Plan Review Notes
Plan Review Notes For Permit 08010070
Permit Number 08010070
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-07 11:38:07****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER BARRIER
 REQUIRED FS553.844(5)(A). PROVIDE INFORMATION
 (PRODUCT APPROVAL OR SPECIFICATIONS) TO SHOW HOW YOU
 WILL COMPLY WITH THIS REQUIREMENT.INFORMATION IS
 AVAILABLE AT WWW.BOAF.NET, HURRICANE MITIGATION.
  
 A PRODUCT APPROVAL WAS PROVIDED BUT HOW THIS WILL BE
 IMPLEMENTED IS NOT CLEAR.TAPE THE JOINTS; FULL DECK,
 SELF ADHERED OVER A BASE SHEET?
  
 2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING INFORMATION
 ON THE APPLICATION, SEE ATTACHED POLICY; MEAN ROOF
 HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF EACH ROOF
 TYPE.ROOF PITCH INFORMATION IS REQUIRED TO DETERMINE
 CODE COMPLIANCE.
  
  
  
  