2007-12-30 16:21:29 | |
| *** DENIED REVIEW *** |
| |
| 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| THE FOLLOWING CODE STATED ON PLANS FOR RELEVANT |
| DESIGN. |
| 2005 NFPA-70 |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION FOR TITLE |
| BLOCKS FOR ELECTRICAL ENGINEERING FIRM OF RECORD. |
| PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER |
| AS REQUIRED PER FS 471.023 AND FAC 61G15-23.002. |
| |
| 3) NOTE: PLEASE BE SURE TO INCLUDE ADDRESS OF APPLIED |
| PROJECT ON ALL SHEETS. PLEASE KNOW THE APPLIED ADDRESS |
| IS 501 7TH ST. |
| FBC 106.1.2, 106.5 ETC |
| |
| 4) NOTE: PLEASE CLARIFY WHAT APPEAR TO BE TWO DIFFERENT |
| SYSTEM VOLTAGES IN THE GUTTER ON 1-E-1CR. |
| PLEASE SEE FOR EXAMPLE PANEL 17PL SHOWS CONNECTION |
| POINTS FROM TRANSFORMER AND GUTTER. THIS GUTTER |
| THERE-FORE SHOWS ELECTRICAL FROM TWO SYSTEMS. |
| PLEASE PLACE NOTE ON PLANS FOR CONDUCTORS PER 300.3C. |
| |
| 5) NOTE: PLEASE SUBMIT WIND LOAD FOR LIGHT POLES FOR |
| FBC 140MPH. |
| THE ENGINEERING CALCULATIONS WILL BE REVIEWED BY THE |
| BUILDING REVIEWER. |
| ** THIS IS NOTED FOR INFORMATION REQUIRED** |
| |
| 6) NOTE: PLEASE BE SURE TO INDICATE AIC RATINGS FOR ALL |
| ELECTRICAL SERVICE EQUIPMENT. |
| 110.3 |
| |
| 7) NOTE: PLEASE PROVIDE LOAD CALCULATIONS FOR THE |
| EXISTING MDP WHICH NEW ELECTRICAL LOADS ARE BEING FED |
| FROM. |
| 220 |
| FBC 106.3.5.1.2 |
| |
| |
| |
| ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE |
| ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |