Date |
Text |
2008-09-15 08:17:47 | REVIEW #: REVISION 5 |
| ACTION:DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PAGE M-101B: THIS PLAN SHOWS SEVERAL CHANGES TO THE |
| GENERATOR ROOM EXHAUST SYSTEM. HOWEVER, THESE CHANGES |
| ARE NOT IDENTIFIED ON THE PLANS AS A PERT OF THIS |
| REVISION. CLEARLY MARK AND INDENTIFY ON PLANS ALL |
| CHANGES FROM THE CURRENT PERMIT DOCUMENTS TO FACILITATE |
| AN ACCURATE REVIEW OF THE AMENDED CONSTRUCTION |
| DOCUMENTS IN ACCORDANCE WITH FBCB 106.4. ALSO, PLEASE |
| MAINTAIN THE REVISION HISTORY AT THE TITLE BLOCKS ON |
| THE PLANS TO AID IN TRACKING AND RECORDS RETENTION. |
| REVISION #4, WHICH HAS BEEN INCORPORATED INTO THE |
| PERMIT SET OF PLANS, NO LONGER APPEARS IN THE REVISION |
| HISTORY. |
| |
| NOTE: THIS IS ONE EXAMPLE OF ONE CHANGE WHICH HAS NOT |
| BEEN IDENTIFIED. PLEASE CHECK THE ENTIRE REVISION SET |
| AND ENSURE ALL REVISIONS ARE CLEARLY INDICATED ON PLANS |
| PRIOR TO RESUBMISSION. |
| |
| 2. PAGE M-101B: THERE IS AN UNNECESSARY LAYER SHOWING |
| KITCHEN EQUIPMENT IN THE GARAGE AND TRASH COMPACTOR |
| AREA. PLEASE REMOVE ERRONEOUS LAYERS AND PROVIDE PLANS |
| WHICH ARE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED IN |
| ACCORDANCE WITH FBCB 106.1.1. |
| |
| 3. PAGE M-101B: GENERATOR ROOM NOTE INDICATES THAT THE |
| DUCT FROM EF-7 IS TO ATTACH TO THE GENERATOR WITH |
| FLEXIBLE DUCT CONNECTIONS. IT IS UNCLEAR AS TO WHY THE |
| DUCT WOULD CONNECT TO THE GENERATOR ITSELF. PROVIDE |
| ADDITIONAL DETAIL WHICH CLARIFIES THE INTENT OF THIS |
| DESIGN AND DEMONSTRATES COMPLIANCE WITH FBCM 915.2 AND |
| FBCM 304.1. |
| |
| 4. PAGE M-101B: THE CHANGES TO THE GENERATOR ROOM |
| VENTILATION AND GENERATOR EXHAUST SYSTEMS WILL HAVE AN |
| IMPACT ON THE DESIGN AS SHOWN ON SEVERAL OTHER PAGES OF |
| THE PLANS. HOWEVER, THESE OTHER PAGES ARE NOT A PART OF |
| THIS REVISION. PLEASE COORDINATE CHANGES ON THIS PAGE |
| WITH ALL OTHER PAGES WHICH MAY ME AFFECTED BY THEM. |
| SUBMIT ALL PAGES WHICH ARE PART OF THIS CHANGE WITHIN |
| THE SAME REVISION TO FACILITATE AN ACCURATE REVIEW AND |
| DEMONSTRATE COMPLIANCE WITH THE PROVISIONS OF FBCM |
| 915.2, FBCM 401.5, 401.6 AND FBCM CHAPTER 5. |
| |
| 5. PAGES M-103B THROUGH M-104B AND M-408: FLOOR PLANS |
| HAVE BEEN CHANGED TO SHOW 6 INCH ROUND EXHAUST DUCTS |
| GOING TO EXHAUST RISERS. HOWEVER, RISER DIAGRAMS ARE |
| STILL SHOWING 4 INCH ROUND DUCTS IN SEVERAL LOCATIONS. |
| PLEASE CLARIFY BY COORDINATING DUCT SIZES ON FLOOR |
| PLANS WITH DETAILS AND RISER DIAGRAMS IN ACCORDANCE |
| WITH FBCM 603.1 AND FBCB 106.1.1. |
| |