2008-01-09 16:52:50 | RESIDENTIAL RENOVATION, BUILDING REVIEWCHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. THE PERMIT VALUATION NEEDS TO BE UPDATED TO |
| INCLUDE ALL SCOPE OF WORK TO BE PERFORMED, INCLUDING |
| BUILDING, PLUMBING, ELECTRICAL AND MECHANICAL WORK |
| SPECIFIED ON PERMIT APPLICATION AND PLANS. SEC. |
| 108.3 CITY AMENDMENTS OT FBC 2004. (REPEAT COMMENT). |
| |
| 2-PROVIDE ONLY THE INFORMATIONTHAT IS RELEVANT TO |
| THE SCOPE OF WORK TO BE PERFORMED.IF NOT WORK IS DONE |
| ON EXTERIOR WALLS, THEN EXTERIOR ELEVATIONS AND TYPICAL |
| WALL SECTIONS ARE NOT REQUIRED.THIS CONFUSES THE |
| SCOPE OF WORK TO BE PERFORMED ANDTOTAL PERMIT |
| VALUATION.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004. |
| |
| 3- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN.SOME DRAWINGS ARE |
| MISSING THE SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN.SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 4-DESIGNER OF RECORDTO REVIEW AND APPROVE IN |
| WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC. |
| 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 5- ENERGY CALCULATIONS: REVISE ITEM #10(A)AND TABLE |
| 6C-1.NEED R-30AS THE MINIMUM INSULATION. ALSO, |
| REVISE MINIMUM INSULATION FOR DUCT. SEE TABLE 6C-1 AND |
| COMMENTS BY MECHANICAL PLAN REVIEWER. |
| |
| 6-ACCORDING TO PERMIT APPLICATION SCOPE OF WORK |
| INCLUDES ONLY ONE WINDOW TO BE REPLACED.SEC. 507.3 |
| EXCEPTION #1 DOESN'T REQUIRE SHUTTERS IFLESS THAN 25% |
| OF THEHOUSE GLASS AREA IS REPLACED. |
| NOTE:IS HIGHLY RECOMMENDED TO PROTECT ALL OPENINGS, |
| BUT IS NOT REQUIRED FOR THE SCOPE OF WORKSTIPULATED |
| IN THE PERMIT APPLICATION. |
| |
| 7- PLEASE COORDINATE WITH ZONING REGARDING LOCATION OF |
| A/C UNITS AND REQUIRED SETBACKS. CALL CHRIS HOOPS AT |
| 805-6720 FOR REQUIRED INFORMATION. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |