Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 11
Notes
Date Text
2009-01-29 19:20:38*** DENIED ***
  
 1) NOTE: LIGHTING SUBMITTALS FOR INTERIOR LIGHTING IN
 GUEST ROOMS CONTAINS GENERAL NOTES WITH RESPECT TO THE
 INNCOM LIGHTING SYSTEM.
 THE GENERAL NOTES STATES THE T-STAT E528 DEVICE WILL
 NOT PROVIDE SUFFICIENT COVERAGE FOR THE CONTROL OF
 LIGHTING IN ROOMS BASED ON THE LOCATION AS SHOWN. THE
 NOTE ALSO STATES AN ADDITIONAL K594 DEVICE WOULD BE
 REQUIRED FOR FULL COVERAGE. THE DEVICE SCHEDULE HOWEVER
 DOES NOT CONTAIN ANY ADDITIONAL DEVICE FOR REQUIRED
 COVERAGE.
 THE LIGHTING SUBMITTAL SUBMITTED BY THE CONTRACTOR DOES
 HOWEVER INDICATE THE T-STAT E528 DEVICE IN A DIFFERENT
 LOCATION WHICH IS MORE CENTRAL TO ROOM. PLEASE
 COORDINATE THE ELECTRICAL PLANS AS THESE ARE THE FINAL
 DESIGN DOCUMENTS FOR THE ROOM.
 IF AN OCCUPANT IS LOCATED IN BED AREA AND THE T-STAT
 WHICH IS LOCATED AT THE DOOR DOES NOT PROVIDE COVERAGE
 THEN AN OCCUPANT WOULD NOT BE ABLE TO TURN LIGHTING FOR
 EGRESS AROUND THE GUEST ROOM OR EGRESS OUT OF THE ROOM.
 FBC 13-415.1.ABC.1.3, NFPA-101 7.8
  
 FBC 106.1.1 FOR COORDINATION WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  