| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| NONCOMPLIANT WITH THE FOLLOWING: |
| |
| 1} 13-415.1.ABC.1.2 SPACE CONTROL. |
| EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A |
| CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY |
| TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS |
| LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL, |
| IN THE FOLLOWING: |
| 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| CLASSROOMS) |
| 2. CONFERENCE/MEETING ROOMS. |
| 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| |
| PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE PUT A ON |
| THE PLAN FOR CLARITY IN THE FIELD. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |