Plan Review Notes For Permit 08010010 |
Permit Number |
08010010 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2008-01-09 16:14:17 | *****DENIED***** | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | REFERENCED. | | | | 4.IS THE OCCUPANT LOAD LISTED ON SHEET 1 FOR THE | | BUILDING OR A TENANT SPACE? | | | | 5.SPECIFY THE INTERIOR FINISH FOR THE NEW PARTITION | | WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | EXTINGUISHER(S) FOR EACH TENANT SPACE. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS | | ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|