Plan Review Notes
Plan Review Notes For Permit 07120627
Permit Number 07120627
Review Stop P
Sequence Number 1
Notes
Date Text
2008-01-04 14:33:28PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FOR THE
 SHOWER ON THE RESUBMITTAL.
 A} 417.4.1 WALL AREA.
 THE WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER
 HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED
 OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF
 MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT
 THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT
 WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR
 SHOWER FLOOR.
  
 B} 424.3 SHOWER VALVES.
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR CSA B125.
  
 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]