Plan Review Notes
Plan Review Notes For Permit 07120601
Permit Number 07120601
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-04 12:56:19 
  
 BUILDING PLAN REVIEW
 PERMIT: 07120601
 ADD: 900 S. DIXIE HWY.
 CONT: MINUTEMAN CONST.
 TEL: (561)791-1637
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 1-4-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN
 SHOWING WHERE ALL THE CHANGES ARE MADE. THE PLANS
 SUBMITTED SHOW THE SAME FLOOR LAY-OUT. PROVIDE A WALL
 LEGEND INDICATING ALL WALLS TO BE DEMOED AND ALL NEW
 WALLS. SHOW THE ATTACHMENT DETAIL FOR THE NEW WALLS,
 AND INDICATE IF THE WALL WILL BE ATTACHED TO THE
 STRUCTURE ABOVE. A REFLECTED CEILING PLAN IS REQUIRED
 WITH THE HEIGHT AND TYPE OF CEILING TO BE INSTALLED
 THROUGH-OUT THE AREA. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISION OF THIS CODE. FBC
 106.1.1.
  
 3) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY. A FINISH SCHEDULE
 SHALL BE SUBMITTED FOR EACH ROOM AFFECTED BY THE NEW
 CONSTRUCTION.
  
 4)FBC 11-7.2(2)(I) A PORTION OF THE RECEPTIONIST
 COUNTER SHALL HAVE A MINIMUM OF 36 INCHES IN LENGTH AND
 SHALL HAVE A MAXIMUM HEIGHT OF 36 INCHES. PROVIDE AN
 ELEVATION DETAIL DRAWING SHOWING COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]