2008-08-29 09:34:52 | ** DENIED REVISION ** |
| |
| |
| |
| 1) NOTE: PLEASE SEE SHEET E6.1 WHICH INDICATES SEVERAL |
| LIGHTING CIRCUITS WHICH ARE NOT LISTED ON THE LIGHTING |
| CONTACTOR DETAIL. PLEASE SEE THE LIGHTING CONTACTOR |
| DETAIL AND SCHEDULE ONLY INDICATES TWO CIRCUITS. PLEASE |
| BE SURE TO COORDINATE WITH PLANS. |
| |
| ** CALLED ENGINEER AS OF REVIEW TO OVER COMMENTS |
| HOWEVER WAS OUT OF THE OFFICE. |
| |
| ** OTHER SHEETS MAY BE OK, HOWEVER IF NO OTHER CHANGES |
| ON OTHER SHEETS ARE NEEDED PLEASE BE SURE BRING BACK |
| SHEETS WITH THE SIGNED AFFIDAVITS. |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |