Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 12
Notes
Date Text
2009-01-31 08:58:31*** DENIED ***
  
 PANEL BOARD/ BREAKERS SUBMITTAL.
  
 1) NOTE: PLEASE CORRECT THE SUBMITTALS AS NOTED BY THE
 ENGINEERING FIRM. THERE ARE SEVERAL ITEMS WHICH DO NOT
 COORDINATE WITH PLANS. IF AIC RATINGS ARE BEING REVISED
 ON THE ACTUAL EQUIPMENT INSTALLED IN FIELD THEN IT WILL
 BE REQUIRED TO REVISE THE COORDINATION STUDY.
 THE RATINGS ON EMERGENCY EQUIPMENT, PANELS AND BREAKERS
 PER 240.12, 700.27, AND 701.18 ARE REQUIRED AS A LIFE
 SAFETY REQUIREMENT.
 ** IMPORTANT**
 THERE ARE OTHER ITEMS ON THE SUBMITTALS WHICH ARE NOT
 NOTED BY ENGINEERING FIRM WHICH DO NOT COORDINATE WITH
 PLANS. AN EXAMPLE IS THE RATINGS OF BREAKERS IN SOME
 PANELS. ONE WOULD BE THE PLANS ON REV #7 SUBMITTED
 CONTAINS A 2-POLE 80AMP BREAKER ON PANEL HP2LW (SECT 1)
 FOR AHU #6, HOWEVER THE ITEM #16 FOR THIS SAME PANEL ON
 SUBMITTALS DOES NOT INDICATE THIS BREAKER.
 THIS IS ONE EXAMPLE ONLY.
  
 FBC 106.1.1 FOR COORDINATION WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  