEED TO BE SUBMITTED IN WRITING WITH CALCULATIONS AND |
| TO BE REVIEWED BY THE BUILDING OFFICAL. THE SAME ISSUES |
| WILL OCCUR IF THIS STRUCTURE IS TO RESTRICT PORTIONS OF |
| THE RTU CLADDING WIND WILL NOT BE ABLE TO TRAVEL |
| THRUOGH, PROVIDE CALCULATIONS INDICATING COMPLIANCE |
| WITH 301.13 FBCM. |
| |
| JIM WITMER C. B. O. |
| BUILDING PLAN REVIEW II |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |
| |
| PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| |
| |
| |