2008-03-10 15:57:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 CITY WPB MUNICIPAL CODES
  
 1. SHT G.000 GUESTROOM MATRIX. THE TOTAL FOR FOR THE
 QUEEN STANDARD IS SHOWN AS 81, BUT ADDS UP TO 72.
 PLEASE RECHECK THE CALCULATIONS. SECTIONS 106.1.2 &
 11-9.1.2.
  
 2. SHT G.000 GUESTROOM MATRIX DOES NOT COMPLY WITH
 SECTION 11-9.1.4 AS THERE IS NOT ACCESSIBLE BOARDROOM
 SUITE AVAILABLE.
  
 3. SHT G.000 PER SECTION 11-9.1.2, PURSANT TO CHAPTER
 509, FLORIDA STATUTES, A NUMBER OF ROOMS EQUALLING AT
 LEAST 5% OF THE GUEST ROOMS MINUM THE NUMBER OF
 ACCESSIBLE ROOMS REQUIRED BY TABLE BELOW SHALL PROVIDE
 ADDITIONAL FEATURES OF SECTION 11-9.2.3. ONE ROOM IS
 REQUIRED, PLEASE INDICATE THE ROOM NUMBER & LOCATION OF
 THE REQUIRED ROOM.
  
 4. SHTS G-00- THRU G-009 & SHTS AC-101 THRU A-812. THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENTS IS
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(6) & FS
 481.2055.
  
 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE
 INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201
 THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS
 P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE
 SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES
 ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT
 REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX
 WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3.
  
 6. SHT AC-102 SHOWS A COMPACTOR PAD FLOOR DRAIN. PLEASE
 INDICATE IF THE COMPACTOR WILL BE COMPACTING GREASY
 WASTE. ALSO THE STORM WATER CAN NOT DRAIN INTO THE
 SANITARY SYSTEM. INDICATE THE METHOD OF KEEPING THE
 STORM WATER OUT OF THE SANT. SYSTEM. ARTICLE III,
 SECTION 90-125(B)(5). IN THE PAST WHEN THIS ISSUE CAME
 UP, WE INDICATED THAT THE DRAIN IS NOT REQUIRED. PLEASE
 CLARIFY.
  
 7. ALL PLUMBING SHEETS THAT INDICATE "TYPICAL LEVEL
 PLAN". PLEASE INDICATE WHAT FLOORS THE PLANS ARE
 TYPICAL OF. SECTIONS 106.1.1 & 106.1.2.
  
 8. SHT A-100D IS INDICATED AS TYPICAL LEVEL PLAN 4TH
 FLOOR. ARE THE 3RD & 5TH FLOORS DIFFERENT. THESE FLOORS
 HAVE NOT BEEN SUBMITTED. SECTIONS 106.1.1 & 106.1.2.
  
 9. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION. (DBPR), DIVISION OF HOTEL AND
 RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF 3
 SETS OF PLANS WITH THE DBPR REVIEW SHALL BE SUBMITTED.
 THE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED TO THE
 SHEET WITH THE DBPR PLAN REVIEW STAMP. SECTION
 102.2.1.
  
 10. SHT A-423 DETAILS 1, 3, 7 & 8 THE TURNING AREA
 SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE
 TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 8
 SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV
 PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2.
  
 11. SHT A-425 DETAILS 1, 3, 4 & 5 THE TURNING AREA
 SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE
 TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 5
 SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV
 PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2.
  
 12 SHT A-4.26 DETAIL 1 THE TURNING AREA SHALL BE
 UNOBSTRUCTED. THE W/C CAN NOT BE IN THE TURNING AREA.
 SECTION 11-4.22.3.--DETAILS 1 & 6 SHALL SHOW THE
 CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV PER SECTIONS
 11-4.16.2, 11-4.19.3 & 11-4.20.2.
  
 13. SHT A-612 THE WALL FINISH FOR THE TOILET ROOMS 112,
 113, 137 & 138 IS STATED AS "VARIES"PLEASE SHOW
 COMPLIANCE WITH SECTION 1210.2 REQUIREMENT FOR THE
 WALLS WITHIN 2 FT OF THE TOILETS OR URINALS SHALL HAVE
 A "SMOOTH, HARD, NONABSORBENT" SURFACE.
  
 14. ALL MECH, PLMG & ELECT SHEETS. THE ADDRESS OF THE
 ENGINEER FIRM ON THE TITLE BLOCKS DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE.
 PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE SO
 THEY REFLECT PRIOR TO RESUBMITTING TO THE CITY FOR
 REVIEW. IF MULTIPLE ADDRESS, PLEASE ADD THE ADDRESS OF
 RECORD TO TITLE BLOCKS. FAC 61G15-23.002(2) & FS
 471.025.
  
 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02
 GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING
 TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF.
 INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW
 METHOD. SECTIONS 106.1.2 & 608.
  
 16. SHT P-101A A 2-WAY CLEANOUT IS REQUIRED AT THE
 INLET AND EXIT OF EACH GREASE INTERCEPTOR. PLEASE
 INDICATE ON THE CLEANOUT BETWEEN THE GREASE
 INTERCEPTORS. UTILITY STANDARD FOR GREASE INTERCEPTORS
 & SECTION 708.3.2.
  
 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY
 FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A
 DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER.
 IF CONNECTING TO THE STORM SEWER, A RELIEF VENT,
 (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. SECTION 314.2.1.
  
 18. SHT P101AINDICATES "6 INCH PDD DN 4546SF. PLEASE
 SHOW WHERE THE LINE IS AND INDICATE WHAT PDD STANDS FOR
 AS IT IS NOT INDICATED ON THE ABBREVIATION SCHEDULE ON
 SHT P-001. SECTION 106.1.2.
  
 19. SHT P-101B THE COMPACTOR INDICATES4" GREASE
 (4DFU'S), BUT SHOWS THE FLOOR DRAIN CONNECTING TO THE
 SANITARY SYSTEM. PLEASE SEE COMMENT #6. SECTION
 106.1.1
  
 20. SHT P-101B CLEANOUTS ARE REQUIRED ON THE SANITARY &
 STORM SYSTEMS PER SECTIONS 708.3.5 & 1101.8.
  
 21. SHTS P-102A P-102B, P-103A & P-103B THE CONDENSATE
 SHALL DRAIN FROM THE BUILDING SEPARATELY. (SEE COMMENT
 #17).--THE BACKWATER VALVES ARE NOT REQUIRED IF THE
 RELIEF VENTS ARE INSTALLED.
  
 22. SHT P-103A THE W/C & LAV ARE NOT SHOWN ON THE FLOOR
 PLAN IN ROOM 219. PLEASE SHOW ALL FIXTURES ON FLOOR
 PLAN. SECTION 106.1.1.
  
 23. SHT P-103A SAN-8A RISER "B" SHOWS TUBS ON THE
 RISER, BUT SHOWERS ON THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 24. SHT P-103A SHOWERS ARE NOT SHOWN ON THE FLOOR PLAN
 IN ROOMS 213 THRU 216, 224 & 225.--PLEASE SHOW
 RISER DESIGNATIONS FOR RISERS ST/14 & STO/14. SECTION
 106.1.2.
  
 25. SHT P-103B SANITARY RISER SAN-4A SHOWS SHOWERS ON
 THE FLOOR PLAN, BUT TUBS ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 26. SHT P-104A KING ROOMS 449, *48, 447, 445, 432, 430,
 429 & 431 SHOW SHOWERS ON THE FLOOR PLAN, BUT TUBS ON
 THE RISER DIAGRAMS. PLEASE CORRELATE. SECTION 106.1.1.
  
 27. SHT P-104A INDICATES RISER "C" ON THE FLOOR PLAN,
 BUT RISER "C" NOT SUBMITTED. PLEASE CLARIFY. SECTION
 106.1.1.
  
 28. SHT P-104A RISER SAN-10A THE SINK, (S-1) SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT FOR THE BATHROOM
 FIXTURES. SECTION 909.1.
  
 29. SHT P-104B KING ROOMS 413, 414, 415 &416 SHOWS
 SHOWERS ON THE FLOOR PLAN, BUT SHOWS TUBS ON THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 30. SHTS P-105A & P-105B INDICATE THE RISER DESIGNATION
 NUMBERS AT THE ROOF DRAINS/OD'S TO TRACK RISER THRU
 BUILDING. SECTION 106.1.2.
  
 31. SHT P-203A THE SHOWERS ARE NOT SHOWN ON THE FLOOR
 PLAN IN MANY ROOMS/UNITS. PLEASE SHOW ALL FIXTURES ON
 THE FLOOR PLAN. SECTION 106.1.1.
  
 32. SHT P-203A SUBMIT THE RISER DIAGRAM FOR THE LAUNDRY
 ROOM. SHOW ALL PIPE SIZES, VALVES & REQUIRED WATER
 HAMMER ARRESTORS. SECTIONS 103.5.1.3, 604.1, 604.9,
 606.2(1).
  
 33. SHT. P-203A IDENTIFY FIXTURE (TMV-3) SHOWN AT COL.
 LINE D BETWEEN COLS 10 & 11. SECTION 106.1.2.
  
 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE
 IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN
 BE FOUND. SECTION 106.1.2.
  
 35. SHT P-302 IDENTIFY COLD WATER RISER NEAR COL. LINE
 E/8.5. (NOT SHOWN ON THE RISER DIAGRAM). SECTION
 106.1.2.
  
 36. SHT P-302 HOT WATER SUPPLY ONLY SHOWN TO RISER #45
 ON THE FLOOR PLAN, BUT THE NOTE INDICATES HW & CW TO
 RISER. PLEASE CORRELATE. SECTION 106.1.1.
  
 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE
 REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.--
 THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN
 DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE
 INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL
 EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT
 MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART.
 INDICATE MODEL NUMBERS. SECTION 607.3.2.
  
 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
  
 38. SHT P-500 RISER SAN-10B SHOWS A DRY HORIZONTAL VENT
 PAST FIXTURE BT-1. THIS IS PROHIBITED PER SECTIONS
 905.3 & 905.4.
  
 39. SHT P-500 RISER SAN-10A THE S-1 SINK SHALL
 DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM
 FIXTURES. SECTION 909.1.
  
 40 SHT P-500 RISER SAN-9A DOES NOT REFLECT THE FLOOR
 PLAN AT THE 2ND FLOOR AND NOT ALL FIXTURES ARE VENTED.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 901.2.1.
  
 41. SHT P-500 RISER SAN-8A DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 42. SHT P-500 FIXTURE UPSTREAM OF RISER SAN-10 DOES NOT
 REFLECT THE FLOOR PLAN. SHOWER INDICATED ON THE FLOOR
 PLAN, FLOOR DRAIN ON RISER DIAGRAM. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 43. SHT P-500 CONNECTIONS TO THE BUILDING DRAIN AT
 RISER SAN-10 & BRANCH LINE DO NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 44. SHT P-500 RISER SAN-8/9 OFFSET IN THE 1ST FLOOR
 CEILING DOES NOT REFLECT THE FLOOR PLAN OFFSET. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 45. SHT P-500 RISERS SAN-6A, 7A, 8A, 12A & 13 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 46. SHT P-500 RISER SAN-6 DOES NOT REFLECT THE FLOOR
 PLAN AT THE OFFSET BELOW THE 3RD FLOOR. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 47. SHT P-500 RISER SAN-11 DOES NOT REFLECT THE FLOOR
 PLAN AT THE BASE OF THE STACK. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 48. SHT P-500 VENTING ABOVE TOILET ROOMS 137 & 138 DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 49. SHT P-500 RISER SAN-12A DOES NOT REFLECT THE FLOOR
 PLAN AT TOILET ROOM 2ND FLOOR. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 50. SHT P-500 RISER SAN-13 DOES NOT REFLECT THE FLOOR
 PLAN 2ND FLOOR. FLOOR PLAN SHOWS SHOWER,RISER SHOWS
 TUB. PLEASE CORRELATE. SECTION 106.1.1.
  
 51. SHT P-500 2 WAY CLEANOUT REQUIRED BETWEEN THE
 GREASE INTERCEPTORS. UTILITY STANDARD & SECTION
 708.3.2.
  
 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
  
 53. SHT P-501 SHOW ALL PIPE SIZES FOR THE GREASE
 SYSTEM. SECTIONS 701.1 AND TABLES 710.1(1) & 710.1(2).
  
 54. SHT P-501 THE VENT PIPING FROM TOILET ROOMS 112 &
 113 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 55. SHT P-501 RISERS SAN-5A, 4A, 3A & 2A DO NOT REFLECT
 THE FLOOR PLAN, NOR DO THEY MEET CODE REQUIREMENTS FOR
 VENTING FOR THE SECOND FLOOR FIXTURES. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 901.2.1.
  
 56. SHT P-501 RISERS FOR ROOMS 104, 105, 106 & 107 DO
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT
 REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION
 106.1.1.
  
 58. SHT P-501 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR
 PLAN AT THE COMPACTOR, BUT ONLY ONE IS SHOWN ON THE
 RISER DIAGRAM. PLEASE CLARIFY & PLEASE CORRELATE.
 SECTION 106.1.1. (PLEASE SEE COMMENT #6).
  
 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY
 FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 60. SHT P-501 PIPING IN THE MEZZANINE CEILING FOR
 RISERS SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 61. SHTS P-500 & P-501 CLEANOUTS ARE REQUIRED AT THE
 BASE OF EACH STACK PER SECTION 708.3.4. PLEASE SHOW ON
 RISERS.
  
 62. SHT P-502 SHOW 2 RISERS DESIGNATED RISER "E" PLEASE
 CLARIFY. SECTION 106.1.1.
  
 63. SHT P-502 SECOND RISER "E"THE S-1 SINK SHALL
 DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM
 FIXTURES. SECTION 909.1.
  
 64. SHT P-503 FIVE HOSE BIBB LINES SHOWN ON THE FLOOR
 PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 65. SHT P-504 THREE HOSE BIBB LINES SHOWN ON THE FLOOR
 PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 66. SHT P-504 THE BRANCH LINE TO CW/18 DOES NOT REFLECT
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 67. SHT P-504 THE BASE OF RISER CW/14A CONNECTION TO
 THE WATER MAINS DOES NOT REFLECT THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 68. SHT P-504 THE 1-1/4" HOT WATER BRANCH LINE DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 69. SHT P-505 2 HOSE BIBB LINES SHOWN ON THE FLOOR PLAN
 ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 70. SHT P-507 RISER "H" DOES NOT REFLECT THE FLOOR PLAN
 PIPING FROM THE RISER AND TUBS ARE SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 71. SHT P-600 CONDENSATE SHALL DRAIN SEPARATELY FROM
 THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17).
  
 72. SHT P-600 CONDENSATE INFORMATION NOTE STATES "SEE
 DWG P-103 FOR CONT". SHT P-103 WAS NOT SUBMITTED. SHT
 103A 2ND FLOOR WEST DOES NOT SHOW RISER. PLEASE
 INDICATE WHERE INFORMATION CONTINUES. SECTION 106.1.1.
  
 73. SHT P-600 RISERS STO/8 & STO/9 DO NOT REFLECT THE
 FLOOR PLAN AT THE TERMINATION. (SEE SHT P-101A). PLEASE
 CORRELATE. SECTION 106.1.1.
  
 74. SHT P-600 CLEANOUTS REQUIRED PER SECTION 1101.8.
 PLEASE SHOW ALL REQUIRED C/O'S ON PLANS.
  
 75. SHT P-600 PDD CONNECTION TO RISER ST/8-ST/9 DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 76. SHT P-600 RISERS ST/10 & STO/10 DO NOT REFLECT THE
 FLOOR PLAN AT THE OFFSET & LOCATION OF RISER STO/10.
 (SEE SHT P-102A). PLEASE CORRELATE. SECTION 106.1.1.
  
 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR
 PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR
 ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION
 106.1.1.
  
 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12
 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 79. SHT P-600 THE LOCATION OF STO/12 DOES NOT REFLECT
 THE FLOOR PLAN.. PLEASE CORRELATE. SECTION 106.1.1.
  
 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE
 OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE
 AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM
 DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 81. SHT P-600 RISER STO/13 ALSO DOES NOT REFLECT THE
 FLOOR PLAN. (SHT P-101A). PLEASE CORRELATE. SECTION
 106.1.1.
  
 82. SHT P-600 RISER STO/14 IS SHOWN TO THE SOUTH SIDE
 OF ST/14 ON THE FLOOR PLAN. RISER DOES NOT REFLECT THE
 FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 83. SHT P-600 RISERS ST/14 & STO/14 DO NOT REFLECT THE
 FLOOR PLAN AS IT SHOWS THE RISERS THRU THE 5TH FLOOR
 AND TO THE UPPER ROOF. THE FLOOR PLAN SHOWS THE ROOF
 DRAINS AT THE 2ND LEVEL LOWER ROOF. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM
 THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17).
  
 85. SHT P-601 CLEANOUTS REQUIRED PER SECTION 1101.8.
 PLEASE SHOW ALL REQUIRED C/O'S ON PLANS.
  
 86. SHT P-601 THE PIPING AT THE BASE OF RISERS ST/6 -
 ST/7 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 87. SHT P-601 CONDENSATE NOTE REFERS TO DWG P--103A,
 BUT NO RISER CONT. WAS FOUND. PLEASE INDICATE THE
 LOCATION OF THE RISER DIAGRAMS. SECTION 106.1.2.
  
 88. SHT P-601 THE PIPING OUT OF THE CATCH BASIN TO
 RISERS ST/1 & ST/2 DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 89. A SEPARATE IRRIGATION PERMIT AND PLANS ARE
 REQUIRED. THIS CAN BE SUBMITTED AFTER BUILDING PERMITS
 ARE ISSUED BUT PRIOR TO COMMENCMENT OF IRR. WORK.
 (INFORMATIONAL).
  
 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--RISER NOTED, BUT THE ISOMETRIC
 DRAWING DOES NOT REFLECT THE FLOOR PLAN AT THE WATER
 HEATERS AND AT THE DRYERS. ALSOTHE LENGTHS OF PIPE
 ARE NOT CLEAR AS INDICATED. PLEASE SHOW WHERE EACH
 SECTION OF PIPE BEGINS AND WHERE EACH SECTION OF PIPE
 ENDS.PLEASE CORRELATE. SECTION 106.1.1.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--THE PIPE
 SIZES FOR THE RUNS INDICATED AS "A", "C" & "E" ARE
 INCORRECT SIZES. RUN "A" SHALL BE 4", RUN "C" SHALL BE
 2-1/2" AND RUN "E" SHALL BE 2-1/2" PER TABLE 402.4(6).
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.--SHT P-602
 INDICATES THE UTILITY COMPANY AS TECO GAS. THE GAS
 PROVIDER IN WEST PALM BEACH IS FLORIDA PUBLIC UTILITIES
 AND THEY PROVIDE THE GAS AT 1/2 PSI OR 2 PSI. PLEASE
 INDICATE THE PROPER PROVIDER AND INDICATE THE CORRECT
 DELIVERY PRESSURE.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  