2007-12-27 15:34:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PROPOSED FLOOR PLAN SHOWS TWO NEW SUPPLY AIR GRILLS
 AND ONE NEW RETURN AIR GRILL. PLEASE SHOW ON PLAN ALL
 NEEDED SUPPLY AND RETURN AIR GRILLS, LISTED AS NEW OR
 EXISTING FOR NEW OFFICES 1, 2, 3, AND TRAINING ROOM.
 SHOW ALL NEW DUCT SIZES AND CFM'S. SEE 2004 FBC/M 401.2
 AND 601.4.
  
 2) PLAN ALSO SHOWS NEW DOORS BEING INSTALLED IN
 EXISTING OFFICES 4, 5, 6, AND LOBBY. IF DOORS ARE
 REPLACEMENTS PLEASE STATE SO ON PLAN, IF NOT, SHOW
 SUPPLY AND RETURN AIR TO THESE IN-CLOSED SPACES, LISTED
 AS NEW OR EXISTING. SEE 2004 FBC/M 401.2 AND 601.4.
  
 MECHANICAL PLAN REVIEW BY;