Plan Review Notes
Plan Review Notes For Permit 07120585
Permit Number 07120585
Review Stop E
Sequence Number 2
Notes
Date Text
2008-02-11 09:07:19** DENIED REVIEW**
  
 1) NOTE: PLEASE SEE THE REQUIRED AFFIDAVIT AS REQUIRED
 PER FS 553.791(4)(C) WAS NOT SUBMITTED.
  
 2) NOTE: PLEASE KNOW THE LETTER OF AGREEMENT BETWEEN
 CONTRACTORS REQUIRED.
  
 3) NOTE: PLEASE SEE TWO FIXTURES MISSING DESIGNATIONS.
 PLEASE SEE ARE WORK AREA 771 AND ALSO FIXTURE IN
 BETWEEN CORRIDOR 778 AND 777.
 THESE COULD BE REDLINED AND PART OF A PROVISO HOWEVER
 THIS IS A PRIVATE PROVIDER PROJECT AND THIS MAY NOT BE
 DONE.
 PLEASE OBTAIN REVISED SHEET FOR LIGHTING IN ALL THREE
 SETS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  