2008-03-10 15:57:52 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 BUILDING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| FHA-98 DESIGN MANUAL |
| CITY WPB MUNICIPAL CODES |
| |
| 1. SHT G.000 GUESTROOM MATRIX. THE TOTAL FOR FOR THE |
| QUEEN STANDARD IS SHOWN AS 81, BUT ADDS UP TO 72. |
| PLEASE RECHECK THE CALCULATIONS. SECTIONS 106.1.2 & |
| 11-9.1.2. |
| |
| 2. SHT G.000 GUESTROOM MATRIX DOES NOT COMPLY WITH |
| SECTION 11-9.1.4 AS THERE IS NOT ACCESSIBLE BOARDROOM |
| SUITE AVAILABLE. |
| |
| 3. SHT G.000 PER SECTION 11-9.1.2, PURSANT TO CHAPTER |
| 509, FLORIDA STATUTES, A NUMBER OF ROOMS EQUALLING AT |
| LEAST 5% OF THE GUEST ROOMS MINUM THE NUMBER OF |
| ACCESSIBLE ROOMS REQUIRED BY TABLE BELOW SHALL PROVIDE |
| ADDITIONAL FEATURES OF SECTION 11-9.2.3. ONE ROOM IS |
| REQUIRED, PLEASE INDICATE THE ROOM NUMBER & LOCATION OF |
| THE REQUIRED ROOM. |
| |
| 4. SHTS G-00- THRU G-009 & SHTS AC-101 THRU A-812. THE |
| PRINTED NAME OF THE PERSON SEALING THE DOCUMENTS IS |
| REQUIRED ON EACH SHEET. FAC 61G1-16.004(6) & FS |
| 481.2055. |
| |
| 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE |
| SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE |
| INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201 |
| THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS |
| P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE |
| SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES |
| ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT |
| REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX |
| WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3. |
| |
| 6. SHT AC-102 SHOWS A COMPACTOR PAD FLOOR DRAIN. PLEASE |
| INDICATE IF THE COMPACTOR WILL BE COMPACTING GREASY |
| WASTE. ALSO THE STORM WATER CAN NOT DRAIN INTO THE |
| SANITARY SYSTEM. INDICATE THE METHOD OF KEEPING THE |
| STORM WATER OUT OF THE SANT. SYSTEM. ARTICLE III, |
| SECTION 90-125(B)(5). IN THE PAST WHEN THIS ISSUE CAME |
| UP, WE INDICATED THAT THE DRAIN IS NOT REQUIRED. PLEASE |
| CLARIFY. |
| |
| 7. ALL PLUMBING SHEETS THAT INDICATE "TYPICAL LEVEL |
| PLAN". PLEASE INDICATE WHAT FLOORS THE PLANS ARE |
| TYPICAL OF. SECTIONS 106.1.1 & 106.1.2. |
| |
| 8. SHT A-100D IS INDICATED AS TYPICAL LEVEL PLAN 4TH |
| FLOOR. ARE THE 3RD & 5TH FLOORS DIFFERENT. THESE FLOORS |
| HAVE NOT BEEN SUBMITTED. SECTIONS 106.1.1 & 106.1.2. |
| |
| 9. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. |
| OF BUSINESS REGULATION. (DBPR), DIVISION OF HOTEL AND |
| RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO |
| RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF 3 |
| SETS OF PLANS WITH THE DBPR REVIEW SHALL BE SUBMITTED. |
| THE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED TO THE |
| SHEET WITH THE DBPR PLAN REVIEW STAMP. SECTION |
| 102.2.1. |
| |
| 10. SHT A-423 DETAILS 1, 3, 7 & 8 THE TURNING AREA |
| SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE |
| TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 8 |
| SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV |
| PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2. |
| |
| 11. SHT A-425 DETAILS 1, 3, 4 & 5 THE TURNING AREA |
| SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE |
| TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 5 |
| SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV |
| PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2. |
| |
| 12 SHT A-4.26 DETAIL 1 THE TURNING AREA SHALL BE |
| UNOBSTRUCTED. THE W/C CAN NOT BE IN THE TURNING AREA. |
| SECTION 11-4.22.3.--DETAILS 1 & 6 SHALL SHOW THE |
| CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV PER SECTIONS |
| 11-4.16.2, 11-4.19.3 & 11-4.20.2. |
| |
| 13. SHT A-612 THE WALL FINISH FOR THE TOILET ROOMS 112, |
| 113, 137 & 138 IS STATED AS "VARIES"PLEASE SHOW |
| COMPLIANCE WITH SECTION 1210.2 REQUIREMENT FOR THE |
| WALLS WITHIN 2 FT OF THE TOILETS OR URINALS SHALL HAVE |
| A "SMOOTH, HARD, NONABSORBENT" SURFACE. |
| |
| 14. ALL MECH, PLMG & ELECT SHEETS. THE ADDRESS OF THE |
| ENGINEER FIRM ON THE TITLE BLOCKS DOES NOT REFLECT THE |
| ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE. |
| PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE SO |
| THEY REFLECT PRIOR TO RESUBMITTING TO THE CITY FOR |
| REVIEW. IF MULTIPLE ADDRESS, PLEASE ADD THE ADDRESS OF |
| RECORD TO TITLE BLOCKS. FAC 61G15-23.002(2) & FS |
| 471.025. |
| |
| 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 |
| GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING |
| TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. |
| INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW |
| METHOD. SECTIONS 106.1.2 & 608. |
| |
| 16. SHT P-101A A 2-WAY CLEANOUT IS REQUIRED AT THE |
| INLET AND EXIT OF EACH GREASE INTERCEPTOR. PLEASE |
| INDICATE ON THE CLEANOUT BETWEEN THE GREASE |
| INTERCEPTORS. UTILITY STANDARD FOR GREASE INTERCEPTORS |
| & SECTION 708.3.2. |
| |
| 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY |
| FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A |
| DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER. |
| IF CONNECTING TO THE STORM SEWER, A RELIEF VENT, |
| (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE |
| BUILDING. SECTION 314.2.1. |
| |
| 18. SHT P101AINDICATES "6 INCH PDD DN 4546SF. PLEASE |
| SHOW WHERE THE LINE IS AND INDICATE WHAT PDD STANDS FOR |
| AS IT IS NOT INDICATED ON THE ABBREVIATION SCHEDULE ON |
| SHT P-001. SECTION 106.1.2. |
| |
| 19. SHT P-101B THE COMPACTOR INDICATES4" GREASE |
| (4DFU'S), BUT SHOWS THE FLOOR DRAIN CONNECTING TO THE |
| SANITARY SYSTEM. PLEASE SEE COMMENT #6. SECTION |
| 106.1.1 |
| |
| 20. SHT P-101B CLEANOUTS ARE REQUIRED ON THE SANITARY & |
| STORM SYSTEMS PER SECTIONS 708.3.5 & 1101.8. |
| |
| 21. SHTS P-102A P-102B, P-103A & P-103B THE CONDENSATE |
| SHALL DRAIN FROM THE BUILDING SEPARATELY. (SEE COMMENT |
| #17).--THE BACKWATER VALVES ARE NOT REQUIRED IF THE |
| RELIEF VENTS ARE INSTALLED. |
| |
| 22. SHT P-103A THE W/C & LAV ARE NOT SHOWN ON THE FLOOR |
| PLAN IN ROOM 219. PLEASE SHOW ALL FIXTURES ON FLOOR |
| PLAN. SECTION 106.1.1. |
| |
| 23. SHT P-103A SAN-8A RISER "B" SHOWS TUBS ON THE |
| RISER, BUT SHOWERS ON THE FLOOR PLAN. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 24. SHT P-103A SHOWERS ARE NOT SHOWN ON THE FLOOR PLAN |
| IN ROOMS 213 THRU 216, 224 & 225.--PLEASE SHOW |
| RISER DESIGNATIONS FOR RISERS ST/14 & STO/14. SECTION |
| 106.1.2. |
| |
| 25. SHT P-103B SANITARY RISER SAN-4A SHOWS SHOWERS ON |
| THE FLOOR PLAN, BUT TUBS ON THE RISER DIAGRAM. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 26. SHT P-104A KING ROOMS 449, *48, 447, 445, 432, 430, |
| 429 & 431 SHOW SHOWERS ON THE FLOOR PLAN, BUT TUBS ON |
| THE RISER DIAGRAMS. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 27. SHT P-104A INDICATES RISER "C" ON THE FLOOR PLAN, |
| BUT RISER "C" NOT SUBMITTED. PLEASE CLARIFY. SECTION |
| 106.1.1. |
| |
| 28. SHT P-104A RISER SAN-10A THE SINK, (S-1) SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT FOR THE BATHROOM |
| FIXTURES. SECTION 909.1. |
| |
| 29. SHT P-104B KING ROOMS 413, 414, 415 &416 SHOWS |
| SHOWERS ON THE FLOOR PLAN, BUT SHOWS TUBS ON THE RISER |
| DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 30. SHTS P-105A & P-105B INDICATE THE RISER DESIGNATION |
| NUMBERS AT THE ROOF DRAINS/OD'S TO TRACK RISER THRU |
| BUILDING. SECTION 106.1.2. |
| |
| 31. SHT P-203A THE SHOWERS ARE NOT SHOWN ON THE FLOOR |
| PLAN IN MANY ROOMS/UNITS. PLEASE SHOW ALL FIXTURES ON |
| THE FLOOR PLAN. SECTION 106.1.1. |
| |
| 32. SHT P-203A SUBMIT THE RISER DIAGRAM FOR THE LAUNDRY |
| ROOM. SHOW ALL PIPE SIZES, VALVES & REQUIRED WATER |
| HAMMER ARRESTORS. SECTIONS 103.5.1.3, 604.1, 604.9, |
| 606.2(1). |
| |
| 33. SHT. P-203A IDENTIFY FIXTURE (TMV-3) SHOWN AT COL. |
| LINE D BETWEEN COLS 10 & 11. SECTION 106.1.2. |
| |
| 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE |
| IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN |
| BE FOUND. SECTION 106.1.2. |
| |
| 35. SHT P-302 IDENTIFY COLD WATER RISER NEAR COL. LINE |
| E/8.5. (NOT SHOWN ON THE RISER DIAGRAM). SECTION |
| 106.1.2. |
| |
| 36. SHT P-302 HOT WATER SUPPLY ONLY SHOWN TO RISER #45 |
| ON THE FLOOR PLAN, BUT THE NOTE INDICATES HW & CW TO |
| RISER. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE |
| REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.-- |
| THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN |
| DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE |
| INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL |
| EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT |
| MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART. |
| INDICATE MODEL NUMBERS. SECTION 607.3.2. |
| |
| 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK |
| SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER |
| SECTION 903.4. |
| |
| 38. SHT P-500 RISER SAN-10B SHOWS A DRY HORIZONTAL VENT |
| PAST FIXTURE BT-1. THIS IS PROHIBITED PER SECTIONS |
| 905.3 & 905.4. |
| |
| 39. SHT P-500 RISER SAN-10A THE S-1 SINK SHALL |
| DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM |
| FIXTURES. SECTION 909.1. |
| |
| 40 SHT P-500 RISER SAN-9A DOES NOT REFLECT THE FLOOR |
| PLAN AT THE 2ND FLOOR AND NOT ALL FIXTURES ARE VENTED. |
| PLEASE CORRELATE. SECTIONS 106.1.1 & 901.2.1. |
| |
| 41. SHT P-500 RISER SAN-8A DOES NOT REFLECT THE FLOOR |
| PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 42. SHT P-500 FIXTURE UPSTREAM OF RISER SAN-10 DOES NOT |
| REFLECT THE FLOOR PLAN. SHOWER INDICATED ON THE FLOOR |
| PLAN, FLOOR DRAIN ON RISER DIAGRAM. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 43. SHT P-500 CONNECTIONS TO THE BUILDING DRAIN AT |
| RISER SAN-10 & BRANCH LINE DO NOT REFLECT THE FLOOR |
| PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 44. SHT P-500 RISER SAN-8/9 OFFSET IN THE 1ST FLOOR |
| CEILING DOES NOT REFLECT THE FLOOR PLAN OFFSET. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 45. SHT P-500 RISERS SAN-6A, 7A, 8A, 12A & 13 DO NOT |
| REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 46. SHT P-500 RISER SAN-6 DOES NOT REFLECT THE FLOOR |
| PLAN AT THE OFFSET BELOW THE 3RD FLOOR. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 47. SHT P-500 RISER SAN-11 DOES NOT REFLECT THE FLOOR |
| PLAN AT THE BASE OF THE STACK. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 48. SHT P-500 VENTING ABOVE TOILET ROOMS 137 & 138 DOES |
| NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 49. SHT P-500 RISER SAN-12A DOES NOT REFLECT THE FLOOR |
| PLAN AT TOILET ROOM 2ND FLOOR. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 50. SHT P-500 RISER SAN-13 DOES NOT REFLECT THE FLOOR |
| PLAN 2ND FLOOR. FLOOR PLAN SHOWS SHOWER,RISER SHOWS |
| TUB. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 51. SHT P-500 2 WAY CLEANOUT REQUIRED BETWEEN THE |
| GREASE INTERCEPTORS. UTILITY STANDARD & SECTION |
| 708.3.2. |
| |
| 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK |
| SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER |
| SECTION 903.4. |
| |
| 53. SHT P-501 SHOW ALL PIPE SIZES FOR THE GREASE |
| SYSTEM. SECTIONS 701.1 AND TABLES 710.1(1) & 710.1(2). |
| |
| 54. SHT P-501 THE VENT PIPING FROM TOILET ROOMS 112 & |
| 113 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 55. SHT P-501 RISERS SAN-5A, 4A, 3A & 2A DO NOT REFLECT |
| THE FLOOR PLAN, NOR DO THEY MEET CODE REQUIREMENTS FOR |
| VENTING FOR THE SECOND FLOOR FIXTURES. PLEASE |
| CORRELATE. SECTIONS 106.1.1 & 901.2.1. |
| |
| 56. SHT P-501 RISERS FOR ROOMS 104, 105, 106 & 107 DO |
| NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT |
| REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 58. SHT P-501 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR |
| PLAN AT THE COMPACTOR, BUT ONLY ONE IS SHOWN ON THE |
| RISER DIAGRAM. PLEASE CLARIFY & PLEASE CORRELATE. |
| SECTION 106.1.1. (PLEASE SEE COMMENT #6). |
| |
| 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY |
| FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 60. SHT P-501 PIPING IN THE MEZZANINE CEILING FOR |
| RISERS SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN. |
| PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 61. SHTS P-500 & P-501 CLEANOUTS ARE REQUIRED AT THE |
| BASE OF EACH STACK PER SECTION 708.3.4. PLEASE SHOW ON |
| RISERS. |
| |
| 62. SHT P-502 SHOW 2 RISERS DESIGNATED RISER "E" PLEASE |
| CLARIFY. SECTION 106.1.1. |
| |
| 63. SHT P-502 SECOND RISER "E"THE S-1 SINK SHALL |
| DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM |
| FIXTURES. SECTION 909.1. |
| |
| 64. SHT P-503 FIVE HOSE BIBB LINES SHOWN ON THE FLOOR |
| PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 65. SHT P-504 THREE HOSE BIBB LINES SHOWN ON THE FLOOR |
| PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 66. SHT P-504 THE BRANCH LINE TO CW/18 DOES NOT REFLECT |
| THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 67. SHT P-504 THE BASE OF RISER CW/14A CONNECTION TO |
| THE WATER MAINS DOES NOT REFLECT THE FLOOR PLAN. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 68. SHT P-504 THE 1-1/4" HOT WATER BRANCH LINE DOES NOT |
| REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 69. SHT P-505 2 HOSE BIBB LINES SHOWN ON THE FLOOR PLAN |
| ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 70. SHT P-507 RISER "H" DOES NOT REFLECT THE FLOOR PLAN |
| PIPING FROM THE RISER AND TUBS ARE SHOWN ON THE FLOOR |
| PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 71. SHT P-600 CONDENSATE SHALL DRAIN SEPARATELY FROM |
| THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17). |
| |
| 72. SHT P-600 CONDENSATE INFORMATION NOTE STATES "SEE |
| DWG P-103 FOR CONT". SHT P-103 WAS NOT SUBMITTED. SHT |
| 103A 2ND FLOOR WEST DOES NOT SHOW RISER. PLEASE |
| INDICATE WHERE INFORMATION CONTINUES. SECTION 106.1.1. |
| |
| 73. SHT P-600 RISERS STO/8 & STO/9 DO NOT REFLECT THE |
| FLOOR PLAN AT THE TERMINATION. (SEE SHT P-101A). PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 74. SHT P-600 CLEANOUTS REQUIRED PER SECTION 1101.8. |
| PLEASE SHOW ALL REQUIRED C/O'S ON PLANS. |
| |
| 75. SHT P-600 PDD CONNECTION TO RISER ST/8-ST/9 DOES |
| NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 76. SHT P-600 RISERS ST/10 & STO/10 DO NOT REFLECT THE |
| FLOOR PLAN AT THE OFFSET & LOCATION OF RISER STO/10. |
| (SEE SHT P-102A). PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR |
| PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR |
| ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 |
| DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 79. SHT P-600 THE LOCATION OF STO/12 DOES NOT REFLECT |
| THE FLOOR PLAN.. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE |
| OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE |
| AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM |
| DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE |
| CORRELATE. SECTION 106.1.1. |
| |
| 81. SHT P-600 RISER STO/13 ALSO DOES NOT REFLECT THE |
| FLOOR PLAN. (SHT P-101A). PLEASE CORRELATE. SECTION |
| 106.1.1. |
| |
| 82. SHT P-600 RISER STO/14 IS SHOWN TO THE SOUTH SIDE |
| OF ST/14 ON THE FLOOR PLAN. RISER DOES NOT REFLECT THE |
| FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 83. SHT P-600 RISERS ST/14 & STO/14 DO NOT REFLECT THE |
| FLOOR PLAN AS IT SHOWS THE RISERS THRU THE 5TH FLOOR |
| AND TO THE UPPER ROOF. THE FLOOR PLAN SHOWS THE ROOF |
| DRAINS AT THE 2ND LEVEL LOWER ROOF. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM |
| THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17). |
| |
| 85. SHT P-601 CLEANOUTS REQUIRED PER SECTION 1101.8. |
| PLEASE SHOW ALL REQUIRED C/O'S ON PLANS. |
| |
| 86. SHT P-601 THE PIPING AT THE BASE OF RISERS ST/6 - |
| ST/7 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| SECTION 106.1.1. |
| |
| 87. SHT P-601 CONDENSATE NOTE REFERS TO DWG P--103A, |
| BUT NO RISER CONT. WAS FOUND. PLEASE INDICATE THE |
| LOCATION OF THE RISER DIAGRAMS. SECTION 106.1.2. |
| |
| 88. SHT P-601 THE PIPING OUT OF THE CATCH BASIN TO |
| RISERS ST/1 & ST/2 DOES NOT REFLECT THE FLOOR PLAN. |
| PLEASE CORRELATE. SECTION 106.1.1. |
| |
| 89. A SEPARATE IRRIGATION PERMIT AND PLANS ARE |
| REQUIRED. THIS CAN BE SUBMITTED AFTER BUILDING PERMITS |
| ARE ISSUED BUT PRIOR TO COMMENCMENT OF IRR. WORK. |
| (INFORMATIONAL). |
| |
| 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| INFORMATION IS REQUIRED: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE.--RISER NOTED, BUT THE ISOMETRIC |
| DRAWING DOES NOT REFLECT THE FLOOR PLAN AT THE WATER |
| HEATERS AND AT THE DRYERS. ALSOTHE LENGTHS OF PIPE |
| ARE NOT CLEAR AS INDICATED. PLEASE SHOW WHERE EACH |
| SECTION OF PIPE BEGINS AND WHERE EACH SECTION OF PIPE |
| ENDS.PLEASE CORRELATE. SECTION 106.1.1. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED.--THE PIPE |
| SIZES FOR THE RUNS INDICATED AS "A", "C" & "E" ARE |
| INCORRECT SIZES. RUN "A" SHALL BE 4", RUN "C" SHALL BE |
| 2-1/2" AND RUN "E" SHALL BE 2-1/2" PER TABLE 402.4(6). |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| E. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI.--SHT P-602 |
| INDICATES THE UTILITY COMPANY AS TECO GAS. THE GAS |
| PROVIDER IN WEST PALM BEACH IS FLORIDA PUBLIC UTILITIES |
| AND THEY PROVIDE THE GAS AT 1/2 PSI OR 2 PSI. PLEASE |
| INDICATE THE PROPER PROVIDER AND INDICATE THE CORRECT |
| DELIVERY PRESSURE. |
| |
| G. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| I. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| J. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED |
| LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL |
| HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |