Plan Review Notes For Permit 08010223 |
Permit Number |
08010223 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-02-05 09:57:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.SEE ENGINEERING FOR THE SPAN TUBE.2 1/2" EDGE | | DISTANCE REQUIRED; INSTALLATION SCHEDULE SPECIFIES 2". | | PLEASE REVISE. | | | | 2.SEE OPENING 1.A 2" EDGE DISTANCE REQUIRES A | | FACTOR OF .5, SEE SHEET 14.THEREFORE A 5' SPACING IS | | REQUIRED, NOT 10" AS SPECIFIED ON THE INSTALLATION | | SCHEDULE.PLEASE CHECK ALL OPENINGS AND REVISE.THIS | | COMMENT APPLIES TO OTHER OPENINGS. |
|