Plan Review Notes
Plan Review Notes For Permit 08010041
Permit Number 08010041
Review Stop M
Sequence Number 2
Notes
Date Text
2008-04-03 15:46:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) IN LAST MECHANICAL REVIEW I REQUESTED COOLING LOAD
 CALCULATIONS, WHAT HAS BEEN SUBMITTED IS A SIZING
 SUMMARY.
 UNDER 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A SUMMARY
 SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED BY THE
 ENGINEER AND HAS THE MINIMUM INFORMATION ON IT.
 **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING
 METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY
 BULB USED... **OUTDOOR WET BULB USED... **RELATIVE
 HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING
 REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN...
 **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)...
 **TOTAL COOLING REQUIRED WITH OUTSIDE AIR. PLEASE
 CORRECT.
  