Plan Review Notes
Plan Review Notes For Permit 07120667
Permit Number 07120667
Review Stop M
Sequence Number 1
Notes
Date Text
2008-01-03 12:11:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) ENERGY CALCULATIONS LINE 10A IS SHOWING R-19 FOR
 UNDER ATTIC, TABLE 6C-1 ON BACK OF ENERGY CALCULATIONS
 STATES MINIMUM INSULATION FOR UNDER ATTIC IS R-30, SEE
 2004 FBC 13-604.1.C.1, PLEASE CORRECT.
  
 2) SHOW ATTIC INSULATION AND R. VALUE ON BUILDING PLAN
 PAGE 2, SEE 2004 FBC 13-604.1.C.1.
  
 4) PROVIDE RETURN AIR TO BEDROOMS, SEE 2004 FBC/R
 M1602.4.
  
 5) MECHANICAL PLAN SHOWS A 10" AND A12" DUCT GOING TO
 THE MIXING BOX NEAR THE AIR HANDLER, THIS APPEARS TO BE
 AN ERROR (SEE YELLOW HIGH LIGHT ON MECH. PLAN), SEE
 2004 FBC 106.1.1, PLEASE CORRECT.
  
 6) SHOW IN THE A/C EQUIPMENT SCHEDULE THE MODEL NUMBERS
 FOR THE AIR HANDLER AND CONDENSER UNIT, ALSO THE TOTAL
 BTU'S, SEE 2004 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]