Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-24 09:05:031. FIRE AND LIFE SAFETY CODE 2004 FLORIDA BUILDING CODE
 SHOULD READ FLORIDA FIRE PREVENTION CODE ON PAGE
 G-000.
  
 2. FIRE WALL RATINGS BETWEEN PORTIONS OF THE HOTEL AND
 PARKING GARAGE APPEARS TO BE ONLY ONE HOUR RATED ON
 PAGE G-007. A TWO HOUR RATING IS REQUIRED BETWEEN
 PARKING GARAGES AND OTHER PORTIONS OF THE BUILDING.
  
 3. EXIT SIGN IN MEETING ROOM # 110 DIRECTS PERSONS INTO
 CLOSET ON PAGE G-007.
  
 4. SOME EXIT SIGNS APPEAR TO BE DIRECTING PERSONS TO
 EXIT INTO GARAGE. THE GARAGE IS A MORE HAZARSOUS AREA
 THAN THE HOTEL. PLEASE SEE PAGE G-007. EXITING IS NOT
 PERMITTED TO PASS INTO A MORE HAZARDOUS AREA.
  
 5. EXIT TRAVEL ROUTE ON PAGE G-007 IN GARAGE ON
 MEZZANINE LEVEL TRAVELS OVER COLUMN TO REACH STAIR #
 2.
  
 6. FIRE RATED WALLS BETWEEN GARAGE AND MEZZANINE ARE
 ONLY ONE HOUR ON PAGE G-007.
  
 7. OTHER EXIT ROUTE FROM GARAGE TOWARDS STAIR # 1
 APPEARS TO TRAVEL OVER A SHAFT, LIFE SAFETY MEZZANINE.
  
 8. TRAVEL DISTANCE ROUTE ON THE LIFE SAFETY, SECOND
 LEVEL APPEARS TO TRAVEL OVER PARKING STALLS ON PAGE
 G-008.
  
 9. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN
 CORRIDOR ON SECOND LEVELS AND TYPICAL LEVELS ON PAGE
 G-008.
  
 10. FIRE RATED WALLS APPEAR TO BE ONE HOUR BETWEEN
 GARAGE AND OTHER AREAS ON PAGE G-008.
  
 11. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON SECOND
 LEVEL ON PAGE G-008.
  
 12. THE PROPOSED LIVE OAK TREE DISPLAYED ON LP1 SHALL
 NOT OBSTRUCT OR INTERFERE WITH THE PROPOSED FIRE
 DEPARTMENT CONNECTION SHOWN ON THE OLIVE AVENUE SIDE
 ELEVATION.
  
 13. WHAT CHEMICALS IF ANY OR ANY PLANNED TO BE STORED
 IN THE SPA EQUIPMENT ROOM 141 ON PAGE AC-103. IF
 CHEMICALS ARE PLANNED WHAT TYPES AND WHAT QUANTITIES.
  
 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS PLANNED FOR THE
 PROJECT.
  
 15. ELEVATOR WARNING SIGNS WILL BE REQUIRED AT ELEVATOR
 LOCATIONS.
  
 16. PLEASE PROVIDE DETAILS ON FIRE SHUTTER CALLED OUT
 ON PAGE A100C.
  
 17. DOORS LOCATED ADJACENT TO STAIR # 1 AND STAIR # 2
 THAT MAY BE CONFUSED AS EXITS SHALL BE PROPERLY
 IDENTIFIED WITH SIGNS INDICATING "NO EXIT".
  
 18. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 19. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING
 PARTITIONS IN MEETING ROOM 111 ON PAGE A-101A.
  
 20. REFLECTED CEILING PLAN SYMBOLS DOES NOT IDENTIFY
 WHAT A HALF DARKENED CIRCLE IS. PLEASE IDENTIFY AR
 SHEETS.
  
 21. BUILDING ADDRESS SHALL BE SHOWN ON PROPER EXTERIOR
 ELEVATION DRAWING.
  
 22. COULD NOT LOCATE ANY SMOKE DETECTOR IN KING
 ELECTRICAL PLAN ON PAGE A-421.
  
 23. ARCHITECTURAL SOFFIT SHALL NOT INTERFERE WITH ANY
 OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 24. TRASH CHUTE TO COMPLY WITH NFPA 82.
  
 25. DOOR SCHEDULE ON PAGE A-611 WILL HAVE INCORRECT
 DOOR RATINGS DUE TO ONE HOUR WALLS WHEN TWO HOUR WALLS
 SHOULD HAVE BEEN PROVIDED.
  
 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEM SHOWN ON PAGE E-202.
  
 27. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM. FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 28. PLEASE FURTHER DEFINE NOTE # 9 ON PAGE E-303.
  
 29. SEPERATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM. ENTIRE BUILDING SHALL BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES ALL VERTICAL
 SHAFTS, ELECTRICAL, MECHANICAL AND ELEVATOR ROOMS.
  
 30. FIRE PROTECTION SYSTEM GENERAL NOTES # 1 SHOULD
 INCLUDE NFPA 20.
  
 31. ALL FIRE DAMPERS ILLUSTRATED ON THE MECHAICAL PLANS
 ARE TO BE DROP TESTED TO ENSURE PROPER OPERATION AFTER
 INSTALLATION.
  
 32. CARBON MONOXIDE DETECTORS ILLUSTRATED IN THE
 PARKING GARAGE SHALL BE TESTED TO ENSURE PROPER
 OPERATION. THESE DETECTORS SHALL BE TESTED WITH
 CALIBRATION GAS AT THE PROPER SET POINT OF THE
 DETECTORS. INFORMATION SHALL BE PROVIDED FOR THE CARBON
 MONOXIDE DETECTORS SELECTED.
  
 33. STAIRWELL IDENTIFICATION SIGNS REQUIRED. STAIR
 IDENTITY, FLOOR LEVEL, TERMINUS TOP AND BOTTOM SHALL BE
 PROVIDED.
  
 34. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS
 SHALL BE PROVIDED.
  
 35. GAS EQUIPMENT AND RISER INSTALLATIONS TO COMPLY
 WITH NFPA STANDARDS THAT ARE SHOWN ON PAGE P-602.
  
 36. FIRE MARSHAL NOTES NOTED ON PLANS SHALL BE
 FOLLOWED.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4776 FAX