2008-01-09 16:54:27 | RESIDENTIAL RENOVATION, BUILDING REVIEWCHECKLIST. |
| REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| |
| 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. THE PERMIT VALUATION NEEDS TO BE UPDATED TO |
| INCLUDE ALL SCOPE OF WORK TO BE PERFORMED, INCLUDING |
| BUILDING, PLUMBING, ELECTRICAL AND MECHANICAL WORK |
| SPECIFIED ON PERMIT APPLICATION AND PLANS.SEC. 108.3 |
| CITY AMENDMENTS OT FBC 2004. (REPEAT COMMENT). |
| |
| 2-PROVIDE ONLY THE INFORMATIONTHAT IS RELEVANT TO |
| THE SCOPE OF WORK TO BE PERFORMED.IF NOT WORK IS DONE |
| ON EXTERIOR WALLS, THEN EXTERIOR ELEVATIONS AND TYPICAL |
| WALL SECTIONS ARE NOT REQUIRED.THIS CONFUSES THE |
| SCOPE OF WORK TO BE PERFORMED ANDTOTAL PERMIT |
| VALUATION.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004. |
| |
| 3- IF ALL DOORS AND WINDOWS ARE EXISTING(SEE NOTE ON |
| SHEET 1 OF 3),THEN, WHY SUBMITTING PRODUCT APPROVAL |
| FOR EXTERIOR DOOR? |
| |
| 4- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN.SOME DRAWINGS ARE |
| MISSING THE SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| DESIGN.SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004. |
| |
| 5- ENERGY CALCULATIONS: REVISE ITEM #10(A)AND TABLE |
| 6C-1.NEED R-30AS THE MINIMUM INSULATION. ALSO, |
| REVISE MINIMUM INSULATION FOR DUCT. SEE TABLE 6C-1 AND |
| COMMENTS BY MECHANICAL PLAN REVIEWER. |
| |
| 6- PLEASE COORDINATE WITH ZONING REGARDING LOCATION OF |
| A/C UNITS AND REQUIRED SETBACKS. CALL CHRIS HOOPS AT |
| 805-6720 FOR REQUIRED INFORMATION. |
| |