| BUILDING PLAN REVIEW |
| PERMIT: 07120601 |
| ADD: 900 S. DIXIE HWY. |
| CONT: MINUTEMAN CONST. |
| TEL: (561)791-1637 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2007 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW: 1ST |
| ACTION: DENIED |
| 1-4-08 |
| |
| 1A)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| YOUR ANTICIPATED COOPERATION. |
| |
| 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 2)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN |
| SHOWING WHERE ALL THE CHANGES ARE MADE. THE PLANS |
| SUBMITTED SHOW THE SAME FLOOR LAY-OUT. PROVIDE A WALL |
| LEGEND INDICATING ALL WALLS TO BE DEMOED AND ALL NEW |
| WALLS. SHOW THE ATTACHMENT DETAIL FOR THE NEW WALLS, |
| AND INDICATE IF THE WALL WILL BE ATTACHED TO THE |
| STRUCTURE ABOVE. A REFLECTED CEILING PLAN IS REQUIRED |
| WITH THE HEIGHT AND TYPE OF CEILING TO BE INSTALLED |
| THROUGH-OUT THE AREA. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISION OF THIS CODE. FBC |
| 106.1.1. |
| |
| 3) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| REQUIREMENTS BASED ON OCCUPANCY. A FINISH SCHEDULE |
| SHALL BE SUBMITTED FOR EACH ROOM AFFECTED BY THE NEW |
| CONSTRUCTION. |
| |
| 4)FBC 11-7.2(2)(I) A PORTION OF THE RECEPTIONIST |
| COUNTER SHALL HAVE A MINIMUM OF 36 INCHES IN LENGTH AND |
| SHALL HAVE A MAXIMUM HEIGHT OF 36 INCHES. PROVIDE AN |
| ELEVATION DETAIL DRAWING SHOWING COMPLIANCE. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |