2008-02-25 12:23:54BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL. PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL.106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) INFORMATIONAL. PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3*BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 ICC TOTAL VALUATION FOR PROJECT IS $18,616,066.00
  
 MINUS VIBRO-FLOTATION& STRUCTURAL-3,941,840.00
 VALUATION FOR THIS PERMIT $
 14,674,226.00
  
 FEES DUE THIS PERMIT
 $163,439.36
 PAID TO DATE
 $45,493.17
 FEE BALANCE
 $117,946.19
 SEE FEE BALANCE SHEET ATTACHMENT.
  
 3) SHEET A-101A:
 3A) WHEN THE CONFERENCE ROOMS 110, 111 & 117 ARE OPENED
 INTO ONE LARGE CONFERENCE ROOM THE OCCUPANT LOAD WOULD
 BE 68 REQUIRING 2 EXITS. WHEN AN ASSEMBLY OCCUPANCY IS
 OVER 30 OCCUPANTS THE EXIT ACCESS CORRIDORS ARE
 REQUIRED TO BE FIRE RATED 1 HOUR EVEN WITH FIRE
 SPRINKLERS PLEASE SEE TABLE 1016.1.
  
 3B) THE OTHER CONCERN IS WITH THE RATING OF THE
 CORRIDOR, PLEASE REVIEW 1016.5 CONTINUITY OF CORRIDORS
 AND THE FIRE RATING INTO THE LOBBY AND RECEPTION AREAS.
 THIS WILL ALSO EFFECT THE DOOR RATINGS IN TABLE 715.3,
 PROTECTION OF OPENINGS.
  
 3C) THE FIRST FLOORDOORS CAN NOT BE CHECKED IN THE
 DOOR SCHEDULE SHEET A-611, THE NUMBERING SEQUENCE IS SO
 FAR OVER INTO THE LEFT MARGIN OF THE SHEET THAT THE
 NUMBERING SEQUENCE COLUMN IS BOUND BY THE STAPLES,
 PLEASE REPRINT THIS SHEET AND ALLOW FOR BINDING OF
 PLANS TOGETHER. 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF WORK PROPOSED AND
 SHOW IN DETAIL THAT IT CONFORMS TO THE PROVISIONS OF
 THIS CODE.
  
 3D) THE EXTERIOR NORTH WALL OF THE BUILDING INDICATES
 WALL TAGS OF 1 HOUR RATING, PLEASE REVIEW TABLE 602 , <
 5?-0? REQUIRES A 3 HR RATED WALL FOR THESE
 OCCUPANCIES:
 ASSEMBLY, BUSINESS OR RESIDENCE. PLEASE CORRECT PLAN.
  
 3E) ADDITIONAL INFORMATION REQUIRED, 106.1.2. OCCUPANCY
 SEPARATION, WALL TAGS ARE MISSING ON THE COMMON PARKING
 GARAGE AND THE OTHER OCCUPANCIES, PLEASE SEE
 TABLE302.3.2.
  
 3F) PLEASE REVIEW THE ELEVATOR WALLS FOR WALL
 IDENTIFICATION TAGS INDICATING THE RATING FOR SHAFTS,
 SEE 707.4.
  
 3G) THE MAIN ENTRY DOOR 131 APPEARS TO BE A PASSENGER
 LOADING ZONE WITH A VALET SERVICE AND LUGGAGE AREA. THE
 PLANS DO NOT INDICATE A DROPPED CURB NOR A PASSENGER
 LOADING ZONE.
 11-4.1.2(5)?. ALSO SEE 11-4.2.9.5 DETECTABLE WARNING
 DEVISES.
  
 3H) THE DISABLED PARKING SPACE, WEST END OF, INDICATES
 A RAMP NO INFORMATION ON HEIGHT OF RAMP, CHANGE IN
 GRADE SEE 11-4.8(1-6).
  
 3I) RESTROOMS 112 & 113 ARE INDICATED AS DETAIL# 2
 SHEET A-403, PLEASE CORRECT TO A-402.
  
 3J) RESTROOMS 112 & 113 PLEASE PROVIDE IN DETAIL THE
 CLEAR WIDTH OF THE ACCESSIBLE STALL DOOR, PLEASE SEE
 FIGURE 30E.
  
 3K) 106.1.2 ADDITIONAL INFORMATION REQUIRED, WHAT IS
 THE PURPOSE OF THE E-ROOM?
  
 3L) PLEASE PROVIDE STAIR IDENTIFICATION 1009.5.3
  
 3M) PLEASE REVIEW STAIR ACCESS TO ROOF BUILDINGS IN
 BUILDINGS 4 STORIES AND MORE, 1009.12..
  
 3N) THERE APPEARS TO BE A RAMP IN FRONT OF DOOR# 114,
 THIS RAMP DOES NOT PROVIDE THE MAXIMUM ALLOWABLE SLOPE
 INFORMATION, HANDRAILS OR BOTTOM LANDING INFORMATION,
 PLEASE SEE 11-4.8.
  
 3O)THIS PLAN INDICATES THE USE OF AN EMERGENCY
 GENERATOR PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 GENERATOR AND FUEL SUPPLY TANK. QUANTITY OF FUEL THAT
 IS TO BE STORED ON SITE AND TYPE OF VAULT. DOES THIS
 FUEL TANK HAVESECONDARY CONTAINMENT?
  
 4) SHEET A-101B
 4A) THE NORTH AND EAST PROPERTY LINE WALLS HAVE WALL
 IDENTIFICATION TAGS 1-B, PLEASE SEE
 TABLE 602 FOR WALLS LOCATED LESS THAN 5?-0? FROM THE
 PROPERTY LINE. TABLE 602 INDICATES
 A 3HOUR WALL.
  
 4B) PLEASE LOOK AT THE DOOR # 149 IN THE DOOR SCHEDULE,
 SCHEDULE INDICATES NO FIRE RATING,
 1016.1 ANDTABLE 302.3.2 OCCUPANCY SEPARATION, OPENING
 PROTECTIVE TABLE 715.3 .
  
 4C) RAMP FROM DOOR# 149 TO THE EXTERIOR, THE PLANS ARE
 MISSING THE TOP TURNING RADIUS.
 PLEASE SEE 11-4.8.4(3).
  
 4D) RAMP FROM DOOR # 149 IS MISSING THE HANDRAILS
 REQUIRED BOTH SIDES11-4.8.5.
  
 4E) RAMP BY DOOR 149 DOES NOT INDICATE THE BOTTOM
 LANDING, 11-4.8.4(2).
  
 4F) RAMP BY DOOR# 149 PLEASE PROVIDE THE CLEAR
 DIMENSION AT THE BOTTOM OF THE RAMP FROM COLUMN TO
 COLUMN. 11-4.8.3 WHEN PART OF A MEANS OF EGRESS MINIMUM
 OF44? CLEAR.
  
 4G) RAMP BY DOOR# 149 INDICATES A SLOPE OF 8% PLEASE
 SEE 11-4.8.2 THE MAXIMUM SLOPE OF A RAMP IN NEW
 CONSTRUCTION SHALL BE 1 TO 12.
  
 4H)EAST SIDE OF THE BUILDING ROOM 103 THE EMERGENCY
 GENERATOR ROOM INDICATES OPENINGS IN THE WALL, PLEASE
 SEE TABLE 602 LESS THAN FIVE FOOT FROM THE PROPERTY
 LINE, NO OPENINGS.
  
 4I) COMPACTOR DETAIL FOUND ON SHEET AC-102 DETAIL 9
 INDICATES THE USE OF A SCISSOR LIFT, PLEASE PROVIDE
 ADDITIONAL INFORMATION.106.1.2.
  
 4J) PLEASE PROVIDE STAIR IDENTIFICATION 1009.5.3
  
 4K) PLEASE REVIEW STAIR ACCESS TO ROOF BUILDINGS IN
 BUILDINGS 4 STORIES AND MORE, 1009.12..
  
  
 5)SHEET A-102A
 5A) PLEASE PROVIDE AREA CALCULATIONS HOW THIS LEVEL
 CLASSIFIES AS A MEZZANINE?505.2 AREA LIMITATION.THE
 AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN A
 ROOM SHALL NOT EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
  
 5B)DOORS ON THE A-102A & A-102B FLOOR PLANS DO NOT
 SHOW UP ON THE DOOR SCHEDULE
 SHEET A-611, PLEASE CORRECT, THIS SHEET CAN NOT BE
 CHECKED FOR OPENING PROTECTIVES
 TABLE 715.3.
  
 5C) THIS COMMENT WILL NOT BE REPEATED FOR EVERY CASE
 BOTH SHEET A-102A AND A-102B THE NORTH AND EAST
 PROPERTY LINES ARE LESS THAN 5?-0? FROM THE PROPERTY
 LINE REQUIRING 3 HR FIRE RATING. SEE TABLE 602.
  
 5D) THERE IS A ROOM NOT IDENTIFIED, DOOR 155A LEADS
 INTO THIS AREA. PLEASE PROVIDE ADDITIONAL INFORMATION
 106.1.2.
  
 5E) ADDITIONAL INFORMATION REQUIRED 106.1.2. ON SHEET
 A-101A THERE ARE ROOMS 118-123
 THE NEXT LEVEL UP (SHEET A-102A) THE PLAN INDICATES
 CEILING BELOW BUT THERE IS NO CUT SECTIONS OF THIS AREA
 INDICATING HEIGHT OF THE CEILING OR MATERIAL. PLEASE
 PROVIDE HEIGHT OF THE CEILING AND STRUCTURAL COMPONENTS
 OF THIS SYSTEM.
  
 6) A-102B
 6A) THE ROOMS BELOW (105-108) ARE INDICATED AS CEILING
 BELOW, PLEASE PROVIDE A CUT SECTION THROUGH INDICATING
 TYPE OF CEILING, HEIGHT OF CEILING AND TYPE OF
 STRUCTURAL COMPONENTS. 106.1.2.
  
 6B) IN THE SAME ROOMS MENTIONED ABOVE THE PLANS APPEAR
 TO HAVE (3) CHASES IN THE CENTER OF THIS AREA? PROVIDE
 MORE DETAILS AND FIRE RATINGS. 106.1.2. ? 712.4.
  
 6C) THERE IS A CONCRETE WALL ON GRID LINE B.4 BETWEEN
 COLUMN LINE 2-3. THIS SHOULD BE A GUARD RAIL AS WELL AS
 VEHICLE BARRIER, PLEASE PROVIDE COMPLIANCE WITH
 1607.7.3
  
 6D) THE OTHER AREA OF CONCERNS WITH GUARDS WOULD BE THE
 DROP OFF EDGE WHERE THE RAMP RISES AND OR FALLS TO THE
 NEXT LEVEL. PLEASE PROVIDE COMPLIANCE WITH 1607.7.3.
  
 6E) THE NORTHEAST CORNER OF THE GARAGE THERE APPEARS TO
 BE A SHAFT BUT NO WALL TAGS.
 707.4.
  
 6F) CORRIDOR M114 IS INDICATED AS A 1 HR RATED WALL
 WITH NO DOORS SEPARATING THE GARAGE FROM THE CORRIDOR.
 106.1.2.
  
 7) SHEET A-103A:
 7A) EXIT WAY# 230 IS INDICATED AS NON RATED WALLS, THE
 MECHANICAL SHEETS INDICATE FIRE DAMPERS, SEE TABLE
 1016.1 FOR FIRE RATINGS.
  
 8) SHEET A-103A
 8A) ELEVATOR LOBBY 240, THIS COMMENT WILL STAND FOR ALL
 FLOORS WITH R1 TYPE OCCUPANCY.
 PLEASE SEE REQUIRED 1 HOUR RATING & OPENING PROTECTION,
 707.14.1, TABLE 1016.1 AND THE CODE COMMENTARY FOR
 REQUIREMENTS FOR A 1 HR FIRE RATING, THIS COMMENT WILL
 STAND FOR ALL COMMON FLOORS.
  
 8B)STAIR TOWER# 2 INDICATES TWO METAL STUD WALLS IN
 THE INTERIOR OF THE STAIR TOWER ONE SEPARATES THE
 STAIRS FROM THE ELECTRIC ROOM PLEASE IDENTIFY WALL TYPE
 AND HOURLY RATING, 707.4 THIS COMMENT WILL STAND FOR
 THE COMMON FLOORS.
  
 8C) STAIR TOWER# 2 INDICATES TWO METAL STUD WALLS IN
 THE INTERIOR OF THE STAIR TOWER ONE SEPARATES THE
 STAIRS FROM WHAT APPEARS TO BE A SHAFT WITHIN THE STAIR
 TOWER, PLEASE IDENTIFY WALL TYPE AND HOURLY RATING,
 707.4. THIS COMMENT WILL STAND FOR ALL COMMON FLOORS.
  
 8D) LAUNDRY ROOM 235 DOES NOT HAVE A TERMINATION ROOM
 AS REQUIRED IN 707.13.4.THE TERMINATION ROOM SHALL
 HAVE OPENING PROTECTION NOT LESS THAN ? HOURS AND BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 8E) LAUNDRY ROOM ITSELF WOULD NORMALLY ONLY REQUIRE THE
 WALLS TO BE SMOKE RATED, AS THE WALLS THAT ARE SHARED
 BY THE TRAINING AND HOUSE KEEPING ROOMS, PLEASE NOTE
 THAT NON OF THE NON-RATED WALL TYPES ARE SPECIFIED AS
 SMOKE PARTITIONS SEE SECTION 710. IN THIS CASE THE
 LAUNDRY ROOM WALLS THAT ARE COMMON TO THE EXIT ACCESS
 CORRIDOR WILL NEED TO BE 1 HR FIRE RATING BECAUSE OF
 THE R1 OCCUPANCY, TABLE 1016.1.
  
 8F) DOOR 230A IS STILL PART OF THE 1 HR RATED EXIT
 ACCESS CORRIDOR THAT LEADS TO THE VERTICAL EXIT
 STAIRWELL, THE DOOR SCHEDULE INDICATES THIS DOOR NOT
 RATED, PLEASE CORRECT, TABLE 1016.1/ TABLE 715.3
 OPENING PROTECTIVE.
  
 8G) DOOR 230A APPEARS TO BE MISSING THE REQUIRED 18? ON
 THE PULL, LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 8H) LAUNDRY ROOM PLAN IS MISSING THE THROUGH
 PENETRATIONS (2-LOUVERS) IN THE RATED WALL
 COMMON WITH THE GARAGE. OPENING PROTECTION IS REQUIRED,
 SEE TABLE 715.3.
  
 8I) BETWEEN UNITS THERE ARE QUITE A FEW WALLS THAT DO
 NOT HAVE WALL IDENTIFICATION TAGS,
 SEE 1207.2. THIS COMMENT WILL STAND FOR ALL
 SHEETS.
  
 9) SHEET A-103B:
 9A) DOOR# 237APPEARS TO BE MISSING THE REQUIRED 18?
 ON THE PULL, LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 9B) LAUNDRY ROOM 238 INDICATES ON THE MECHANICAL SHEETS
 DRYER EXHAUST PENETRATINGA 1HR FIRE RATED WALL
 INDICATE OPENING PROTECTION, TABLE 715.3.
  
  
  
 10) A-104A COMMON TO THE 3RD, 4TH & 5TH FLOORS.
 10A) ROOM# 450 VENDING / ICEAND ROOM 451LINEN ROOM
 THIS COMMON WALL IS PART OF THE
 1 HR RATED CORRIDOR IS MISSING WALL TAG, TABLE 715.3.
  
 10B) THE LAUNDRY ROOM DOOR IS ALSO THE LAUNDRY CHUTE
 ACCESS DOOR REQUIRING A ? HR OPENING PROTECTIVE AND BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
 IS FOR ALL COMMON FLOORS. NOT 20 MINUTE AS INDICATED IN
 THE DOOR SCHEDULE, PLEASE CORRECT& SEE 707.13.4. THIS
 COMMENT IS FOR ALL COMMON FLOORS.
  
 10C)THE LAUNDRY ROOM ACCESS ROOM ALSO IS MISSING THE
 WALL RATINGS OF BOTH SHAFT ENCLOSURES IN THIS ROOM.
 707.4. SHAFTS. THIS COMMENT IS FOR ALL COMMON FLOORS.
  
 10D)BETWEEN UNITS 433 & 436 AT THE SHOWER LOCATIONS
 THE PLANS INDICATE A WALL TAG
 ?OC? NON-RATED WALL. 708.1(2) , 708.3 & 708.4.
  
 10E) THE UNIDENTIFIED ROOM JUST LEFT OF STAIR TOWER# 2
 HAS A 25X45 MECHANICAL CHASE, THE SHAFT WALLS ARE NOT
 IDENTIFIED WITH WALL TAGS. SEE 707.4.
  
 10F) PLEASE IDENTIFY THE USAGE OF ROOM LISTED ABOVE.
 106.1.2.
  
 11) SHEET A-104B COMMON TO 3RD, 4TH & 5TH FLOORS.
 11A) THIS SHEET THERE ARE NO WALL TAGS IDENTIFYING WALL
 RATINGS. TABLE 1016.1, 708.1(2), 708.3 & 708.4.
  
 11B) STAIR TOWER# 1 INDICATES A SHAFT LOCATED WITHIN
 THE STAIR TOWER, SEE 707.4 & 1019.1.2.
  
 11C) PLANS INDICATE A CHASE OR SHAFT IN THE ELECTRIC
 ROOM 402, PLEASE SEE 707.4.
  
 11D)THE EAST ELECTRICAL ROOM AND STORAGE ROOM DOORS
 AND HALLWAY DOOR DO NOT HAVE IDENTIFICATION TAGS, FIRE
 RATINGS? THIS IS A 1HR FIRE RATED CORRIDOR. TABLE
 1016.1. THE CORRIDOR WIDTH IN THE UPPER DETAIL IS NOT
 PROVIDED?CONSIDER DOOR WIDTH VERSES CORRIDOR WIDTH.
 1005.2DOOR ENCROACHMENT.
  
 12) SHEET A-105A:
 12A) NO ROOF ACCESS SEE COMMENT (3M) FOR STAIR ACCESS
 TO ROOF. 1009.12.
  
 13) SHEET A-105B:
  
 13A) THE STAIRWELL# 2 IS NOT DEPICTED AS GOING THROUGH
 TO THE ROOF LEVEL,SEE 1009.12.
  
  
 13B) THERE IS NO ROOF PLAN OF STAIR# 2 INDICATING THAT
 DOES GO TO THE ROOF AND DOOR TO THE
 ROOF LEVEL, THE DOOR SCHEDULE ALSO WILL NEED TO REFLECT
 THIS DOOR AND FIRE RATING, 106.1.2,
 & TABLE 715.3 OPENINGPROTECTION.
  
 14) SHEET A-202, A-203 & A-204 ALL FAIL TO INDICATE THE
 STAIRWELL# 2 CONTINUING THROUGH TO THE ROOF LEVEL.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2 & 1009.12.
  
 15) SHEET A-307 DETAIL# 2 ON THE MEZZANINE AND 2ND
 FLOOR LEVELS INDICATE WHAT APPEARS TO BE CONCRETE KNEE
 WALLS WHERE IS THIS CUT SECTION TAKEN, SHEETS A-102A,
 A-102B, A-103A
 & A103B ALL INDICATE A 1HOUR RATED BLOCK WALL?
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 16)SHEET A-402 BUFFET PLEASE INDICATE COMPLIANCE WITH
 11-5.2, 11-5.4&11.5.5.
  
 17)SHEET A-428 INDICATES THE USE OF A FIRE SHUTTER AT
 THE ELEVATOR LOBBYPLEASE PROVIDE INFORMATION ON THE
 RATING OF FIRE SHUTTER AND COMPLIANCE WITH 715.3.9.
  
 18) SHEET A-429, A-430 &A-431 BOTH FAIL TO INDICATE
 OPENING PROTECTION AT THE ELEVATOR LOBBY.PLEASE SEE
 707.14.1.
  
 19) SHEET AR 401 DETAIL 3 INDICATES THE USE OF ACRYLIC
 PANELS PLEASE PROVIDE THE AREA WHERE THIS CEILING WILL
 TAKE PLACE AND HOW IT WILL BE HUNG? PLEASE PROVIDE THE
 SMOKE DEVELOPMENT AND FLAME SPREAD FOR THIS PRODUCT IN
 THIS APPLICATION. TABLE 803.5 & 803.1.
  
 20)PROVISO: EXTERIOR LIGHT GAUGE METAL FRAMING TO BE
 SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE
 DESIGNER OF RECORD REVIEW AND APPROVAL.
  
 21)A-511 FIN WALL DETAIL# 9 INDICATES THAT THE
 FINWALL FRAME IS TO BE ATTACHED TO THE STRUCTURE PER
 NOA REQUIREMENTS,THERE IS NO FIN WALL LISTED UNDER
 EITHER MIAMI-DADE OR
 THE FLORIDA STATE WEB SITE.THE PRODUCT TESTING REPORT
 WILL NEED TO HAVE THIS TYPE WINDOW APPLICATION TESTED
 AND SHOW THE REQUIRED ANCHORAGE.
 1714.5.4.1. WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER?S RECOMMENDATIONS TO ACHIEVE THE DESIGN
 PRESSURE SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED
 FOR SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 22)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 22A) STOREFRONT UNITS- OK COMPLIED
 22B) FIXED WINDOWS- TRACO WINDOWS DID NOT MEET THE -89
 IN END ZONES
 22B) HORIZONTAL SLIDING UNITS TRACO- CIRCLE GLAZING
 TYPE FOR PRESSUES
 22C) FINWALL WINDOW SYSTEMS- NO REPORT SUBMITTED
 22D) MULLIONS- PGT MULLIONS CIRCLE MULLION LENGTHS TO
 BE USED/ FOR PRESSURES
 22E) WALL LOUVERS- OK REVIEWED
 22F)EXTERIOR HOLLOW METAL DOORS, SINGLE & PAIR OF
 DOORS
 22G) EXTERIOR AUTOMATIC SLIDING DOORS- OK REVIEWED
 22H) EXTERIOR GLAZED SWING DOORS- OK COMPLIED
 22I)PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED
 22J) ROOFING ASSEMBLIES- CARLISLE REPORT, REQUIRES
 SHOP DRAWINGS AND AN APPROVED ROOFING
 CONTRACTOR TO BE SIGNED ON.
  
 23) FOR FLAT ROOF THESE ARE THE MOST COMMON MISTAKES IN
 SUBMITTING ROOFING REPORTS
 _XX__ THE SUB-SYSTEM PROVIDED IN THE REPORT IS NOT
 HIGHLIGHTED.
 __XX__ THE SUB-SYSTEM PICKEDHAS A LOWPRESSURE FOR
 ZONE _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTEREDPROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 __XX_ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 24)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 25) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 26) S-207 EAST ELEVATION PRESSURES ARE NOT PROVIDED FOR
 WALL LOUVER AT EAST LOWER LEFT
 ELEVATION.
  
 27) NOTE: AWNINGS REQUIRE A SEPARATE PERMIT. WILL NOT
 BE PART OF THIS REVIEW.
  
 28)SHEET A-711/ ELEVATORS:
 28A)BUILDINGS 4 STORIES IN HEIGHT, AT LEAST ONE
 ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CARS
 SHALL BE OF SUCH SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH AMBULANCE STRETCHER IN THE
 HORIZONTAL, OPEN POSITION AND SHALL BE IDENTIFIED BY
 THE INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE).
  
 28B)THERE IS NO FIRE ALARM PLANS AND THE ELECTRICAL
 PLANS DO NOT INDICATE THE USE OF SMOKE DETECTORS IN
 EACH LEVEL OF THE ELEVATOR LOBBIES NOR IN THE MACHINE
 ROOM. PLEASE SEE 3002.8.
 ALSO SEE THE REQUIREMENTS FOR IF HOIST-WAY IS OR IS NOT
 FIRESPRINKLED.
  
 28C)PLEASE SEE REQUIREMENTS FOR ELEVATOR VENTING FOR
 R! OCCUPANCIES 3 STORIES AND GREATER.3004.2 LOCATION
 OF VENTS
 3004.3 AREA OF VENTS
  
 29) SHEET A-513:
 29A) PLANS FAIL TO INDICATE THE USE OF FIRE SPRINKLERS
 AS REQUIRED IN 707.13.6 & 903.2.10.2.
  
 29B) PLANS INDICATE 2 SHAFTS IN THIS PLAN BOTH
 INDICATING THEY ARE 2 HR CONSTRUCTION, PLEASE PROVIDE
 AN ASSEMBLY NUMBER FORTHESE SHAFTS. 707.4.
  
 30) FP-205:
 30A) FP-205A IS THE FIRE SPRINKLER PLAN FOR THE ROOF
 LEVEL WEST PORTION OF THE BUILDING, NO INFORMATION IF
 FIRE SPRINKLERS WILL BE IN THE ELEVATOR SHAFT.
  
 30B) FP-205B THIS SHEET IS MISSING TOTALLY, STAIRWELL
 AND STANDPIPE THAT PROVIDES ROOF ACCESS.
  
 31) PLEASE COORDINATE PLANS BETWEEN A-101A AND FP-201 A
 DOOR 114 ON THE FP SWINGS AGAINST THE EGRESS FLOW, SEE
 1008.1.2.
  
 32) PLEASE PROVIDE FIRE ALARM INFORMATION 907.2.10.1.1.
 / 106.3.5.1.1(5) & (6) EARLY WARNING SYSTEMS. WILL ALSO
 REQUIRE A SEPARATE PERMIT AND REVIEW NOT UNDER THIS
 PERMIT.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  