Plan Review Notes
Plan Review Notes For Permit 08010202
Permit Number 08010202
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-18 10:30:56***DENIED***
  
 1) PLEASE ILLUSTRATE THE LOCATION OF THE FIRE
 DEPARTMENT CONNECTION. KNOX LOCKING CAPS SHALL BE
 REQUIRED.
  
 2) PLEASE SHOW THE DOUBLE DETECTOR CHECK ASSEMBY OR
 APPROVED METHOD THAT PREVENTS SYSTEM WATER FROM
 CONTAMINATING THE CITY SUPPLY.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756