Plan Review Notes
Plan Review Notes For Permit 08010010
Permit Number 08010010
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-01-09 16:14:17*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIAL, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.IS THE OCCUPANT LOAD LISTED ON SHEET 1 FOR THE
 BUILDING OR A TENANT SPACE?
  
 5.SPECIFY THE INTERIOR FINISH FOR THE NEW PARTITION
 WALLS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) FOR EACH TENANT SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722