Plan Review Notes For Permit 08010249 |
Permit Number |
08010249 |
|
Review Stop |
E |
Sequence Number |
12 |
|
Notes |
Date |
Text |
2009-01-31 08:58:31 | *** DENIED *** | | | | PANEL BOARD/ BREAKERS SUBMITTAL. | | | | 1) NOTE: PLEASE CORRECT THE SUBMITTALS AS NOTED BY THE | | ENGINEERING FIRM. THERE ARE SEVERAL ITEMS WHICH DO NOT | | COORDINATE WITH PLANS. IF AIC RATINGS ARE BEING REVISED | | ON THE ACTUAL EQUIPMENT INSTALLED IN FIELD THEN IT WILL | | BE REQUIRED TO REVISE THE COORDINATION STUDY. | | THE RATINGS ON EMERGENCY EQUIPMENT, PANELS AND BREAKERS | | PER 240.12, 700.27, AND 701.18 ARE REQUIRED AS A LIFE | | SAFETY REQUIREMENT. | | ** IMPORTANT** | | THERE ARE OTHER ITEMS ON THE SUBMITTALS WHICH ARE NOT | | NOTED BY ENGINEERING FIRM WHICH DO NOT COORDINATE WITH | | PLANS. AN EXAMPLE IS THE RATINGS OF BREAKERS IN SOME | | PANELS. ONE WOULD BE THE PLANS ON REV #7 SUBMITTED | | CONTAINS A 2-POLE 80AMP BREAKER ON PANEL HP2LW (SECT 1) | | FOR AHU #6, HOWEVER THE ITEM #16 FOR THIS SAME PANEL ON | | SUBMITTALS DOES NOT INDICATE THIS BREAKER. | | THIS IS ONE EXAMPLE ONLY. | | | | FBC 106.1.1 FOR COORDINATION WITH PLANS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW II | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|