Plan Review Notes
Plan Review Notes For Permit 07120585
Permit Number 07120585
Review Stop E
Sequence Number 8
Notes
Date Text
2008-07-15 13:15:22** DENIEDREVISIONS **
  
  
 1) NOTE:THE SHEET E 6.1( REV 11) SUBMITTED NOW DOES
 NOT COORDINATE WITH THE PREVIOUS SUBMITTED POWER PLANS
 AND LIGHTING PLANS FOR CIRCUITING. PLEASE SUBMIT
 REVISED LIGHTING AND POWER PLANS WITH REVISED
 CIRCUITING ETC.
 408.4, 310.16, 240.4, 220, ETC
 FBC 106.1.2, 106.1.1
  
 PLEASE COORDINATE.
  
 2) NOTE: PLEASE EXPLAIN HOW/WHY THE DATE THE ENGINEER
 OF RECORD CONTAINS WHITE OUT AND IS DATED AFTER THE
 DATE OF BASE BUILDING DESIGNER AND ACTUAL DATE PLANS
 WERE SIGNED AND SEALED.
 SOME SHEETS ARE DATED 5/22 AND ONE SHEET CONTAINS THE
 WHITE OUT AND NEW DATE OF 6/4/08. NO INDIVIDUAL IS
 PERMITTED TO PLACE WHITE OUT ON PLANS AND MODIFY
 ANYTHING WHICH WAS DONE BY THE ENGINEER OF RECORD.
 FS 471.025
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717