 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES
 "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN
 BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS
 CLEAR,106.1.1 FBC AS AMENDED.
  
 2} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE
 PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS
 MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO
 NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL
 LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED,
 (SEE 1500 VA).
  
 3} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT
 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE
 SAME.
  
 4} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS.
  
 5} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT
 210.52(A)(1), IN THE DINING ROOM ON THE A/C WALL.
  
 6} NFPA-72 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET
 OF COOKING APPLIANCES BE SILENCING OR PHOTOELECTRIC.
 SEE 11.8.3.5(4).
  
 7} R313.1 SMOKE ALARMS.
 SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING
 LOCATIONS:
 1. IN EACH SLEEPING ROOM.
 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE
 VICINITY OF THE BEDROOMS.
 THE BACK BEDROOM DOES NOT HAE ONE "OUTSIDE".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718