| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES |
| "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN |
| BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS |
| CLEAR,106.1.1 FBC AS AMENDED. |
| |
| 2} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE |
| PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS |
| MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO |
| NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL |
| LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED, |
| (SEE 1500 VA). |
| |
| 3} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT |
| 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE |
| SAME. |
| |
| 4} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. |
| SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND |
| 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| |
| 5} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT |
| 210.52(A)(1), IN THE DINING ROOM ON THE A/C WALL. |
| |
| 6} NFPA-72 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET |
| OF COOKING APPLIANCES BE SILENCING OR PHOTOELECTRIC. |
| SEE 11.8.3.5(4). |
| |
| 7} R313.1 SMOKE ALARMS. |
| SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| LOCATIONS: |
| 1. IN EACH SLEEPING ROOM. |
| 2. OUTSIDE EACH SEPARATE SLEEPING AREA IN THE IMMEDIATE |
| VICINITY OF THE BEDROOMS. |
| THE BACK BEDROOM DOES NOT HAE ONE "OUTSIDE". |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |