2008-03-24 09:05:03 | 1. FIRE AND LIFE SAFETY CODE 2004 FLORIDA BUILDING CODE |
| SHOULD READ FLORIDA FIRE PREVENTION CODE ON PAGE |
| G-000. |
| |
| 2. FIRE WALL RATINGS BETWEEN PORTIONS OF THE HOTEL AND |
| PARKING GARAGE APPEARS TO BE ONLY ONE HOUR RATED ON |
| PAGE G-007. A TWO HOUR RATING IS REQUIRED BETWEEN |
| PARKING GARAGES AND OTHER PORTIONS OF THE BUILDING. |
| |
| 3. EXIT SIGN IN MEETING ROOM # 110 DIRECTS PERSONS INTO |
| CLOSET ON PAGE G-007. |
| |
| 4. SOME EXIT SIGNS APPEAR TO BE DIRECTING PERSONS TO |
| EXIT INTO GARAGE. THE GARAGE IS A MORE HAZARSOUS AREA |
| THAN THE HOTEL. PLEASE SEE PAGE G-007. EXITING IS NOT |
| PERMITTED TO PASS INTO A MORE HAZARDOUS AREA. |
| |
| 5. EXIT TRAVEL ROUTE ON PAGE G-007 IN GARAGE ON |
| MEZZANINE LEVEL TRAVELS OVER COLUMN TO REACH STAIR # |
| 2. |
| |
| 6. FIRE RATED WALLS BETWEEN GARAGE AND MEZZANINE ARE |
| ONLY ONE HOUR ON PAGE G-007. |
| |
| 7. OTHER EXIT ROUTE FROM GARAGE TOWARDS STAIR # 1 |
| APPEARS TO TRAVEL OVER A SHAFT, LIFE SAFETY MEZZANINE. |
| |
| 8. TRAVEL DISTANCE ROUTE ON THE LIFE SAFETY, SECOND |
| LEVEL APPEARS TO TRAVEL OVER PARKING STALLS ON PAGE |
| G-008. |
| |
| 9. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN |
| CORRIDOR ON SECOND LEVELS AND TYPICAL LEVELS ON PAGE |
| G-008. |
| |
| 10. FIRE RATED WALLS APPEAR TO BE ONE HOUR BETWEEN |
| GARAGE AND OTHER AREAS ON PAGE G-008. |
| |
| 11. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON SECOND |
| LEVEL ON PAGE G-008. |
| |
| 12. THE PROPOSED LIVE OAK TREE DISPLAYED ON LP1 SHALL |
| NOT OBSTRUCT OR INTERFERE WITH THE PROPOSED FIRE |
| DEPARTMENT CONNECTION SHOWN ON THE OLIVE AVENUE SIDE |
| ELEVATION. |
| |
| 13. WHAT CHEMICALS IF ANY OR ANY PLANNED TO BE STORED |
| IN THE SPA EQUIPMENT ROOM 141 ON PAGE AC-103. IF |
| CHEMICALS ARE PLANNED WHAT TYPES AND WHAT QUANTITIES. |
| |
| 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| FOR ALL HANDRAILS AND GUARDRAILS PLANNED FOR THE |
| PROJECT. |
| |
| 15. ELEVATOR WARNING SIGNS WILL BE REQUIRED AT ELEVATOR |
| LOCATIONS. |
| |
| 16. PLEASE PROVIDE DETAILS ON FIRE SHUTTER CALLED OUT |
| ON PAGE A100C. |
| |
| 17. DOORS LOCATED ADJACENT TO STAIR # 1 AND STAIR # 2 |
| THAT MAY BE CONFUSED AS EXITS SHALL BE PROPERLY |
| IDENTIFIED WITH SIGNS INDICATING "NO EXIT". |
| |
| 18. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| WALLS AND CEILINGS. |
| |
| 19. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING |
| PARTITIONS IN MEETING ROOM 111 ON PAGE A-101A. |
| |
| 20. REFLECTED CEILING PLAN SYMBOLS DOES NOT IDENTIFY |
| WHAT A HALF DARKENED CIRCLE IS. PLEASE IDENTIFY AR |
| SHEETS. |
| |
| 21. BUILDING ADDRESS SHALL BE SHOWN ON PROPER EXTERIOR |
| ELEVATION DRAWING. |
| |
| 22. COULD NOT LOCATE ANY SMOKE DETECTOR IN KING |
| ELECTRICAL PLAN ON PAGE A-421. |
| |
| 23. ARCHITECTURAL SOFFIT SHALL NOT INTERFERE WITH ANY |
| OPERATION OF ANY FIRE SPRINKLER HEADS. |
| |
| 24. TRASH CHUTE TO COMPLY WITH NFPA 82. |
| |
| 25. DOOR SCHEDULE ON PAGE A-611 WILL HAVE INCORRECT |
| DOOR RATINGS DUE TO ONE HOUR WALLS WHEN TWO HOUR WALLS |
| SHOULD HAVE BEEN PROVIDED. |
| |
| 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, |
| DUCT, AND FIRE SUPPRESSION SYSTEM SHOWN ON PAGE E-202. |
| |
| 27. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| SYSTEM. FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE |
| MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR |
| CENTRAL STATION SERVICE. |
| |
| 28. PLEASE FURTHER DEFINE NOTE # 9 ON PAGE E-303. |
| |
| 29. SEPERATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| SPRINKLER SYSTEM. ENTIRE BUILDING SHALL BE COMPLETELY |
| FIRE SPRINKLER PROTECTED. THIS INCLUDES ALL VERTICAL |
| SHAFTS, ELECTRICAL, MECHANICAL AND ELEVATOR ROOMS. |
| |
| 30. FIRE PROTECTION SYSTEM GENERAL NOTES # 1 SHOULD |
| INCLUDE NFPA 20. |
| |
| 31. ALL FIRE DAMPERS ILLUSTRATED ON THE MECHAICAL PLANS |
| ARE TO BE DROP TESTED TO ENSURE PROPER OPERATION AFTER |
| INSTALLATION. |
| |
| 32. CARBON MONOXIDE DETECTORS ILLUSTRATED IN THE |
| PARKING GARAGE SHALL BE TESTED TO ENSURE PROPER |
| OPERATION. THESE DETECTORS SHALL BE TESTED WITH |
| CALIBRATION GAS AT THE PROPER SET POINT OF THE |
| DETECTORS. INFORMATION SHALL BE PROVIDED FOR THE CARBON |
| MONOXIDE DETECTORS SELECTED. |
| |
| 33. STAIRWELL IDENTIFICATION SIGNS REQUIRED. STAIR |
| IDENTITY, FLOOR LEVEL, TERMINUS TOP AND BOTTOM SHALL BE |
| PROVIDED. |
| |
| 34. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS |
| SHALL BE PROVIDED. |
| |
| 35. GAS EQUIPMENT AND RISER INSTALLATIONS TO COMPLY |
| WITH NFPA STANDARDS THAT ARE SHOWN ON PAGE P-602. |
| |
| 36. FIRE MARSHAL NOTES NOTED ON PLANS SHALL BE |
| FOLLOWED. |
| |