Plan Review Notes For Permit 07120591 |
Permit Number |
07120591 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-12-26 16:43:29 | ELECTRICAL PERMIT REQUIRED FOR NEW EXIT LIGHTS AND | | EMERGENCY LIGHTS. | | | | CIRCUITING REQUIRED PER 700.12F WHICH REQUIRES THE TEMP | | EXIT/EMLIGHTS TO BE CIRCUITED TO THE LOCAL LIGHTING | | BRANCH CIRCUIT(S). | | TEMP LIGHTING IN SPACE TO BE PROVIDED PER LS 101 7.8 | | AND 7.9 WHICH MAY BE OCCUPIED W.BATTERY BACK UP. |
|