2008-01-04 14:33:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| PLUMBING PLAN REVIEW: |
| DENIED: |
| |
| 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FOR THE |
| SHOWER ON THE RESUBMITTAL. |
| A} 417.4.1 WALL AREA. |
| THE WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER |
| HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED |
| OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF |
| MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM) |
| ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT |
| THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT |
| WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR |
| SHOWER FLOOR. |
| |
| B} 424.3 SHOWER VALVES. |
| SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE |
| BALANCED PRESSURE, THERMOSTATIC OR COMBINATION |
| BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| THE REQUIREMENTS OF ASSE 1016 OR CSA B125. |
| |
| 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| SECTION *106.3.4.3. |
| IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| |
| END OF COMMENTS: |
| |