2008-01-05 13:54:22 | REVIEW #: 1ST |
| ACTION: DENIED |
| |
| FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| |
| 1. PG M2.1 AND P2.1 SHOW NEW CONDENSER WATER AND |
| CONDENSATE LINES PENETRATING FIRE RESISTANCE RATED WALL |
| ASSEMBLIES. THESE PENETRATIONS ARE REQUIRED TO BE |
| PROTECTED BY A THROUGH-PENETRATION FIRESTOP SYSTEM IN |
| ACCORDANCE WITH FBC 712.3.1.2. THE ONLY |
| THROUGH-PENETRATION FIRESTOP SYSTEM SHOWN ON PLANS WAS |
| FOUND ON PG FS0.1 AND THIS SYSTEM IS NOT APPLICABLE |
| BECAUSE IT IS ONLY FOR STEEL PIPE OR EMT PENETRATING |
| CONCRETE WALLS AND FLOORS. CONDENSATE IS TO BE TYPE L |
| COPPER AS STATED IN MECHANICAL NOTE #17. CONDENSER |
| WATER MAY BE TYPE L COPPER AS STATED IN MECHANICAL NOTE |
| #27. PROVIDE DETAIL FOR A THROUGH-PENETRATION FIRESTOP |
| SYSTEM TO BE USED TO PROTECT THESE |
| THROUGH-PENETRATIONS, ENSURING THE SYSTEM IS |
| APPROPRIATE FOR THE TYPE OF MATERIAL PENETRATING THE |
| WALLS AS WELL AS THE TYPE OF WALL ASSEMBLY BEING |
| PENETRATED. |
| |
| 2. PG M2.1: A COMBINATION FIRE/SMOKE DAMPER IS SHOWN IN |
| THE 34X12 SUPPLY DUCT PENETRATING THE TENANT SEPARATION |
| WALL (AT APPROXIMATELY COLUMN LINE K.1). THERE ARE ALSO |
| 6 OTHER R/A FIRE/SMOKE DAMPERS SHOWN IN THE TENANT |
| SEPARATION WALLS. NONE OF THESE ARE PART OF THE |
| CONTROLS OR SEQUENCE OF OPERATIONS FOR THE BASE |
| BUILDING SMOKE CONTROL SYSTEM. THEY ARE ALSO NOT SHOWN |
| AS PART OF THE FIRE ALARM PLANS (SEE FA0.1 THROUGH |
| FA5.1). BY WHAT MEANS ARE THESE DAMPERS TO BE ACTUATED? |
| SHOW THE SMOKE DAMPER ACTUATION METHOD TO BE IN |
| COMPLIANCE WITH FBC, M 607.3.2.1. |
| NOTE: THESE DAMPERS ARE NOT LOCATED IN A SHAFT, RATED |
| CORRIDOR OR A SMOKE BARRIER. |
| |
| 3. PG A-7.7.3: EXTERIOR WALLS ABOVE CEILING WHICH ARE |
| EXPOSED TO THE RETURN AIR PLENUM SHALL BE LINED WITH AN |
| AIR BARRIER AND SEALED IN ACCORDANCE WITH FMC, M 603.9 |
| AND SHALL BE INSULATED IN ACCORDANCE WITH TABLE |
| 13-410.1.ABC.2.2 OF CHAPTER 13 OF THE FLORIDA BUILDING |
| CODE, BUILDING. SEE FBC, M 603.8. EXTERIOR WALLS |
| EXPOSED TO THE PLENUM SHALL BE INSULATED TO A MINIMUM |
| OF R-8, RATHER THAN THE R-4.2 AS SHOWN ON DETAILS 1 AND |
| 2 OF THIS PAGE. |
| |
| 4. AS THIS IS AN UNFINISHED SHELL BUILDING, THESE PLANS |
| ARE TO BE REVIEWED AND SIGNED BY THE BASE BUILDING |
| DESIGNER OF RECORD FOR CONFORMANCE WITH THE BASE |
| BUILDING DESIGN. THE MECHANICAL PLANS HAVE BEEN |
| INITIALED BY "TWJ" RATHER THAN DANIEL A. CAMPIA. PLEASE |
| CORRECT AND RESUBMIT. ALSO, PLEASE SEE PLUMBING |
| COMMENTS REGARDING THE REQUIRED LETTER OF UNDERSTANDING |
| TO BE SIGNED BY THE BASE BUILDING CONTRACTOR, BASE |
| BUILDING DEVELOPER AND THE TENANT CONTRACTOR TO BE |
| SUBMITTED WITH PERMIT APPLICATION. |
| NOTE: THESE REQUIREMENTS ARE BASED ON A POLICY |
| ESTABLISHED BY THE BUILDING OFFICIAL FOR THE PURPOSE OF |
| CREATING A SYSTEM BY WHICH TENANT IMPROVEMENT PERMITS |
| MAY BE ISSUED PRIOR TO COMPLETION OF THE SHELL/BASE |
| BUILDING. |
| |