Plan Review Notes For Permit 08010041 |
Permit Number |
08010041 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2008-04-03 15:46:29 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) IN LAST MECHANICAL REVIEW I REQUESTED COOLING LOAD | | CALCULATIONS, WHAT HAS BEEN SUBMITTED IS A SIZING | | SUMMARY. | | UNDER 2004 FBC 13-407.1.ABC.1 " EXCEPTIONS" A SUMMARY | | SHEET MAY BE SUBMITTED WHEN SIGNED AND SEALED BY THE | | ENGINEER AND HAS THE MINIMUM INFORMATION ON IT. | | **PROJECT NAME/OWNER... **PROJECT ADDRESS... **SIZING | | METHOD USED... **AREA IN SQUARE FEET... **OUTDOOR DRY | | BULB USED... **OUTDOOR WET BULB USED... **RELATIVE | | HUMIDITY... **INDOOR DRY BULB.... **TOTAL HEATING | | REQUIRED WITH OUTSIDE AIR... **TOTAL SENSIBLE GAIN... | | **TOTAL LATENT GAIN... **GRAINS WATER (DIFFERENCE)... | | **TOTAL COOLING REQUIRED WITH OUTSIDE AIR. PLEASE | | CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|