Plan Review Notes
Plan Review Notes For Permit 07120631
Permit Number 07120631
Review Stop E
Sequence Number 1
Notes
Date Text
2007-12-30 16:21:29 
 *** DENIED REVIEW ***
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING CODE STATED ON PLANS FOR RELEVANT
 DESIGN.
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE MISSING INFORMATION FOR TITLE
 BLOCKS FOR ELECTRICAL ENGINEERING FIRM OF RECORD.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 AS REQUIRED PER FS 471.023 AND FAC 61G15-23.002.
  
 3) NOTE: PLEASE BE SURE TO INCLUDE ADDRESS OF APPLIED
 PROJECT ON ALL SHEETS. PLEASE KNOW THE APPLIED ADDRESS
 IS 501 7TH ST.
 FBC 106.1.2, 106.5 ETC
  
 4) NOTE: PLEASE CLARIFY WHAT APPEAR TO BE TWO DIFFERENT
 SYSTEM VOLTAGES IN THE GUTTER ON 1-E-1CR.
 PLEASE SEE FOR EXAMPLE PANEL 17PL SHOWS CONNECTION
 POINTS FROM TRANSFORMER AND GUTTER. THIS GUTTER
 THERE-FORE SHOWS ELECTRICAL FROM TWO SYSTEMS.
 PLEASE PLACE NOTE ON PLANS FOR CONDUCTORS PER 300.3C.
  
 5) NOTE: PLEASE SUBMIT WIND LOAD FOR LIGHT POLES FOR
 FBC 140MPH.
 THE ENGINEERING CALCULATIONS WILL BE REVIEWED BY THE
 BUILDING REVIEWER.
 ** THIS IS NOTED FOR INFORMATION REQUIRED**
  
 6) NOTE: PLEASE BE SURE TO INDICATE AIC RATINGS FOR ALL
 ELECTRICAL SERVICE EQUIPMENT.
 110.3
  
 7) NOTE: PLEASE PROVIDE LOAD CALCULATIONS FOR THE
 EXISTING MDP WHICH NEW ELECTRICAL LOADS ARE BEING FED
 FROM.
 220
 FBC 106.3.5.1.2
  
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE
 ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]