Date Text
2008-09-15 08:17:47REVIEW #: REVISION 5
 ACTION:DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-101B: THIS PLAN SHOWS SEVERAL CHANGES TO THE
 GENERATOR ROOM EXHAUST SYSTEM. HOWEVER, THESE CHANGES
 ARE NOT IDENTIFIED ON THE PLANS AS A PERT OF THIS
 REVISION. CLEARLY MARK AND INDENTIFY ON PLANS ALL
 CHANGES FROM THE CURRENT PERMIT DOCUMENTS TO FACILITATE
 AN ACCURATE REVIEW OF THE AMENDED CONSTRUCTION
 DOCUMENTS IN ACCORDANCE WITH FBCB 106.4. ALSO, PLEASE
 MAINTAIN THE REVISION HISTORY AT THE TITLE BLOCKS ON
 THE PLANS TO AID IN TRACKING AND RECORDS RETENTION.
 REVISION #4, WHICH HAS BEEN INCORPORATED INTO THE
 PERMIT SET OF PLANS, NO LONGER APPEARS IN THE REVISION
 HISTORY.
  
 NOTE: THIS IS ONE EXAMPLE OF ONE CHANGE WHICH HAS NOT
 BEEN IDENTIFIED. PLEASE CHECK THE ENTIRE REVISION SET
 AND ENSURE ALL REVISIONS ARE CLEARLY INDICATED ON PLANS
 PRIOR TO RESUBMISSION.
  
 2. PAGE M-101B: THERE IS AN UNNECESSARY LAYER SHOWING
 KITCHEN EQUIPMENT IN THE GARAGE AND TRASH COMPACTOR
 AREA. PLEASE REMOVE ERRONEOUS LAYERS AND PROVIDE PLANS
 WHICH ARE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED IN
 ACCORDANCE WITH FBCB 106.1.1.
  
 3. PAGE M-101B: GENERATOR ROOM NOTE INDICATES THAT THE
 DUCT FROM EF-7 IS TO ATTACH TO THE GENERATOR WITH
 FLEXIBLE DUCT CONNECTIONS. IT IS UNCLEAR AS TO WHY THE
 DUCT WOULD CONNECT TO THE GENERATOR ITSELF. PROVIDE
 ADDITIONAL DETAIL WHICH CLARIFIES THE INTENT OF THIS
 DESIGN AND DEMONSTRATES COMPLIANCE WITH FBCM 915.2 AND
 FBCM 304.1.
  
 4. PAGE M-101B: THE CHANGES TO THE GENERATOR ROOM
 VENTILATION AND GENERATOR EXHAUST SYSTEMS WILL HAVE AN
 IMPACT ON THE DESIGN AS SHOWN ON SEVERAL OTHER PAGES OF
 THE PLANS. HOWEVER, THESE OTHER PAGES ARE NOT A PART OF
 THIS REVISION. PLEASE COORDINATE CHANGES ON THIS PAGE
 WITH ALL OTHER PAGES WHICH MAY ME AFFECTED BY THEM.
 SUBMIT ALL PAGES WHICH ARE PART OF THIS CHANGE WITHIN
 THE SAME REVISION TO FACILITATE AN ACCURATE REVIEW AND
 DEMONSTRATE COMPLIANCE WITH THE PROVISIONS OF FBCM
 915.2, FBCM 401.5, 401.6 AND FBCM CHAPTER 5.
  
 5. PAGES M-103B THROUGH M-104B AND M-408: FLOOR PLANS
 HAVE BEEN CHANGED TO SHOW 6 INCH ROUND EXHAUST DUCTS
 GOING TO EXHAUST RISERS. HOWEVER, RISER DIAGRAMS ARE
 STILL SHOWING 4 INCH ROUND DUCTS IN SEVERAL LOCATIONS.
 PLEASE CLARIFY BY COORDINATING DUCT SIZES ON FLOOR
 PLANS WITH DETAILS AND RISER DIAGRAMS IN ACCORDANCE
 WITH FBCM 603.1 AND FBCB 106.1.1.
  